| 1 | Providing & Fixing of on load change over switch, front handle operated, four pole 415 V confirming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating. |
| 2 | With OEM fabricated sheet steel enclosure, powder coated, door locking system allow opening of door in OFF position only with 2 nos external earthing points. |
| 3 | 125 A |
| 4 | SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 5 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 6 | (b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7 |
| 7 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 8 | (d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. |
| 9 | (e) Testing of earth resistance for value of 5 ohms or less as required. |
| 10 | (f) Test certificates for confirming above standards from OEM is mandatory. |
| 11 | 25 mm thick and 3 Mtr. Long |
| 12 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 13 | 16.0 Sq. mm |
| 14 | 4 core |
| 15 | 25.0 Sq. mm |
| 16 | 3.5 core |
| 17 | 70.0 Sq. mm |
| 18 | 3.5 core |
| 19 | S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required. |
| 20 | 2 x 10.0-16.0 sq.mm |
| 21 | 1 x 70 sq.mm-150 sq.mm |
| 22 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 23 | Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth. |
| 24 | Supply and filling of fresh transformer oil as per IS: 335 in existing transformer along with submission of oil test report for its physical and chemical properties.The oil shall be clear and free from any suspended matter or sediments complete as required complete in all respect. . |
| 25 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 26 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 27 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 28 | Four pole MCB (With B / C curve tripping characteristics) |
| 29 | 50/63 A rating |
| 30 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required. |
| 31 | Suitable for Two / Three / Four module for MCB |
| 32 | GST@18% Please Enable Macros to View BoQ information |