| 1 | Making connection of G.I. distribution branch with G.I. main including all fitting. |
| 2 | Upto 25mm dia |
| 3 | Beyond 25mm & upto 100mm dia |
| 4 | Labour Charges for making connection with proposed pipe line to existing pipe line of AC/ DI/ CI including dewatering etc. complete but excluding the cost of pipes, specials, joints etc as directed bysite engineer for following dia. (Earthwork to be measured and paid separately) |
| 5 | 80-200 mm dia |
| 6 | Labour Charges for making connection with proposed pipe line to existing pipe line of PVC/ HDPE/ GRP including dewatering etc.complete but excluding the cost of pipes, specials, joints etc as directed by site engineer for following dia. (Earthwork to be measured and paid separately) |
| 7 | 75-200 mm dia |
| 8 | P & F Bib Cock (IS : 8931 Mark), Superior quality of approved make: |
| 9 | P.V.C.heavy duty, 15mm nominal bore. |
| 10 | P & F Full-way Valve (IS:778 Mark) or wheel valve of approved make |
| 11 | Gun-metal 15mm nominal bore. |
| 12 | Gun-metal 20mm nominal bore. |
| 13 | Gun-metal 25mm nominal bore. |
| 14 | Gun-metal 32mm nominal bore. |
| 15 | P & F Gun-metal Non-return Valve or Check Valve (IS :Make) of approved make, superior quality:Horizontal |
| 16 | (a) 32mm nominal bore. |
| 17 | Providing & Lowering in tube well ISI marked HDPE pipe as per IS 4984:1995 or amended upto date in PE 80 grade and class PN 10 of following dia. including HDPE/GI fittings and PVC rope confirming to IS 5175:1992 or amended upto date, along with clamping of submersible cable etc. complete in all respect. |
| 18 | 40 mm dia |
| 19 | Supply & Installation of single phase ISI marked submersible motor pump set of three star or better rating of BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. |
| 20 | Up to 2.0 KW |
| 21 | Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. |
| 22 | 3 core 4.0 Sq.mm |
| 23 | 3 core 6.0 Sq.mm |
| 24 | 3 core 10.0 Sq.mm |
| 25 | Supply and Fixing of Electric feeder panel (having projected canopy)for submersible pump set Single phase upto 5 HP, comprising of DOL Starter, MCB, Indicating Light, Ammeter, Volt meter, connection plate, condensers of approved make and the panel enclosure should be made out from 18 gauge M.S. Sheet with powder coating. Panel size Height 600 mm Width 500 mm depth 250 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\\" and double door including in built locking system. The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The operation of panel should be suitable for on 240 Volt AC Supply. |
| 26 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 27 | (a) 6.00 sqmm 2 core |
| 28 | (b) 10.00 sqmm 2 core |
| 29 | Rewinding of single phase/3phase submersible motor including all necessary material and of the same characteristics as original with required size of super enamelled wire 'E' class insulation material and testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 30 | 2.0 H.P.to 3.0 HP |
| 31 | Repairing of submersible pump of with replacement of broken impellers ,diffuser,bush/bearing set , oil seal complete with testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 32 | 2.0 H.P.to 3.0 HP |
| 33 | Labour charges for installation of submersible motor pump set including lowering/ delowering of pipes, cables, accessories etc. in tube-well/ open well complete including T&P, transportation of tripod, chain pulley block & any other material required for this purpose complete in all respect. |
| 34 | Lowering only |
| 35 | Delowering only |
| 36 | Delowering and Lowering Please Enable Macros to View BoQ information |