| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer TLMD-I, Bemina Srinagar, JKPTCL. Name of the Work: Rate Contract for Annual Preventive/Routine/Breakdown maintenance works of various 132/33KV Grid Sub-stations and allied 132kV transmission lines falling under the jurisdiction of TLMD-I, Bemina, Srinagar Only Labour Part involved without material Part (Quote rates for Labour Part complete for Each BOQ Item enlisted) e-NIT No: 02/JKPTCL/TLMD-I/SGR/2026-27; Dated: 18.06.2026 Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # BOQ Item No Item Description(Quoted rates for Labour only without material) Item Code / Make Qty Units Estimated Rate inRs. Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE(with taxes) Rs. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT With Taxes inRs. TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Part: (A) 132kV Transmission Lines (Preventive Maintenance) |
| 3 | Checking and tightening of jumper. |
| 4 | Replacement of jumper. |
| 5 | Replacement of damaged disc insulators- Tension String |
| 6 | Replacement of damaged disc insulators- Suspension string |
| 7 | Repairing of power conductor when lowering of conductor is necessary. Complete job including laying of conductor, making of compression joint, if any, rough sagging ,tensioning of conductor, fixing dead-end assembly etc. up to span of 500 meter tension to tension |
| 8 | Repairing of earth wire when lowering of Earth wire is necessary (Complete job) including compression joint if required. Laying of earthwire,tensioning ,dead-end assembly etc.upto span length 500 meter tension to tension point. |
| 9 | Tightening of Nuts and Bolts of tower superstructures and replacement of missing nut and bolts. |
| 10 | Tower weight up to 2 tones |
| 11 | Tower weight more than 2 tones up to 4 tones. |
| 12 | Tower weight more than 4 tones up to 7.5 tones. |
| 13 | Tower weight more than 7.5 tones |
| 14 | Checking/ tightening of tower footing earthing bolts and measuring tower footing resistance. |
| 15 | Branch cutting in a corridor width of 26 meter . |
| 16 | Replacement of missing tower member |
| 17 | Repairs of tower foundations, retaining walls /breast walls etc ( Stone masonary) |
| 18 | Tag welding of tower bottom section wherever required. |
| 19 | Erection of Tower Superstructures. |
| 20 | Dismantling of Tower super structure. |
| 21 | Dismantling of 0.2 ACSR Conductor.(Single Conductor) |
| 22 | Laying and Stringing of 0.2 ACSR Conductor complete job |
| 23 | Erection of ERS including digging of pits and excavation of soil, providing of wooden logs and carriage of ERS from the Stores to the site of work (Complete job in all respects in such a way that the circuit running on ERS is made operational) (ERS shall be provided by JKPTCL) |
| 24 | Dismantling of ERS including back filling of pits and carriage of ERS from the site to the Stores (Complete job in all respects and site shall be cleared in such a way that the material dumped at site during erection is returned to the respective places) |
| 25 | Part (B) 132 / 33 KV Grid Stations (Preventive /Routine Maintenance) |
| 26 | Power Transformer :-Checking of auto starting of fans/ pumps, hand operation of all taps, including handle interlock switch, local and remote operation of accessories, WTI/OTI indications. Inspection and testing of transformer including drying/ replacement of silica gel, checking of buchhloz relay, conservator oil level indicator, temp. sensors, topping of oil, cooling system, alarm / trip circuit. Measurement of IR Values, dielectric strength of transformer oil and BDV of oil, checking of marshalling box of OLTC,NGR, T.B of PDR, Bucholz relay, External cleaning of radiators, bushings etc. |
| 27 | 10 MVA to 20 MVA |
| 28 | 20 MVA to 50 MVA |
| 29 | Draining/ De-sludging of transformer oil of transformers |
| 30 | Topping/Filling/dehydration of transformer oil. |
| 31 | Repair/ rewinding of three phase transformer cooling fans including replacement of damaged winding, bearing etc. |
| 32 | 1. Circuit Breaker :SF6 Breaker(132KV) :-Checking of auto starting of air compressor, oil pressure drop during duty cycle operation check, Checking of auto-starting / stopping of oil pump,pressure switch setting,etc, Checking of healthiness of accumulator by checking the pre-charging pressure when building up pressure from zero, Checking of operation of safety valve, Cleaning of breaker units, checking of protection equipments and replacement of defective ones, i.e., complete inspection and testing of SF6 type circuit breakers inclusive of operating mechanism. Maintaning gas levels, venting of circuit breakers etc. |
| 33 | 2.Circuit BreakerVCB(33KV):-Checking of pressure settings of switches, pole discrepancy relay, interlocks, operational lockouts, driving mechanism (hydraulic/pneumatic) close/ trip coils, healthiness of operation counter, terminations of MB, door sealing gaskets, duty cycle operation including rapid re-closing , functioning of space heater/ illumination. Cleaning of breaker pole, support insulators, PIR and grading capacitor, interrupter chamber, control cabinet. Re-painting of metallic surfaces if required .Complete inspection of contacts and adjustment of various clearance including draining and re-filling of oil and nitrogen gas. |
| 34 | 132 kV Current Transformer:-Checking /cleanliness and tightness of all electrical connections including earthing of marshalling box ,CT secondary terminal ,healthiness of secondary terminal bushing .Checking of oil level.Measurement of IR Value and tightening of jumpers, filling of nitrogen gas and tightening of jumpers. |
| 35 | 33 kV Current Transformer:-hecking /cleanliness and tightness of all electrical connections including earthing of marshalling box ,CT secondary terminal ,healthiness of secondary terminal bushing .Checking of oil level.Measurement of IR Value and tightening of jumpers, filling of nitrogen gas and tightening of jumpers. |
| 36 | 132 kV C.V. T./ P.T's :-Checking of earthing of HF point, breakage or cracks in HF bushing ,neutral earthling in CVT ,healthiness of all gaskets and oil level .Cleaning of CVT capacitor stacks, marshalling box and junction box ,space heater and illumination .Measurement of IR value and tightening of all connections and droppers, filling of nitrogen gas. |
| 37 | 33 kV C.V. T./ P.T's :-Checking of earthing of HF point, breakage or cracks in HF bushing ,neutral earthling in CVT ,healthiness of all gaskets and oil level .Cleaning of CVT capacitor stacks, marshalling box and junction box ,space heater and illumination .Measurement of IR value and tightening of all connections and droppers, filling of nitrogen gas. |
| 38 | 132 kV Surge Arrestor:-Checking of leakage current(third harmonic resistive current), Testing of counters and leakage current meters, Cleaning of insulators, Checking of earth connections between surge arrester,surge monitor and earth, Checking of leakage current after cleaning of porcelain surface, cleaning of LA insulators. Measurement of IR value and tightening of droppers and testing of counter and leakage of current meters, Cleaning of insulators, Checking of earth cennections between surge arrester, Surge moniter and Earth. |
| 39 | 33 kV Surge Arrestor:-Checking of leakage current(third harmonic resistive current), Testing of counters and leakage current meters, Cleaning of insulators, Checking of earth connections between surge arrester,surge monitor and earth, Checking of leakage current after cleaning of porcelain surface, cleaning of LA insulators. Measurement of IR value and tightening of droppers and testing of counter and leakage of current meters, Cleaning of insulators, Checking of earth cennections between surge arrester, Surge moniter and Earth. |
| 40 | 132 kV Isolators:-Maintenance of linkages including transmission gears, stopper bolts. Cleaning of auxiliary switch contacts and greasing with silica grease, cleaning of support insulators ,termination contacts, checking of electrical /Mechanical interlocks with E/S & CB,mounting bolts, alignment ,nuts, pins, space heater and illumination ,healthiness of gaskets, auxiliary contacts ,alignment of earthing blades, operation of earth switch, aluminum /copper flexible conductor, earth connections of structures and MB .Lubrication of operating mechanism, hinges, lock joints, levers, bearings ,main contacts, cleaning of post insulators,tightning of clamps etc. |
| 41 | 33 kV Isolators:-Maintenance of linkages including transmission gears, stopper bolts. Cleaning of auxiliary switch contacts and greasing with silica grease, cleaning of support insulators ,termination contacts, checking of electrical /Mechanical interlocks with E/S & CB,mounting bolts, alignment ,nuts, pins, space heater and illumination ,healthiness of gaskets, auxiliary contacts ,alignment of earthing blades, operation of earth switch, aluminum /copper flexible conductor, earth connections of structures and MB .Lubrication of operating mechanism, hinges, lock joints, levers, bearings ,main contacts, cleaning of post insulators,tightning of clamps etc. |
| 42 | 132 kV Column and beams:-Tightening of all nuts/bolts and providing of missing nuts/bolts and damaged members |
| 43 | 33 kV Column and beams:-Tightening of all nuts/bolts and providing of missing nuts/bolts and damaged members |
| 44 | Bus Bar:-Checking / tightening of clamps/ jumpers/ droppers. Replacement of damaged/ burnt droppers or jumpers. Checking / repairing of bus bar conductors |
| 45 | Illumination System:-Checking of healthiness of fittings in Station buildings, out door switch yard, repairing and replacement if required, lighting of pannels.Tightening of terminals, maintenance/repairs of high-mast lights etc including repairing to the wiring of these equipments. |
| 46 | Replacement of worn out/damaged electric fittings of control room and other allied buildings of Division. |
| 47 | Battery bank:-Checking and cleaning of battery cell terminals, application of petroleum jelly, if required, conducting of battery impedance test and discharge test checking voltage,temperature,current ,sp.gravity of individual cells as well as terminal voltage. |
| 48 | Battery charger.:-Checking of control cards, measurement of test point voltage values, testing of D.C earth fault and U/V relays, I.R.measurement of charger transformer checking of earthing etc.Checking of charger panel /D.C .D.B for electrical connections, cleanliness etc. |
| 49 | Protection System:-Checking of relays and application of CCL4 for cleaning, carrying out relay testing replacement of worn out defunct relays, testing of event logger/disturbance recorder if any, checking and replacement of control wiring if required. |
| 50 | Part (C) :132 / 33 KV Grid Stations (Breakdown Maintenance) |
| 51 | Circuit Breakers-132 kV SF6 Loading , unloading , dragging and Dismantling of Damaged Circuit Breaker and errection and commisioning of new circuit breaker including control cabling , connections to the breaker, earthing of the breaker and final erection checkup etc. |
| 52 | Circuit Breakers-33 kV VCB Loading , unloading , dragging and Dismantling of Damaged Circuit Breaker and errection and commisioning of new circuit breaker including control cabling , connections to the breaker, earthing of the breaker and final erection checkup etc. |
| 53 | 132 KV CT/PT/CVT/Coupling Capacitor/Wave Trap: Loading , unloading , dragging and Dismantling of Damaged CT/PT/CVT/Coupling Capacitor/wave Trap and its errection and commisioning of new CT/PT/CVT/Coupling Capacitor/Wave Trap including control cabling , connections ,earthing and final erection checkup etc. |
| 54 | 33 kV CT/PT/CVT/Coupling Capacitor/Wave Trap: Loading , unloading , dragging and Dismantling of Damaged CT/PT/CVT/Coupling Capacitor/wave Trap and its errection and commisioning of new CT/PT/CVT/Coupling Capacitor/Wave Trap including control cabling , connections ,earthing and final erection checkup etc. |
| 55 | 132 kV Surge Arrestor: Loading , unloading , dragging and Dismantling of Damaged Surge arrestor and its errection and commisioning of new Surge arrestor including control cabling , connections ,earthing and final erection checkup etc. |
| 56 | 33 KV Surge Arrestor: Loading , unloading , dragging and Dismantling of Damaged Surge arrestor and its errection and commisioning of new Surge arrestor including control cabling , connections ,earthing and final erection checkup etc. |
| 57 | 132 KV Isolators with earthing blade:Installation of new isolator after dismantling of the damaged one including loading, unloading and dragging of the said isolator where ever required. Control cabling , adjustment and carrying out various designated tests after installation etc. |
| 58 | 33 KV Isolators with earthing blade:Installation of new isolator after dismantling of the damaged one including loading, unloading and dragging of the said isolator where ever required. Control cabling , adjustment and carrying out various designated tests after installation etc. |
| 59 | 132 KV Isolators without earthing blade:Installation of new isolator after dismantling of the damaged one including loading, unloading and dragging of the said isolator where ever required. Control cabling , adjustment and carrying out various designated tests after installation etc. |
| 60 | 33 KV Isolators without earthing blade:Installation of new isolator after dismantling of the damaged one including loading, unloading and dragging of the said isolator where ever required. Control cabling , adjustment and carrying out various designated tests after installation etc. |
| 61 | Cable Trench Cleaning :- Cleaning of cable trenches, checking of cable trays , replacement of damaged angles/ channels and tightening of cable trays. |
| 62 | Dewatering of cable trenches and clearance of silt |
| 63 | L.T.Switchgear/Auxiliary Transformer:-Checking of all connections, tightening ,and replacement of wiring if required, testing of BDV oil of aux.transformer,I.R measurement .Functional checks ( Trip/ Close) and operating time measurement of MCB's checking of all motors for normal functioning with cleaning and replacement of worn out wiring etc |
| 64 | Earthing Mat:-Measurement of earth resistivity at terminals,checking of electrical continuity of equipment earthings, tightening of earthing connectors, removal of rust from bottled earth connectors and tightening (132/33 KV yards). |
| 65 | D.C.Distribution Board:-Checking of connections , wiring ,replacement of wiring if needed and checking of healthiness of all the D/C lights. |
| 66 | Repairing of yard concreate of 132/33 KV Bays :-Checking and ascertaining the level of damage to the existing concreting, then replacement of damaged patches with fresh concerting in order to rectify the damaged portions with M10 concrete grade. |
| 67 | Deweeding of the switch yard, store yard including cutting of wild vegetations and thorny bushes,hurbs and shrubs and also displacement of material in Divsional Stores and Yards where-ever required for hassle free dweeding etc. |
| 68 | Painting by way of Aluminium paint on Steel Structures like 132/33 Kv C1 Columns, C2 Columns, Beams, isolator superstructures, CT/PT/LA structures etc. (Complete Job) |
| 69 | Cleaning of Bays Removal of wild grass ,herbs and shurbs etc. 132 KV Bay |
| 70 | Cleaning of Bays Removal of wild grass ,herbs and shurbs etc.33 KV Bay |
| 71 | Part (D) General /Routine Works |
| 72 | Loading/Unloading of 132KV SF6 Breakers at divisional Stores for safe Storage of material. |
| 73 | Loading/Unloading of 33 KV VCB Breakers at divisional Stores for safe Storage of material. |
| 74 | Loading/ Unloading of 132 kV Current transformers, potential transformers, CVT's,Isolators,Lightening arrestors etc |
| 75 | Loading/ Unloading of 33 KV Current transformers, potential transformers, CVT's,Isolators,Lightening arrestors etc |
| 76 | Loading/ Unloading of portland cement 50 Kgs bag at divisional Stores / site of work. |
| 77 | Rearrangement of material in divisional store yard as required instantly for facilitating easy movement of men and material in the yard |
| 78 | Handling (loading, unloading and Carriage including verification , counting & Sorting ) of various line and sub- station materials and equipments viz power & distribution Transformers, ligtining arrestors 132 and 33 Kv , post Insulators and other allied Materials viz Transformer Oil, insulators, etc. |
| 79 | Carriage and staking of various line and Substation materials and equipments viz old MOCBs,scrap of sorts and other allied Materials viz insulators, post insulators, porcelean bushes etc. |
| 80 | Shifting/stacking / Reaarrangement of old tower material/ galvanised/ bend material in the divisional store yard in order to facilitate the easy movement of men and material and to keep the store materials in arranged way. |
| 81 | Shifting/stacking of old material (Serviceable / un serviceable) in the divisional store yard including conductor,TMT, Angle and Channels, scrapes etc. in order to facilitate the easy movement of men and material and to keep the store materials in arranged way. |
| 82 | Repair work to the boundary walling (Brick Work) of the Grid stations |
| 83 | Repair work of chain link fencing. |
| 84 | Fabrication of angle iron of various sizes/ Channel Iron etc as per design which includes cutting, Drilling of Holes, Straigtening, skew Cutting etc. |
| 85 | Repairs to store sheds wherever required like fixing of tin sheets, welding of the same etc |
| 86 | Handling, displacement, rearrangement including loading/ unloading of Control and Relay Pannels of 132 KV and 33 KV side and other allied pannels like DCDB, ACDB etc. |
| 87 | Excavation in all type of soils including mixed soils (i.e. soils containing pebbles/boulders etc.) for any sectioninvloving all labou only , POL, hire charges of equipments and T&Ps etc. including sheeting & shoring, dewatering, lifting, handling and stock piling of excavated materials, back filling with excavated or borrowed earth and disposal of surplus excavated earth as directed for all leads & lifts complete as per specification, construction drawings. |
| 88 | Handling (loading, unloading and displacement) of various Drums like cable drums, 0.2/0.4/0.5 ACSR Conductor Drums, Earthwire drums etc for hassle free movement of men and material in the store yard. |
| 89 | Painting with synthetic enamel paint in Control Room buildings and allied qauters including repairs of the same where-ever required. |
| 90 | Providing of skilled Electrcian for one day |
| 91 | Providing of Line Erector for one day |
| 92 | Providing of skilled Fitter for one day |
| 93 | Providing of skilled Mason for one day |
| 94 | Providing of skilled Blacksmith for one day |
| 95 | Providing of skilled Carpenter for one day |
| 96 | Providing of skilled Painter for one day |
| 97 | Providing of Electrcian for one day |
| 98 | Providing of skilled Labour for one day |
| 99 | Providing of skilled Tree/wood cutter for one day |
| 100 | Providing of labour for one day |
| 101 | Part (E) General /Routine Miscelleneous Works |
| 102 | Laying of various cores(2C,4C,5C,8C,10C,14C,16C),2.5 mm2 1.1kV Voltage grade XLPE/PVC insulated control cable FRLS galvanised steel wire/stripped armoured stranded coppor conductor. |
| 103 | Laying of various 4cores(6 mm2, 10mm2, 16mm2, 25mm2,35mm2) 1.1kV Voltage grade XLPE/PVC insulated control cable FRLS galvanised steel wire/stripped armoured stranded coppor conductor. |
| 104 | Laying of various 4 cores(6 mm2, 10mm2, 16mm2, 25mm2,35mm2) 1.1kV Voltage grade XLPE/PVC insulated control cable FRLS galvanised steel wire/stripped un armoured stranded coppor conductor. |
| 105 | Laying of various 3.5 cores(35mm2, 25mm2, 50 mm2, 70mm2, 95mm2,) 1.1kV Voltage grade XLPE/PVC insulated Power cable FRLS galvanised steel wire/stripped armoured stranded coppor conductor. |
| 106 | Laying of various 3.5 cores(120 mm2, 150mm2, 185mm2, 240mm2, and 300mm2 ) 1.1kV Voltage grade XLPE/PVC insulated Power cable FRLS galvanised steel wire/stripped armoured stranded coppor conductor. |
| 107 | Painting of steel structures with two coats of red oxide and one coat of Al oxide. |
| 108 | Painting of wooden structures with two coats of wood primer. |
| 109 | Hire charges of Hydra for lifting, carrying etc of material/equipments at various sites/Grid Substations/Divisional stores. |
| 110 | Hire charges of Hydraulic excavator(JCB) of 1 cum bucket. |
| 111 | Hire charges of TATA 407 or equivalent for local shifting / carraging of equipment/material . |
| 112 | Reparing of steel shutters at repair bay building at GSS bemina by way of replacing of bearings, locks, etc complte in all respects.(25'x20') including fixing of motor (On Remote mode) |
| 113 | DG Sets:Maintenanace of DG sets (62.5 kVA) including M.Oil /air filter /M Oil filter , checking of exhaust system,cleaning , tightening of nuts /bolts (complete service in all respects )from an authorised service centre . |
| 114 | AC Units :Maintenanace/servicing of split inverter type AC's of rating of 1 T,1.5T and 2T including filling of gas complete service in all respects. |
| 115 | FIRE ALARM PROTECTION AND DETECTION SYSTEM:Maintenanace of FACP system at various control rooms of 5 No Grid Substations of TLMD-I, Bemina |
| 116 | HIGH MAST LIGHTING SYSTEMMaintenanace of High Mast lights system including tighteningof loose connections, fixing/hoisting/installation of any damaged part involved in the smooth fuctioibg of the lights including of all necessary repalcements/repairs |
| 117 | CCTV Survelliance System Maintenanace/ servicing of any the constituent/part of the CCTV survelliance at Grid Subatations of TLMD-I, Bemina Total in Figures 0.0 0.0 Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |