| 1 | Providing Electrical Installaions |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in PVC Casing and caping, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface casing and caping as required 2X1.5Sq.mm+1X1.5Sq.mm Earth wire |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in PVC Casing and capingalongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in PVC Casing and caping as required 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Supplying and fixing of various sizes of Casing capping/PVC Conduit pipes along with accessories in surface of various size. |
| 7 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required. i) 2 modules |
| 8 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required. ii) 4 modules |
| 9 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required. iii) 6 modules |
| 10 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required. iv) 8 modules |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. i) 5/ 6 Amps switch. |
| 12 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (ii) Bell push,. |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. iii) 15/ 16 Amps switch. |
| 14 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. iv) 6 pin 15/16 A socket outlet. |
| 15 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. V) 5 pin 5/6 A socket outlet. |
| 16 | Supplying and fixing ceiling rose connections etc. as required. |
| 17 | Supplying and fixing PVC block including connections etc. as required. |
| 18 | Supplying and fixing Angle/Stright lamp holder all accessories including connections complete in all respect etc. as required:- |
| 19 | Providing and fixing of watt surface mounted Luminaire LED batten ,having high Quality design aluminium extruded decorative end caps and it should be compatible with specification i.e. Power Factor >.9,Harmonic Distortion<10% and efficiency>100Lumens per watt ,CRI> 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc (24 watt) |
| 20 | Providing and fixing of LED Lamp/Bulb ,having high Quality design aluminium extruded decorative end caps and it should be compatible with specification i.e. Power Factor >.9,Harmonic Distortion<10% and efficiency>100Lumens per watt ,CRI> 80 suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc as:Make Philips,Panasonic jaquar or its equivalent as approved by Er-In-Charge( Five year warranty) 09 watt |
| 21 | Supplying and fixing following way, horizontal type three pole and neutral, sheetsteel, MCB distribution board, 415 volts, on surface/ recess, complete with tinnedcopper bus bar, neutral bus bar, earth bar, din bar, interconnections, powderpainted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way (4 + 36), Double door |
| 22 | Supplying and fixing following rating, three pole with neutral,415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A (MCCB/MCB) |
| 23 | Supplying and fixing following rating, Four pole MCB DB complete with connections, testing and commissioning etc. as required. 100 A (MCCB/MCB) |
| 24 | Supplying and fixing following rating, three pole with neutral,415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 100 A (MCCB/MCB) |
| 25 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 26 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A (MCCB/) |
| 27 | Supply and laying of Cat 6 unshielded twisted pair (UTP) with RJ 45 connectors in surface-mounted PVC conduit/ casing-capping , including tagging, dressing , testing and commissionings, complete as required. |
| 28 | Supply , fixing and testing of 5-port networking switch (D-link make ) on surface/rack as required. Please Enable Macros to View BoQ information |