| 1 | Wiring for light point/exhaust Ceiling fan points/Inverter points with (P+N+E) in 3X1.5 sq.mm FRLS-H (PVC Insulated Having Fire Resistant, Low Smoke Double layer Insulation, Copper purity having 99.9% with Company test Certificated Higher Current rating ett) to be laid through PVC recessed Conduits, with 6Amp modular switches, modular plate, cover in front (Switches, Sockets series shall be Most likely Top models of Legrand (Myrus)/Havels top/Schneider/Anchor ROOMA PLUS make) and with suitable size of Gl box eto of approved quality and make ISO/IEC/BIS Certified (quality of wire shall be approved before execution of wok by SITE In-charge Engineer strictly as required) job including cost of conduits (wire shall be approved before execution of wok by SITE In-charge Engineer |
| 2 | Circuit/Sub main Wiring along with earth Wire with the following Sizes of FRL S-H PVC Insulated Multi strand copper conductor, single core Cable in surface/Recessed medium clan PVC conduit included as required quality of wire shall be approved before execution of wok by SITE in-charge Engineer strictly as required) Havels Polycab, Anchor/ Apar/ Grandlay/ eq. make. (incl. cost of conduit) |
| 3 | 2x6 sq.mm PN + 1 x 6 sq.mm earth Wire ( For Lighting sub-main) |
| 4 | 4 x 10 sq. mm TPN+ 2 x 6 sq. mm Earth wire [Sub main for Power points] |
| 5 | 2x4 sq. mm PN+1 x 4 sq. mm Earth wire (Wiring for Power Points) |
| 6 | 2x2.5 sq.mm PN + 1x 4 sq.mm earth Wire (Wiring for Machine Equipments/Computer points and Lighting Circuits) |
| 7 | Supply and drawing following sizes of FRLS PVC insulated single core Cable in EXISTING surface/Reccessed medium class PVC conduit as required (incl. cost of conduit) |
| 8 | 3x4 sq.mm (For AC Points) |
| 9 | Supplying and Fixing of Modular Blanking Plate on the Existing Modular Plate and switch box excludinng modular plate as required |
| 10 | Supplying and Fixing suitable size G I box with Modular plate and cover in front on surface or in recess, Including providing and fixing 3/5-pin 5/6Amp modular socket outlet and 5/6 Amp modular Switch connections etc. as required ( For Switch boards in each room) |
| 11 | Supplying and Fixing suitable size G.I box with Modular plate and cover in front on surface or in recess, including providing and fixing of 2N0s. 5 pin 5/6Amp modular socket outlet and 2Nos. 5/6Amp modular Switch connections et required ( For Equipments/Computer Points) |
| 12 | Supply and fixing of Two modular Stepped Type Electronic Fan Regulator on the existing Modular Plate Switch Box Including Connections but Excluding Modular Plate |
| 13 | Supplying and fixing suitable GI Box with Modular plate and cover in front on surface or in recess, including providing and fixing 6-pin Shutter typed 15/16Amp modular sockt outlet and 15/16 Amp modular Switch, connections etc as required (For powerplug points) |
| 14 | Supplying and fixing of following size of PVC Conduit along with accessories in surface reccess including painting in case of surface conduit or cutting the wall and making the good same in case of recessed condut as required (Subject to actual requirement if any) |
| 15 | 25 mm |
| 16 | 32 mm |
| 17 | Supplying and fixing following way, TPN Horizontal type three pole and neutral, Sheet Steel MCb distribution board, 415 V, on surface/ recess, complets with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder coated painted including earthing etc as required |
| 18 | 8 Way ( 4+ 24), Double Door |
| 19 | Supply and fring of followingway SPN(SINGLE POLE and Neutral sheet steel MCB Distribution boards 240V on surface/recess complete with tinned COPPER BUS BAR Neutral Bar Earth bar interconnections powder coated painted including earthing etc. |
| 20 | 16 way Double Door |
| 21 | Supplying and fixing of following Rating, TPN 240/415 10KA Miniature Circult Breaker suitable for Inductive load of following poles in existing MCB, DB commissioning etc as required Complete with connections, testing and commissioning etc as required |
| 22 | 63 A F.P MCB 10 KA \\" C\\" Curve |
| 23 | Supplying and fixing of 5Amp to 32Amp Rating, 240v/415v, 10KA, C Curve Miniature Circuit Breaker suitable for Inductive load of following poles in existing MCB. DB Complete with connections, testing and commissioning etc as required |
| 24 | SINGLE POLE MCB [Schneider/Slemens/Havells/Legrand) |
| 25 | Supplying and fixing following rating, Double pole, MCB Miniature Circult breaker 240 V), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 26 | 40Amp D.P MCB Schnelder/Siemens/Havells/Legrand |
| 27 | 63 Amp. D.P MCB [Schnelder/Siemens/Havells/Legrand) |
| 28 | Supply, Installation, Testing and Commissioning of 1200 mm sweep BEE 5 star rated, celling fan with Motor, class of Insulation: B, 3 nos. blades, 30 cm long down rod, 2nos, canoples, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min, 350 RPM (tolerance as per IS: 374-2019), THD less than 10%, Including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), Insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase A Supply, etc. complete as required. USHA/Havells |
| 29 | Supply, Installation, Testing and Commissioning Max air exhaust fan high performance air extraction whisper quiet operation automatic shutter operation voltage 38watt having ball bearing motor 50 dsa decibel rating 3m320 Cu.m/Hr. AC 220-240 Volts, 50 Ilz Exhaust fan with inbuilt thermo cut-off Protection and Noise Level not exceeding 37 dB of Following Sizes including connection & 3-pin Socket ete. Up to 450mm size |
| 30 | Supply installation testing and commissioning of 18W + LED Surface Mounted/Recess 124 Panel light luminary fitting round shape with minimum system lumen efficacy of 100-120 lm/W Housing with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 THD<10%,CCT 5700K, CRI 80. The LED with Useful life of 50000 11rs at 1.70.. The Input voltage range shall be 150V to 270V. The Fixture should have In-built Surge Protection of 2kV. Certification:-LM79 & LM80 test report should be from govt approved In-house NABI. lab/government of India authorised lab. The job includes AMC two years replacement warranty makes reff. Of hg Philips/ Havel's/Wipro/hg or Jaguar or TRILUX/hg make should be Commercial/Professional |
| 31 | Supply installation testing and commissioning of IP 65 led Bulk head 10 W +/-1 W LED Surface Pressure Die Cast Aluminum system lumen efficacy of 100 lm/W with Polycarbonate Opal Diffuser and P.F.>0.95, THD<10%, CCT 5700K, CRI 80, IK rating IK08. The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 150V to 265V. The Fixture should have In-bullt Surge Protection of 2.5kV Certification:- LM79 & LM80 test report should be from govt. approved In-house NABL lab/ government of India authorized lab The job includes AMC two years replacement warranty Philips/Havels/Wipro/TRILUX/hg/Jaguar |
| 32 | Design, Fabrication, assembly, Installation, Testing and Commissioning of Main Control Panel Front Operated Cubicle type compartmentalised as per form 3B free standing, dust and vermin proof (IP 42 Ingress protection) LT panel suitable for use of 415 volts, 3 Phase 4 wire 50Hz suitable for a fault levewl of 55kA at 415 volts, fabricated from 2 mm thick Powder coated paint finish of approved shade CRCA MS sheet with hinged, gasketted9 metal based neoprene) and lockable doors having structural reinforcement with suitable angle Cable gland plates as required and lifting hooks with sleeved TPN AL Bus bars.The panel is to painted with Electro static powder coated colour Siemens grey structural with proper chemical pre-treatment with following equipments:-(1) Normal Income:200 Amps TPN MCCB With adjustable breaking capacity 36KA=1No 400 Amps TPN AI. Bus Bar Set = 1 setDigital Voltmeter, Ammeter, C.T Coils with Selector Switch & Phase Indicators (2) Generator Incomer :-63Amp Panel mounted Change over switch -1200 Amps TPN Al. Bus Bar Set = 1 set for Lightings etc Digital Voltmeter, Ammeter, C.T coils with selector switch & Phase Indicators(3) Outgoing for Heating/Lighting Load etca) 63 Amps TPN C curve MCBS =5 No.sb) 63 Amps DP C Curve MCBs = 4 No'sc) 40 Amp D.P C-Curve MCBs = 5 Nosd) 100 Amp DP Bus Bar Set |
| 33 | Supply installation testing and commissioning of 10W LED Surface Mounted/WALL 5 mounted LED Batten fitting (MIRROR LIGIIT) covered by diffuser, high efficiency reflector pre wired electronic driver complete with all accessories suitable for opretion on single phase 240v 5011z AC supply as required |
| 34 | Supply installation, testing and commissioning of 32/40 Amps industrial type metal clad Socket outlet with Inter Connections in heavy gauge powder coated AC box with 3pin plug top to be fitted on wall with 40Amp D.P MCB included complete with making necessary connections [Havells, Schneider, L&T, Legrand/Siemens) |
| 35 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER Rod EARTHING SYSTEMNecessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value Supplying, Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No, bags also having Earth pit chamber (300mm x 300mm) with man-hole cover for the above. Including cost of 20MM Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through DWC High Density Poly ethylene Pipe having Corrugation complete job |
| 36 | Supply, laying, Connecting and Commissioning of 95sq mm 3.5 core XLPE Sheathed /PVC insulated and steel armored 1.1 KV grade Aluminum Cable as S.L from nearby L.T Pole up to Control panel of Havells/RR/Polycabmake with required Test certificate of Manufacturing company with required size of thimbles dully crimped with hydraulic crimping tool with making of connection including cost of cable trench execution to be laid through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench (Subject to actual requirement at site |
| 37 | Supplying, Installation, Testing and Commissioning of CO2 Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683) suitable for 'B' and 'C' class fires - Inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical fires etc MAP-90 |
| 38 | Supplying, Installation, Testing and Commissioning of ABCFire Extinguisher MAP-90 4-4.5 Kg. Capacity ISI Mark(IS:15683) |
| 39 | Supply, Installation, Testing and Commissioning of 30 watt LED Flood Light Luminary fittings 5700K, CRI 80, IK rating IK08. The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 150V to 265V. The Fixture should have In-built Surge Protection of 2.5kV Certification:-LM79 & LM80 test report should be from govt. approved In-house NABL lab/ government of India authorized lab The job includes AMC two years replacement warranty made of pressure die cast Aluminum Housing with high power LEDs, Lens & Toughened glass IP66 fitted on outer wall of Building with D-fast Gyeser bolts] of hg Philips Havells, Philips or wipro/ eq. make Please Enable Macros to View BoQ information |