| 1 | Taking down carefully copper/aluminium any type of point wiring (light/fan/socket /power) complete (fittings such as switches, ceiling roses, holders, sockets,regulators light fittings) and removal from site and making good the disturbed surfaces of (wall/floors/ceiling etc) complete all as specfied & directed. |
| 2 | M&L for point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi stranded copper conductor 4.0 sqmm nominal cross sectional area, single core, PVC insulated and unsheathed FRLSH cable 1100 volts grade, ISI-694 marked with valid CML No in and including medium grade, PVC concealed conduit of dia not less than 20 mm and conduit accessories concealed in wall (Brick/stone masonary), ISI marked with valid CML No (IS-9537-1983 for conduits and IS: 3419:1976 for conduit accessories), including PVC insulated multi stranded copper conductor 4.0 sqmm nominal cross sectional area single core FRLSH cable as earth continuity conductor to common earth and connecting to earth duly complete including replastering and making good the surface of wall and painting with existing colour all as specified and directed.(For AC point) |
| 3 | Taking down carefully sub main wiring three single run of any make and type complete all as directed. |
| 4 | Supply, laying and drawing submain wiring in and including 20 mm dia concealed PVC rigid conduits including cutting of chases for laying conduit making good the surfaces as per existing surfaces or as directed on walls 02 runs of IC x 6.00 sqmm (Main Cable and neutral) and one run of IC x 6.0 sqmm (as earth wire) of multistranded copper conductor PVC insulated, FRLSH, unsheathed cables of 1100 volts grade conforing to IS : 694 of 2010 complete including connection all as specified and directed. Note :- Two runs of IC x 6.00 sqmm (Phase wire and neutral ) and one run of IC x 6.00 sqmm (as earth wire) will be measured as one unit length. |
| 5 | S&F in repair sheet metal enclosure SP and Neutral with a two pin earth plug and socket complete with a MCB SP 20 Amp 220 volts, 50 Hz, 10 KA breaking capacity complete all as specified and directed. |
| 6 | Taking down DBs,VTPN DBs of any make and type from the site and making good to the disturbed surfaces complete all as specified and directed. |
| 7 | S&F in repair factory made epoxy polyester powder coated distribution board SP & N 8 way fabricated from minimum 1.6 mm thick CRCA sheet with metal double door ((IP-43, IK 09 protection,IEC-61439-3) ) fixed flush to wall and suitable for universal mounting and including 100 Amps copper bus bar, Neutral bar, standard DIN rail, eath bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP MCB as incomer and 06 SP MCBs as outgoings complete all as specified and conforming to IS: 8623 including taking down old DBs all as specified and directed.NOTE :-(a) MCBs shall be measured and paid separately.(b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. |
| 8 | S&F in repair factory made epoxy polyester powder coated distribution board TP & N 4 way (VTPN MCCB DB) with metal double door (IP-54 & IK 09 protection) fabricated from minimum 1.6 mm thick CRCA sheet and fixed on wall and suitable for universal mounting and including 100 Amps copper bus bar, Neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with provn for 100 Amps, 4 pole MCCB and ELM as incommer and 12 SP MCBs outgoings including blank spacer for blank space complete all as specified and conforming to IS: 8623 including taking down old DBs all as specified.NOTE :-(a) MCBs/MCCBs shall be measured and paid separately.(b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. |
| 9 | S&F of single pole MCB 6 to 32 Amps, 240 v, 50 Hz AC made from moulded self-extinguishing thermostat plastic and suitable for ‘B’ curve, 10 KA breaking capacity conforming to IEC 60898-1:2002 complete all as specified and directed. Make - Indo Asian/ Havells/ HPL |
| 10 | S&F in repair RCBO, 230 Volt, 40 to 63 Amp, 30mA, 50 Hz, with 10 kA short circuit capacity of double pole for ensuring protection from leakage current, short circuit & over load, complete all as specified and as directed.Make - Indo Asian/ Havells/ HPL |
| 11 | S&F of SPN MCB 32 Amps, 240V, 50 Hz AC made from moulded self-extinguishing thermostat plastic and suitable for ‘B’ curve, 10KA breaking capacity conforming to IEC 60898-1:2002 complete all as specified and directed. |
| 12 | S&F in repair MCB SPN 40 to 63 Amps rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning. |
| 13 | S&F in repair MCCB 100 Amps, 4 Pole 415 volts 16 KA 50 HZ complete all as specified and directed. |
| 14 | S&F in repair MCCB 125 Amps, 4 Pole 415 volts 16 KA 50 HZ complete all as specified and directed. |
| 15 | S&F in repair MCCB 160 Amps, 4 Pole 415 volts 36 KA 50 HZ complete all as specified and directed. |
| 16 | S&F in repair MCCB 200 Amps, 4 Pole 415 volts 36 KA 50 HZ complete all as specified and directed. |
| 17 | S&F in repair decorative wall light fittings suitable for 9/12 watt LED lamp B-22 base, IP-20 protection with plastic body, including connection with all necessary fixing accessories complete all as specified and directed by Engr-in-Charge. Note : LED Lamp shall measured and paid separately. (PHILIPS 30575/31/86 OR APPROVED EQUIVALENT IN TRILUX & ENDO) |
| 18 | S&F in repair ultra bright compact LED downlighter 12/15 Watts (round or square shape) with high efficiency LEDs ideally suited for low ceiling areas to give glare free light, complete all as specified and directed. |
| 19 | S&F in repair 35 watts 230 V AC outdoor type with High efficient LED Building security light fitting with high pressure die cast Aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP: 65/66 protected complete with bracket made out of 32 mm GI pipe light grade 1.2 mtr long bend to shape with clamps and fixing bolts all as specified and directed. |
| 20 | S&F in repair Fresh Air Fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 200/250 mm sweep, single phase,including cutting of holes in wall/windows for fixing the fresh air fan complete all as specified and directed. |
| 21 | M&L in replacement of earthing complete with galvanised steel earth plate 600X600X6 mm thick buried directly in ground (earth pit not les than 2.25 M deep below GL with top edge of plate not less than 1.50 m below GL) connected with GI earth lead wire 4.0 mm as earthing leads by means of bolts, nuts, check nuts and washers all joints as shown in electrical plate No 3 of SSR Part -I and including excavation, earth work. GI pipe light grade 15 mm bore for protection of GI earth wire from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt PCC (1:2:4) type B1 chamber and MS angle iron frame of 40mmx40mm x3 mmand RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No 3 of SSR Part -I and conected to earth test point including testing complete all as secified and directed at site. Please Enable Macros to View BoQ information |