| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GARRISON ENGINEER (AF) BANGALORE NAME OF WORK : REPAIR/MAINT TO LT PANEL EXTERNAL ELEC SUPPLY AND DISTRIBUTION NETWORK SYSTEM INCL CABLES, PANEL AND CONNECTED WORKS AT POCKET I AT CHAFB. CA NO: GE(AF)/B/ OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | Excavation in trenches not exc 1.5 m wide and n.exc 1.5 m in depth, getting out for electric cable complete in any type of soil complete all as specified and directed |
| 3 | Removing surplus excavated soil to a distance not exc 50 mtr and depositing where directed at a level n. exc 1.5 mtr above starting point complete all as specified and directed |
| 4 | Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed |
| 5 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified and directed |
| 6 | M&L for sand filling (pulverized stone dust) for sand cushioning incl spreading & levelling for protection of cable complete all as specified and directed |
| 7 | M&L for boring of holes under road pavment/hard standing by manual boring including making good to the distrubed surfaces complete all as specified and directed. |
| 8 | S&F for GI tubing light grade as in cable protection, laid in trenches/under road crossing/fixed on pole/wall/under floor with suitable iron clamps of required size incl taking down of old/unsv pipe complete for following sizes :- |
| 9 | 40 mm bore |
| 10 | 50 mm bore |
| 11 | 80 mm bore |
| 12 | Dismantling & taking out LT burnt cable ends of any size from LT panel/LT feeder pillar box/trenches any type/size, for repair/making suitable for reconnection to cable, providing lugs to burnt end of cables, preparing fresh terminals and reconnection, fixing the removed portion of cable with in trenches/along pole/ panel/feeder pillar box, including excavation of loop & refilling complete using old bricks/PCC cover and sand returning filling the excavated soil complete all as specified and directed. |
| 13 | Dismantling & taking out defective LT PVC/XLPE cable from trenches including excavation and earth work, cutting and removing defective parts and supply and fixing straight through joint heat shrink kit complete including jointing material and making connection of LT cablescomplete all as specified and directed for the following sizes:- |
| 14 | 25 sqmm to 70 sqmm, 3.5 core |
| 15 | 95 sqmm to 240 sqmm 3.5 core |
| 16 | M&L for repair/cleaning/servicing of existing/old feeder pillar box / LT panel board of any size/type incl cleaning/dusting with compressed air, tightening of all electric connections to bus bar & switchgears, re-fixing of door with proper fixing & locking arrangement, replacement of wornout lugs, nut, bolts, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire and lugs, proper connection to main earth lead, glands to be provided/replaced as required at cable entries, fixing of door front & back side with proper locking arrangement, repair to PCC work as required at site and spray painting with powder coated paint with light grey paint in outer/inner side of panel after cleaning and preparing surface incl sign writing complete all as directed. |
| 17 | M&L for servicing/overhauling of Air Circuit Breaker (ACB) 800/1200 Amp rating, 415 Volts, installed in the LT Panel by disconnection and taking out the breaker after taking power shut down of the respective LT panel and overhauling/ servicing the ACB by opening all parts and cleaning of electrical contacts with CTC/rust remover, lubricating electrical moving parts with petrolium jelly and mechanical moving parts with grease & applying Becktrol red solution to the surface of the bus bars and spouts, applying Monoplast compound at the bus bar joints after tightening of joints and replacing defective spare parts like springs/ bolts/ nuts/ washers etc, including testing, calibrating, refixing the circuit breaker and make proper functional all as directed and specified |
| 18 | S&F (in replacement) following items in the existing LT panels / Feeder Pillar box / Distribution Board of any size / type (indoor or outdoor) installed at any location and connection with using aluminum lugs incl making necessary alteration in panel/door as required for proper fixing & connection incl taking down old/unsv one complete all as specified and directed :- |
| 19 | MCCB 4 pole 63 amps rating, 16/25 KA breaking capacity, 415 Volt |
| 20 | MCCB 100 amps rating, 16/25 KA breaking capacity |
| 21 | MCCB 125 amps rating, 16/25 KA breaking capacity |
| 22 | MCCB 160 amps rating, 36 KA breaking capacity |
| 23 | MCCB 200 amps rating, 36 KA breaking capacity |
| 24 | MCCB 250 amps rating, 36 KA breaking capacity |
| 25 | MCCB 350 amps rating, 36 KA breaking capacity |
| 26 | MCCB 400 amps rating, 50 KA breaking capacity |
| 27 | MCB TPN 63 amps, 415 Volt, 'C' curve |
| 28 | MCB TPN 100 amps, 415 Volt, 'C' curve |
| 29 | Digital Multifunctional Panel meter for measuring Voltage (0-500 V), Current, PF etc including necessary PT & CT's with connected acccessories |
| 30 | Digital type Volt meter (0 to 500 volts) three phase of size 96mm x 96mm or as per existing size in the LT Panel |
| 31 | Digital type Amp meter (0 to 500 amps) digital type, three phase of size 96mm x 96mm with suitable CTs or as per existing size in the LT Panel |
| 32 | Phase Indicator lamp, LED type, RYB with holder |
| 33 | Push button switch with NO/NC contacts 415 V, 6 A , with add on Aux Contacts and connected acccessories |
| 34 | Rotatory selector switch 3/4 way 10 A for Panel meter |
| 35 | S&F in replacement of MCCB sheet metal enclosure, factory fabricated, solid neutral link suitable for fixing of MCCB of 63/100/125 amps rating, enclosure to be fixed on wall with necessary clamping/fixing/grouting arrangement as required at site incl connection of required size of existing incoming/outgoing cables with suitable lugs complete for following type of MCCB:- (Note - MCCB shall be measured and paid seperately) :- |
| 36 | For 3 pole MCCB |
| 37 | For 4 pole MCCB |
| 38 | S&F APFC microcontroller Relay 8 steps fixed to existing APFC panel of the existing make or as approved including connection and testing after taking down the existing unserviceable relay complete all as specified and as directed. |
| 39 | S&F in replacement of power contactor AC coil 240 V, 50 Hz suitable for MNX 70 Contactor complete all as specified |
| 40 | S&F in replacement of power contactor AC coil 240V, 50 Hz suitable for MNX 110/95/140 Contactor complete all as specified and as directed |
| 41 | S&F in replacement of power contactor AC coil 240V, 50 Hz suitable for MNX300/MNX400 Contactor complete all as specified and as directed |
| 42 | S&F in replacement of power contactor AC coil 240V, 50 Hz suitable for MCX40/25/32 Contactor complete all as specified and as directed |
| 43 | M&L for spray Painting of LT Panel complete of any size/capacity after preparation of surface and applying two coats of synthetic enamel (smoke grey) paint and old steel surface, including sign writing and replacing the old/unsv danger notice plate complete all as specified and directed. (Note : New danger notice plate shall be measured and paid seperately) |
| 44 | S&F Danger notice plate, made out of 1.6mm thick MS sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for LT 20X15 cm size, fixed as in repairs, complete all as specified and directed. |
| 45 | S&F of outdoor type bus bar chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including provision of 400 amp, 6 way Aluminium busbar, incl excavation,grouting/PCC/earth work etc as required for fixing of chamber and connecting incoming and out going cables complete with glands and lugs and testing incl taking down old/unsv chamber complete all as specified and directed |
| 46 | S&F of outdoor type bus bar chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including provision of 800 amp, 6 way Aluminium busbar, incl excavation,grouting/PCC/earth work etc as required for fixing of chamber and connecting incoming and out going cables complete with glands and lugs and testing incl taking down old/unsv chamber complete all as specified and directed |
| 47 | Supply, fixing & testing of LT busbar chamber board, made out of 3 mm thick CRCA sheet of size not less than 600x450x200mm duly painted with two coats of synthetic enamelled paint over one coat of red oxide primer wall mounted/semi-grouted in wall with locking arrangement, double door type, compartmentalised and provision for tapping incoming & outgoing electric connections with suitable size of lugs, glands, one MCCB will be mounted on proper din rales and comprising of the followings:-(a) Aluminium busbar chamber TPN of 300 amps rating (set of 4 strips)(b) Phase indication lamp-set of 3(c) MCCB 4 pole 415 Volts, 50 Hz, 100 amps rating, 25 KA breaking capacity - 01 No. (Note :- Cost of busbar, indication lamp & MCCB shall deemed to be included in the quoted rate) |
| 48 | Supply and laying or fixing or passing through pipe, 1100V grade, heavy duty cable with XLPE insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed incl taking down old/unsv cable complete all as specified & directed for following sizes:-(Note :- Excavation & earth work, sand cushioning, PCC cover protection & GI pipe where required shall be measured & paid seperately] |
| 49 | 10 sqmm 2 core |
| 50 | 10 sqmm 4 core |
| 51 | 16 sqmm 4 core |
| 52 | 25 sqmm 4 core |
| 53 | 35 sqmm 3.5 core |
| 54 | 50 sq mm 3.5 core |
| 55 | 70 sq mm 3.5 core |
| 56 | 95 sq mm 3.5 core |
| 57 | 120 sq mm 3.5 core |
| 58 | 240 sq mm 3.5 core |
| 59 | Disconnection of all incoming and outgoing cable connections, dismantling of exisiting LT Panel carefully with all accessories / parts and taking outside from the extg location/room and shifting at new location / place upto 1 KM distance with the help of all T&P, crane, trailor etc arrangement as required at site complete all as specified & directed |
| 60 | M&L for installation and testing of shifted LT Panel (shifted under sl item No 26.00 here in-before) of any size at new location after assemblying all connected accessories / parts and incoming and outgoing cables, control wires, earthing connections etc using glands as required at site complete all as specified & directed. |
| 61 | Disconnection of all incoming and out going connections, dismantling of exisiting DG Set with sound proof enclosure of capacity upto 250 KVA within inside/outside the room / bldg carefully and all connected accessories / parts and taking outside from the room/bldg and shifting at new location / place upto 1 KM distance with the help of all T&P, crane, trailor etc arrangement as required at site complete all as specified & directed |
| 62 | M&L for Installation, testing and commissioning of shifted DG set (shifted under sl item No 29 here in-before) upto 250 KVA capacity with entire connected accessories and parts of DG set with complete arrangement at new location after assemblying all connected accessoried / parts and sound proof enclosure including all incoming and outgoing cables using glands and earthing connections as required at site complete all as specified & directed Notes for item No 26.00 to 29.00 :-(i) Cost of all T&P, crane, trailor, equipment etc required all accessories, equipments, labour cost etc required for proper completion of work shall deemed to be included in the quoted rate.(ii) Excavation, earth work, cable, PCC/civil work for foundation, earthing etc shall be measured and paid seperately under respective items of schedule. |
| 63 | M&L for cement concrete type D-2, 1:4:8 (using 40 mm graded crushed stone aggregate) as in foundation, sub floors/sub-bases, and paving etc complete all as specified & directed |
| 64 | M&L for providing Cement Concrete 1:2:4 type B-1 (using 20 mm graded granite stone aggregate) as in coping/platform for steel pole etc, kerbs or rounded or chamfered, finished surface smooth complete all as specified and as directed |
| 65 | M&L for preparation of old painted surfaces and painting of surfaces of any description of steel / grill / sub-station MS gate etc, over 10 cm in width or girth with synthetic enamel paint including complete all as specified and directed |
| 66 | M&L for preperation of old painted surfaces and painting of surfaces of any description of steel / grill / sub-station over 10 cm in width or girth with aluminium paint complete all as specified and directed |
| 67 | M&L for complete inspection/cleaning/servicing/overhauling/repairing/maintenance, testing and commissioning of existing/old UPS of 120 KVA capacity, 3 Phase, 415 Volts, of any make, by opening all parts, checking and cleaning of all electrical & battery connections, cooling system, checking of corrosion, testing of electrical faults, check battery charger functionality, clean or replace dust filters and verufy that cooling fans are fully operational, update DSP firmware, check for alarm on the LCD/remote monitoring system and monitor input/output voltage levels with replacement of any type of unsv/faulty spare parts/ accessories of UPS to make proper functioning of UPS incl batteries & battery charger including connection with the all 34 existing batteries of 12 Volt, 150 AH rating each, which are to be connected with UPS incl provision of copper cable / terminals all as required essential for proper connections for batteries & battery charger, necessary cable connections between batteries and UPS as required. Also complete UPS equipment and all Batteries with MS rack stand to be taken out carefully at outside from the MES Power House bldg and shifting it at new location / bldg upto 500 Mtr distance where directed with the help of all T&P, crane, trailor etc arrangement as required at site including all necessary cable and batteries connections as required at site with existing electrical system/ DB at new desired location incl testing complete in all respect complete all as specified and directed |
| 68 | Notes for item No 34:- (i) Only authorized / specialist personnel / Service engineer of OEM of UPS shall repair and execute the work. (ii) All items of spares, accessories, fittings, sundries, apparatus or labour whether specified in detail or not but which is necessary for successful functioning, testing & commissioning of the existing / old UPS 120 KVA including all batteries & battery charger shall be part of installation and rate deemed to be included in quoted rate.(iii) Cost of transportation, T&P, crane, trailor etc for shifting and installation of the existing UPS 120 KVA with batteries & charger with MS rack stand at new location / bldg shall be deemed to be included in quoted rate. |
| 69 | M&L for complete inspection/cleaning/servicing/overhauling/repairing/maintenance and testing and commissioning of existing/old UPS of 60 KVA capacity, 3 Phase, 415 Volts, of any make at OT Complex, to ensure clean, consistent power with zero transfer time during outages, by opening all parts, checking and cleaning of all electrical & battery connections, cooling system, checking of corrosion, testing of electrical faults, check battery charger functionality, clean or replace dust filters and verifying that cooling fans and capacitors for reliability, to make fully operational, monitor system of input/output voltage levels with replacement of any type of unsv/faulty spare parts/ fuses/accessories of UPS to make proper functioning of UPS incl batteries & battery charger including connection with the all 60 existing batteries of 12 Volt, 64/100 AH rating each, which are to be connected with UPS incl provision of copper cable / terminals all as required essential for proper connections for batteries & battery charger, necessary cable connections between batteries and UPS as required including all necessary cable and batteries connections as required at site with existing electrical system/ DB incl testing complete in all respect all as specified and directed. |
| 70 | Notes for item No 35.00 :- (i) Authorized / specialist personnel / OEM of UPS shall repair and execute the work. (ii) All items of spares, accessories, fittings, sundries, apparatus or labour whether specified in detail or not but which is necessary for successful functioning & testing of the UPS 60 KVA shall be part of installation and rate deemed to be included in quoted rate. |
| 71 | M&L for Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel using GI nut, bolts & washer complete all as specified & directed |
| 72 | M&L for Earthing complete with galvanised steel earth plate electrode 60x60cmx6mm thick, buried directly in ground ( earth pit not less than 2.25mtrs deep below ground level) with top edge of the plate not less than 1.5mtrs below normal ground level, connected to galvanised earth lead wire 4.00 mm dia as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified & directed |
| 73 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth strip of size 32 x 6 mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in elecrtical plate No 3 of SSR pt I, connected to LT Panel/DB/earthing test point including PCC chamber, RCC cover 50mm thick with 8 mm dia bars, protection pipe, funnel etc including excavation, earth work, disposal of surplus soil and earth strip protection pipe of GI 40 mm bore light grade upto 7.5 metre including testing on completion complete all as specified & directed |
| 74 | M&L for Testing of earthing resistance of existing earthing using calibrated 3/4 wire digital Earth resistance tester and recording the earth resistance value in register obtaining the signature of user and MES excecutive after verification complete all as specified & directed.(Note : Contractor has to provide digital earth resistance tester and should be available all the time during the contract period) |
| 75 | S&F in replacement of changeover switch with sheet metal enclosure, factory fabricated, 415 Volt, changeover switch to be fixed on wall with necessary MS clamping/fixing/grouting arrangement with civil work all as required at site incl connection of existing incoming/outgoing cables with suitable lugs complete of following ratings :- |
| 76 | 125 amps, 4 pole, 415 Volt, Off load |
| 77 | 250 amps, 4 pole, 415 Volt, Off load |
| 78 | 400 amps, 4 pole, 415 Volt, On load |
| 79 | 630 amps, 4 pole, 415 Volt, On load |
| 80 | S&F Steel tubular swaged poles,9 m long complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 and marking ZEBRA pattern with alternate yellow and black colour to steel tubular poles 1.5m from the bottom of pole and one coat of aluminium painting for the remaining portion of pole including numbering of poles complete all as specified and directed (Note :- Item required for excavation earth work, pole foundation, coping, plinth protection etc shall be measured and paid separately under relevant item of schedule) |
| 81 | Dismantling and taking out existing/old/damaged PCC pole any type/size after disconnection all existing incoming/outgoing existing cable connections complete all as specified & directed |
| 82 | Dismantling and taking out existing/old/damaged steel pole any type/size after disconnection all existing incoming/outgoing existing cable connections complete all as specified & directed |
| 83 | M&L for painting of steel tubular poles any length with one coat of aluminium paint and also marking ZEBRA pattern with alternate yellow and black colour to steel tubular poles 1.5m from the bottom of pole including numbering of poles using synthetic enamel paint complete all as specified and directed |
| 84 | M&L for painting of RCC/PCC poles any length with one coat of white cement based paint ans also marking ZEBRA pattern with alternate yellow and black colour to RCC/PCC poles 1.5m from the bottom of pole including numbering of poles using synthetic enamel paint complete all as specified and directed Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |