| 1 | Supply, installing, testing and commissioning of LT out door type factory made(CPRI Approved ), junction box of size 750mmX600mm X500mm (over all dimension )with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 40X6 mm in horizontal sides of the frame LT Junction box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 56 class protection and made of 3.15mm MS sheet and 40x40x5 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and directed. With double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock-2Nos with 3 keys. Aluminium bus bar of 450 Amps rating with drilled holes for incoming /outgoing cable core connection including aluminium lugs, GI bolts, Nuts and washers of suitable size. Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws, bolts, nuts and washers, complete all as specified and as directed. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 50 sqmm to 400 Sqmm by drawing /digging out cable from loops in trenches outside the Bldg inclusive of necessary |
| 2 | excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable lugs for terminal connections of cables, Platform of U shape for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 (using 20 mm graded crushed stone aggregate) on top and grouting bolts etc for Feeder pillar box complete all as specified and as directed.Note:- All types of certificates and design verification with switch gears (ACB/MCCB) confirming to IS/IEC 61439/2011 Part- I & II with short circuit test 4000 A with breaking capacity 65 KA shall be submitted by the contractor before execution of work.. |
| 3 | Supply, installing, testing and commissioning of LT out door type factory made (CPRI Approved), Feeder pillar box of size 900mmX800mmX500mm (over all dimension )with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 40X6 mm in horizontal sides of the frame LT FPB (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 56 class protection and made of 3.15mm MS sheet and 40x40x5 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and directed with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock-2Nos with 3 keys. with MCCB 4 pole, 415 volts AC grade, 200 Amps rating and 25 KA rupturing capacity - 01 No Aluminium bus bar of size 10X6mmX400mm long with drilled holes for incoming /out going cable core connection including aluminium lugs ,GI bolts ,Nuts and washers of suitable size. Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws ,bolts, nuts and washers , all as specified and as directed., Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone aggregate, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 |
| 4 | (using 20 mm graded crushed stone aggregate) on top and grouting bolts etc for Feeder pillar box. The platform shall be such that it is of a height 45 cm above the nearest road level including connections of all out going/in coming existing cables of size 50 sqmm to 400 Sqmm by drawing /digging out cable from loops in trenches outside the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable lugs for terminal connections of cables complete all as specified and directed by Engr-in-chargeNote :- All types of certificates and design verification with switch gears (ACB/MCCB) confirming to IS/IEC 61439/2011 Part- I & II with short circuit test 4000 A with breaking capacity 65 KA shall be submitted by the contractor before execution of work. |
| 5 | Supply, installing, testing and commissioning, factory made and tested . LT feeder pillar box (KIOSK) 1500mm x1200x 700mm size, outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 1000 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 10 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. Platform of U shape for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone aggregate, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for Feeder pillar box complete all as specified and directed including connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation |
| 6 | and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, , All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed.Note :- All types of certificates and design verification with switch gears (ACB/MCCB) confirming to IS/IEC 61439/2011 Part- I & II with short circuit test 4000 A with breaking capacity 65 KA shall be submitted by the contractor before execution of work. |
| 7 | The scope of work includes the following :-(I) Incoming :- (i) ACB 4 Pole, Tharmal Magnetic adjustable type 630A, Breaking capacity 50 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (ii) Digital voltmeter 0-500 volts with selector switch - 01 No (iii) Digital Amp meter 0-630 Amp with selector switch & CT - 01 No (iv) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set (II) Outgoing :-(i) MCCB 4 Pole, Thermal Magnetic Based adjustable type 250A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (ii) MCCB 4 Pole, Thermal Magnetic Based adjustable type 160A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -04 Nos along with Spreader terminals (iv) MCB TPN 63 Amp 10 KA C-Curve - 1No (v) Indicator lamp LED type (R, Y, B) complete with fuse -06 Set |
| 8 | All as per Srl item No 3 here-in-before complete but Size 1200 x1000x600 mm and Busbar 600 Amps rating complete all as specified and directed. |
| 9 | (I) Incoming :- (i) MCCB 4 Pole, Tharmal Magnetic adjustable type 400A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals.(ii) Digital voltmeter 0-500 volts with selector switch - 01 No (iii) Digital Amp meter 0-630 Amp with selector switch & CT of ratio 630/5- 01 No (iv) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set (II) Outgoing :-(i) MCCB 4 Pole, Thermal Magnetic Based adjustable type 200 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -02 Nos along with Spreader terminals (ii) MCCB 4 Pole, Thermal Magnetic Based adjustable type 100A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (iii) MCB TPN 40 Amp 10 KA C-Curve - 2 Nos (iv) Indicator lamp LED type (R, Y, B) complete with fuse -05 Set |
| 10 | M&L for plate earthing for sub station equipments complete with galvanized steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground (Earth pit not less than 2.25 Mtr deep below normal ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level connecting with galvanized iron iron strip 32x6mm as earthing lead by means of bolt nut check nuts and washers of galvanized iron and provision of GI tubing light grade (ISI marked)of size 40 mm for protection of GI earth wire upto test point, 20mm dia GI tubing medium grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in soft / loose soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion. NOTE :-Rates inclusive of necessary excavation in soft / loose soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing) . |
| 11 | Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / walls / paths / drain / culverts or encased in GI pipe complete all as specified and directed. Cables of the following sizes:-(Note;- (i) Rate quotted includes terminal Lugs/ wall cutting/ floor cutting and making good damged portion matching with existing surface with all existing finishes.) (ii) Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection for road crossings will be measured and paid separately all as specified and directed. |
| 12 | 16 Sqmm 4 core |
| 13 | 25 Sqmm 4core |
| 14 | 35 Sqmm 3.5 core |
| 15 | 50 Sqmm 3.5 core |
| 16 | 70 Sqmm 3.5 core |
| 17 | 95 Sqmm 3.5 core |
| 18 | 120 Sqmm 3.5 core |
| 19 | 150 Sqmm 3.5 core |
| 20 | 185 Sqmm 3.5 core |
| 21 | 240 Sqmm 3.5 core |
| 22 | 300 Sqmm 3.5 core |
| 23 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as specified in the following type of soils: |
| 24 | Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each in soft/loose soil complete all as specified & directed. |
| 25 | Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified & directed. |
| 26 | M & L for local sand coushioning with dry and clean sand over and under the cable for protection of cable , 80 mm sand laid before laying the cable and 150 mm sand after laying the cable and filling the sand in cable duct of inside the sub station building and then punned. After punning the thickness of sand cushioning shall be 18 cm complete all as specified and directed. Note :- Only punned thickness of sand shall be measured for payment. |
| 27 | M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm complete all as specified and directed. |
| 28 | Supply and laying galvanised steel tubing, light grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls ( with required size flat iron clamp bolts, nuts and washers ) pipes of the following sizes :- |
| 29 | 40 mm bore |
| 30 | 50 mm bore |
| 31 | 80 mm bore |
| 32 | 100 mm bore |
| 33 | M&L for auguring of hole suitable for passing 40mm to 100mm bore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line as specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified and directed. Note:- Pipe shall be measured and paid separately under appropriate items and any dahage to existing cables of any type shall be made good by the Bidder without any extra cost to department. |
| 34 | M&L for Cutting of worn-out / burnt aluminium cable terminal lugs from the HT/LT cable , crimping of new aluminium cable core and fixing with transformer/ Panel MCCB terminal/ FPB/ JB/ pole/DBs/ stud including cutting/ dressing of cable, disconnecting under ground / OH line cable conductor , cutting down worn-out portion and refixing and including suitable lugs complete , including under ground cables of any type and size for repairs including taking out under ground cable loop from ground and making connections of restoration of electric supply with complete all as specified and directed. |
| 35 | S&F pole mounting type junction box factory made of size 300x200x100mm of FRP sheet duly powder coated with front openable hinged door, locking arrangements, with 4 Nos aluminium bus bars 40 Amps rating mounted on porcelain insulator, cable glands and lugs consisting DP 6 Amps 'C' series ,mounted on MCB rail -01 no. including mild steel flat iron clamp made out of 40x4mm FI, nuts, bolts and washers complete all as specified and directed. |
| 36 | Taking down Old unsv Aluminium Cable 2 Core 4 Sqmm connected from overhead conductor to the street light complete all as specified and directed. |
| 37 | Supply & fixing 1.5 Sqmm three core (nominal area) PVC insulated and PVC sheathed multi stranded unarmed Copper conductor cable LT 1100 volt grade FRLS drawn through pole for connecting to street light and pole JBs with cable terminal pole wirings connecting up with streetlight feeder(Junction box) complete all as specified and directed. |
| 38 | S&F service main distribution (SMC JUNCTION BOX ) box minimum inside size 395 x 235 x 150 mm with Bus bar 200 amps 4 pole for distribution of multiple nos of service connection, (ISI marked )weather and moisture-proof, nuts and bolted bus bar system, 200 Amps capacity and fixing on pole/wall ground with suitable FI clamp nuts and bolt complete all as specified and directed. |
| 39 | Dismantling old existing ACSR conductor of any type/size complete all as specified and directed. |
| 40 | Dismantling old existing MS cross arms of any type/shape complete all as specified and directed. |
| 41 | Dismantling old existing Insulators of any type/shape complete all as specified and directed. |
| 42 | Dismantling old existing LT stay complete all as specified and directed. |
| 43 | Supplying and fixing out door End cable jointing Kit for 1100 V grade cable for complete with jointing material ( heat shrink type) and accessories suitable for 300 sqmm to 400 sqmm 3.5/4 core XLPE armoured aluminium conductor cable and testing after jointing with complete all as specified and directed. |
| 44 | M&L for plate earthing for Street Light Tubular Pole complete with galvanized steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground (Earth pit not less than 2.25 Mtr deep below normal ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level connecting with galvanized iron Wire 04mm dia as earthing lead by means of bolt nut check nuts and washers of galvanized iron and provision of GI tubing light grade (ISI marked)of size 40 mm for protection of GI earth wire upto test point, 20mm dia GI medium grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in soft / loose soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion. Note :- Rates inclusive of necessary excavation in soft / loose soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing) . Please Enable Macros to View BoQ information |