| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Garrison Engineer (AF) Gorakhpur Name of Work: REPAIR/MAINT OF LT EXTERNAL ELECTRIC SUPPLY AND CONNECTED ITEMS, LT PANELS, LT CABLES, DISPLAY BOARDS , SIGN BOARDS, INSTRUCTION BOARDS AT 756 SU, 274 SU, MES AND TECH AREA AT AF STN GORAKHPUR. Contract No.: GE(AF)/GKP/E-24 OF 2026-27 File No. 9462/E8 Serial Page No.15 Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of item Item Code / Make Quantity Units Estimated Rate inRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e. DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit, if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes inRs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Excavation in trenches n. exc 1.5 m wide and n.exc 1.5 m in depth and getting out soft/loose soil complete all as specified and as directed for laying of under ground cable, foundation of pole and stay etc. complete all as specified and as directed |
| 3 | Returning, filling in, including spreading, levelling, watering and well remmining in layers not exc 25 cm complete all as specified and as directed |
| 4 | Removing excavated material n.exc 50 m and depositing where directed at a level n. exc 1.5 m above the starting point complete all as specified and as directed |
| 5 | M&L for sand cushioning to U/G cable in layers of 23 cm thick( 8 Cm before laying the cable and 15 Cm thick after laying the cable) in trenches complete all as specified and directed.Note :- Only Puned down volume shall be measured. |
| 6 | Supply and lay burnt best quality locally available old size sub class 'B' bricks laid in trenches perpendicular to U/G cable for cable protection complete all as specified and as directed. |
| 7 | Laying only serviceable bricks obtained from the items specified here-in-before (i.e during taking out of under ground cable),laid flat dry, in trenches with width of the bricks laid to the axis of cable for protection of cable complete all as specified and as directed |
| 8 | Taking out unserviceable LT U/G cable from trenches of size 6 Sqmm to 120 Sqmm 2/3.5/4 core complete all as specified and as directed. |
| 9 | Supply and lay in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 16 Sqmm 4 core complete all as specified and as directed |
| 10 | Ditto as above but of size 25 sqmm 4 core…ditto…. |
| 11 | Ditto as above but of size 35 sqmm 3.5core.…ditto…. |
| 12 | Ditto as above but of size 50 sqmm 3.5core.…ditto…. |
| 13 | Ditto as above but of size 70 sqmm 3.5core. |
| 14 | Ditto as above above but of size 95 sqmm 3.5core. |
| 15 | Ditto as above above but of size 120 sqmm 3.5core. |
| 16 | Ditto as above above but of size 150 sqmm 3.5core. |
| 17 | Ditto as above above but of size 185 sqmm 3.5core. |
| 18 | Ditto as above above but of size 240 sqmm 3.5core. |
| 19 | Boring holes horizontally under road without damaging the surface of road ( minimum 1.0 Metre below the road surface with the help of GI tubing not exc 100 mm bore(dia) for passing UG cable, complete all as specified and as directed. NOTE : - GI Pipe laid will be measured and paid separately under respective item |
| 20 | S&F in replacement of 40 mm bore GI tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor/wall for cable protection with suitable size of MS clamps and nut and botls/washers complete all as specified . |
| 21 | S&F in replacement of 25 mm bore GI tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor/wall for cable protection with suitable size of MS clamps and nut and botls/washers complete all as specified . |
| 22 | M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick, burried directly into the ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI earth strip 32x6 mm by means of bolts, nuts, check nuts, and washers of galvanised iron or steel all as shown iln electrical plate No. 3 connected to earthing test point all as specified or indicated including excavation and connected earth work, PCC chamber and cover, watering pipe, funnel wire mesh but without earth lead protection pipe and test on completion after dismantling unserviceable erthing (above GL only) complete all as directed. |
| 23 | Dismantling existing unserviceable feeder pillar box including disconnection from different sites complete all as directed. |
| 24 | Fabrication, supply, installation, testing and commissioning in replacement of outdoor type feeder pillar box floor mounted made out from 3.15 mm thick MS sheet ( CPRI type tested) with canopy type roof, front operated, one part hinged doors with locking arrangement comprising of Aluminium bus bar suitable for 3 phase, 4 wire, 415 volts,50 Hz, AC supply mounted on suitable bus bar insulators, 200 Amps rating suitably drilled and tapped for bolts with openable two part front and rear shutter with heat strinkable PVC sleeving having RYB-B colour code drilling holes for connection of incoming and outgoing cable, complete powder coated painting, testing and installation on PCC/brick foundation, connection of cable with suitable aluminium lugs all as specified and directed. |
| 25 | Repairing of unserviceable MCCBs/MCBs/changeover switch in LT panel/ DBs any type including replacing of burnt out lugs, including cutting of burnt cable terminals ,prepare and crimping the cable lugs with LT cables in no light/unhealthy light complaints and making serviceable in all respect by providing skilled manpower.Work shall also include checking and removal of leakages in neutral and phase in 440/220 Volts connection as and when directed.NOTE:- (a) The rate quoted by the contractor for Each Job is deemed to inclusive in rate quoted (b) The ladder and T&P as required will be provided by the contractor(c)Risk factor will be the contractor's end(d) Minor items like cable lugs,Insulation tape,nut,bolts etc deemed to be included in rate quoted (e)Major Items will be measured and paid separately in the relevant items here under:- |
| 26 | S & F in replacement MCCB 630 Amps, 4 pole, 415 volts, 50 Hz 50 KA breaking capacity with adjustable thermal magnetic release with spreader link on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed |
| 27 | S & F in replacement MCCB 400 Amps, 4 pole, 415 volts, 50 Hz 36 KA breaking capacity with adjustable thermal magnetic release with spreader link on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed |
| 28 | S & F in replacement MCCB 315 Amps, 4 pole, 415 volts, 50 Hz 36 KA breaking capacity with adjustable thermal magnetic release with spreader link on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed |
| 29 | S & F in replacement MCCB 250 Amps , 4 pole, 415 volts , 50 Hz , 25 KA breaking capacity with adjustable thermal magnetic release, with spreader links on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed |
| 30 | S & F in replacement MCCB 200 Amps , 4 pole, 415 volts , 50 Hz , 25 KA breaking capacity with adjustable thermal magnetic release, with spreader links on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed |
| 31 | S & F in replacement MCCB 160 Amps , 4 pole, 415 volts , 50 Hz , 25 KA breaking capacity with adjustable thermal magnetic release, with spreader links on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed |
| 32 | Supply only in replacement on load Changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 200 Amp all as specified and directed |
| 33 | Supply only in replacement on load Changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 400 Amp all as specified and directed |
| 34 | M&L straight through joints( epoxy) for LT underground cable including joint kits suitable for aluminium conductor cable 3.5 core 6 sqmm to 240 sqmm all as specified and directed |
| 35 | M&L outdoor LT END Termination Heat Shrink Kits for LT underground cable suitable for aluminium conductor cable of size 6 sqmm to 240 Sqmm (3.5/4C) all as specified and directed |
| 36 | M & L for preparing old painted surfaces by scraping and removing old paints,rust etc from steel tubular poles (above the planting depth and PCC coping of 9.0 Metre long pole) and Mild Steel cross arms, cable protection pipe,brackets etc and applying one coat of synthetic enamel paint alternate yellow & black strips painting ( 5 Nos each strip 300 mm wide) and remaining portion of pole and cross arms,cable protection pipe,brackets etc painted with one coat of aluminium paint including marking of pole No with black background and white lettering with all arrangement for ladder etc all as specified and directed . |
| 37 | Dismantling of old PCC/steel tubular pole of any size with necessary disconnection of electric wire, demolition of concrete foundation including excavation, earth work as reqd & removing the same from site complete all as specified and as directed. |
| 38 | Supply & errection of steel tubuler swaged & welded pole 9.0 m long type 410 SP- 31 complete with CI base plate and finial tapper plug , bolts nuts screw conforming to IS: 2713 (part I to III) complete painting of pole with two coat of aluminium paint over a coat of red oxide primer and applying one coat of synthetic enamel paint alternate yellow & black strips painting ( 5 Nos each strip 300 mm wide ) all as specified and directed. |
| 39 | Disconnection and dismantling of existing serviceable under ground cable of size 6 Sqmm to 240 Sqmm 2/4 core from LT Panel/FPB and taking out cable/cable loop from underground by excavtion of soft/loose soil and insertion of heat shrinkable PVC colour sleeves on cable cores and crimping of suitable size aluminium cable lugs as required and refixing the same in its original position complete all as specified and as directed. |
| 40 | Supply and spary of grass burning chemical(Paraquat dicholride 24 SI Herbicides ) with the help of manually opearted machine complete in sub station complete in air force stn directed by engineer incharge. |
| 41 | Detecting of fault of LT UG cable (any place any length any type /size) with help of vehicle mounted cable fault locator including detecting exact location of cable fault and remove of cable for rectification. complete all as specified and as directed. |
| 42 | Supply, install, testing and commissioning of LT Cubicle panel of suitable size, outdoor type, platform mounted, totally enclosed, dust and vermin proof, openable from both front and rear side, made out of 3.15mm thick CRCA sheet complete including inner chambers/partitions to mount the following electrical accessories and built upon 50x50x6mm angle iron frame work, having front and rear hinged doors, lifting lugs (2 Nos), provision for earth strip connection, bottom detachable gland plates, connecting using suitable size of zinc plated and passivated nut, bolts , springs and washers. The cabinet and all members should be chemically treated with anti-corrosive chemicals and apply spray paint with two coats of synethetic enamel paint over a coat of red oxide primer. The panel should be suitable for 415 volts, 50Hz , 3 phase 4 wire system 1100 volts grade, coloured heat shrinkable sleaving, internal connection should be provided with aluminium strip of suitable size and necessary grouting/ foundation all as required at site and comprising following:-a) Ammeter, digital including selector switchb) CT of required capacity -03 No(c) Voltmeter Digital type including selector switch(d) Phase indicating lamps -03 Nose) Control wiring(f) Copper conductor wiring .g) BusBar strip made out of aluminium of 400 amps capacity mounted on insulators.h) MCCB 4 Pole 415 Volt 250 Amps Capacity, 36 KA - 01 Nos ( for incoming ) Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |