| 1 | Excavation in soft / loose soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable all as specified and directed by Engr-in-Charge. |
| 2 | Returning filling using excavated soil including spreading leveling, watering and well ramming in layers n exc 25 cms all as specified and directed by Engr-in-Charge . |
| 3 | Removal of surplus excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point all as specified and directed by Engr-in-Charge |
| 4 | M&L for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed and making the disturbed surface after relaying the cable and making joints suitable for aluminium conductor of 95 to 150 Sqmm 3.5 core complete all as specified and directed.Note : Taking down the fault cable, excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this sch. |
| 5 | M&L for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed and making the disturbed surface after relaying the cable and making joints suitable for aluminium conductor of 185 to 300 Sqmm 3.5 core complete all as specified and directed.Note : Taking down the fault cable, excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this sch. |
| 6 | Supplying and laying in replacement of GI tubing medium grade of 100 mm dia for cable protection in trenches/duct/fixing to pole/wall or in such similar position complete all as specified and directed. |
| 7 | Supplying and laying in replacement of GI tubing medium grade of 80 mm dia for cable protection in trenches/duct/fixing to pole/wall or in such similar position complete all as specified and directed. |
| 8 | Supplying and laying in replacement of GI tubing medium grade of 50 mm dia for cable protection in trenches/duct/fixing to pole/wall or in such similar position complete all as specified and directed. |
| 9 | Taking up old unserviceable LT UG cables of 25 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 10 | Taking up old unserviceable LT UG cables of 35 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 11 | Taking up old unserviceable LT UG cables of 50 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 12 | Taking up old unserviceable LT UG cables of 70 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 13 | Taking up old unserviceable LT UG cables of 95 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 14 | Taking up old unserviceable LT UG cables of 120 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 15 | Taking up old unserviceable LT UG cables of 185 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 16 | Taking up old unserviceable LT UG cables of 240 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 17 | Taking up old unserviceable LT UG cables of 300 Sqmm 3.5 core from trench/poles/wall etc complete all as specified and directed. |
| 18 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 25 Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 19 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 35 Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 20 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 50Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 21 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 70Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 22 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 95Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 23 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 120 Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 24 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 185 Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 25 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 240 Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed.. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 26 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 300 Sqmm 3.5 core complete all as specified and make at PS complete all as specified and directed. Note : Earth works excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 27 | M&L for Re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 50 Sqmm 3.5 core and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge. Note : Earth works excavation, returning filling, removal of surplus soil, shall be measured and paid separately under relevant of this Items. |
| 28 | M&L for Re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 95 Sqmm 3.5 core and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge. Note : Earth works excavation, returning filling, removal of surplus soil, shall be measured and paid separately under relevant of this Items. |
| 29 | M&L for Re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 120 Sqmm 3.5 core and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge. Note : Earth works excavation, returning filling, removal of surplus soil, shall be measured and paid separately under relevant of this Items. |
| 30 | M&L for Re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 185 Sqmm 3.5 core and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge. Note : Earth works excavation, returning filling, removal of surplus soil, shall be measured and paid separately under relevant of this Items. |
| 31 | M&L for Re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 240 Sqmm 3.5 core and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge.Note : Earth works excavation, returning filling, removal of surplus soil, shall be measured and paid separately under relevant of this Items. |
| 32 | M&L for Re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of 300 Sqmm 3.5 core and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge.Note : Earth works excavation, returning filling, removal of surplus soil, shall be measured and paid separately under relevant of this Items. |
| 33 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed. |
| 34 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 63 mm and inner dia 50 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed. |
| 35 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 77 mm and inner dia 63 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed. |
| 36 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 90 mm and inner dia 76 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed. |
| 37 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 110 mm and inner dia 95 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed. |
| 38 | Material and labour for earthing with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to galvanised iron strip 32 mm x 6 mm by means of GI Welding made out of galvanised iron mild steel and 40 mm dia GI pipe \\"light grade\\" for protection of earth lead, 20 mm dia GI pipe for watering and earth plate surrounded by packed layer of coal and common salt, 15cm thick all around bottom and top, watering pipe of 20 mm bore of light grade with funnel all as shown in electrical plate No 3 of SSR Part-I (2009) and connecting to earthing test point, main switch board, transformer neutral and testing on completion as directed including earthing pit in PCC (1:3:6) type C-1, pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 400 x 400 x 100 mm with one handle made out of 8 mm dia round bar, wire mesh and testing complete all as specified and as directed including dismantling old defective earth pit.Note: (i) Cost of GI earth Strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item.(ii) The unit rate shall also includes for Wire mesh, funnel, excavation.returninng & filling. PCC chamber pit,RCC cover & test point.(iii) If the desired earth resistance is not achived during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissable. |
| 39 | Supply and fixing as in repair for GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 32 mm x 6mm thick, Galvanised using porcelain clit/post insulators, complete all as specified and as directed |
| 40 | Supply and fixing as in repair for GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 25 mm x 3 mm thick, Galvanised using porcelain clit/post insulators, complete all as specified and as directed |
| 41 | Supply and fix in replacement of on load automatic change over switch 415 V, 4 pole, 125 A as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 42 | Supply and fix in replacement on load change over switch 415 V, 4 pole, 160 A as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 43 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 63 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 44 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 100 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 45 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 46 | M & L for repair of LT Panel board outdoor type repair/replace damaged door hinges set of three nos front and back side and legs 40x40x6mm MS angle and necessary cutting, welding drilling hole,pcc repairs,cables slevees with colour code,repairs old us wiring etc works required at site complete all as specified and directed by Engr-in-Charge . |
| 47 | S&F in replacement of digital Volt meter (0-500) including connections and testing for proper functioning complete all as specified and directed. by Engr-in-Charge. |
| 48 | S&F in replacement of digital ammeter including connections and testing for proper functioning complete all as specified and directed. by Engr-in-Charge. |
| 49 | S&F in replacement of Indicating Lamp R. Y. B (LED) Type including connections and testing for proper functioning complete all as specified and directed. |
| 50 | S&F in replacement of selector switch for ammeter/ volt mete including connections and testing for proper functioning complete all as specified and directed. by Engr-in-Charge . |
| 51 | S&F in replacement of CTs of required rating including connections and testing for proper functioning complete all as specified and directed. by Engr-in-Charge . |
| 52 | Material & Labour for spray painting to feeder pillar box / LT panel & duct cover etc, including angle iron frame with two coats of synthetic enamel paint grey or colour as approved by GE / Engr in -Charge as per site suitability synthetic enamel paint including door welding with hinges complete as specified and directed by Engr-in-Charge. |
| 53 | M&L for PCC 1:2:4 type B-2 using 20mm grade stone aggregate as in coping of LT panels including necessary form work and fair finishing to exposed surface without using extra cement complete all as specified. |
| 54 | M/L for attending LT breakdown complaints/defects from transformer LT terminal box upto Bldg feeder pillar box/DBs with connected switchgears, cables etc complete for making the continuity of supply after rectifying the defects of the electrical network by carrying out with the following scope of work:- (i) cable faults : disconnecting the both ends of cable and check the insulation resistance value.Physical inspection / tracing the cable in cable duct/ trenches. Cutting/disconnecting damaged portion and re-checking for insulation value, and make the cable connection after rectification at both end terminations to restore the power supply.(ii) unserviceable control switch gears / MCCBs / MCB: remove the MCCB/MCB from the panel board and clean the carbonized / burnt surfaces with varnish / CRC solution to make good and fix the new MCCB of suitable rating and connect the cable to MCCB terminals with proper lugging and by applying proper torque to avoid loose connections. spreader links shall be provided if necessary as per site requirement.(iii) Terminals/lugs failure: check for any cable terminal damage / melting by over heating, loose contacts. the damaged portion of cable shall be removed and fixing the lugs and terminate the cable by applying proper torque to avoid loose connections and proper re-distribution of over loading of cable complete all as specifed and as directed.Note :- (i) cable joint kit, MCCB/MCB, lugs and cable fault detection by fault finding machine, any excavation earth work shall be measured and paid seperately under relevant items. spreader links /insulation tape shall be deemed to be included in the rate quoted.(iii) Each Breakdown complaint/defect attended shall be measured as one job through job card.(iv) The contractor shall depute necessary man power on daily basis for rectifying the jobs including sundays and holidays. |
| 55 | M&L for detecting LT UG cable faults located in any stretch/ depth with sophisticated cable fault locator consisting of microprocessor based pre-locator system, surge generator of capacity upto 1.1 KV, fault pin point surge wave reciever, cable indentification instrument , cable tracer for exact location of under ground cable routes. Note: The rate quoted deemed to be inclusive of transportation of equipment from any location and charges for service engineer for identifying the fault including their boarding & lodging complete. |
| 56 | Design, Supply, installing testing and commissioning factory fabricated out door type totally enclosed LT cubical panel board suitable size with busbar, conforming to relevant IS and protection class IP-65 ,dust,vermin and weather proof fabricated out of 3.15mm thick CRCA sheet duly powder coated ,mounted on 40x40x5mm MS angle iron frame,duly welded in shape and coated with two coats of synthetic enamel paint of approved colour over a coat of redoxide primer including necessary grouting of legs 300mm deep in ground in PCC 1:4:8 type D2 using 40mm graded stone aggregate ,panel base to be 500mm above ground level with suitable compartments for controls and Monitors including cable glands for incoming and outgoing cables,locking arrangement,including accomodating, unserviceable LT panels supply and fixing the following accessories/items with necessary internal panel wiring with suitable size of Copper wire PVC insulated & sheathed multi stranded complete all as specified and as directed by Engr-in-charge.including Supply and fixing the following :- (a) MCCB TPN 250 Amps 50 Hz, 415 V with rupturing capacity 36 KA-1 No (Incoming)make : L& T (b) MCCB TPN 100 Amps 50 Hz, 415 V with rupturing capacity 35 KA-02 Nos (Outgoing)make : L& T (c) MCCB TPN 63 Amps 50 Hz, 415 V with rupturing capacity 25 KA - 01 Nos (Outgoing)make : L& T (d) Voltmeter 0-500V with selector switch (Digital type)-01 Nomake : L& T (e) Ammeter 0-50 Amps with CTs (50/5Amps) and selector switch(Digital type)-01 Nomake : L& T (f) Indicating lamps (RYB) -01 Set(g) PCC Foundation (Civil works) for grouting of panel |
| 57 | M&L for dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity 800 to 1250 Amps ,415 V 50 HZ of L&T Make/C&S/GE/ABB make, strip opening the Air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- a) Cleaning the insulation parts including bushings with CRC solution.b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts. d) Check arc chutes for damage. e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual. f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Checking control device free for operation. j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional Note : The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like Shunt release & trip coil etc will be measured & paid separately under relevant schedule items |
| 58 | Supply only CTs suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider |
| 59 | Supply only auxiliary contact block suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: L&T/C&S/ GE/ABB/Havells/Hager/ Schneider |
| 60 | Supply only arcing contacts (fixed/ moving) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider |
| 61 | Supply only arc chutes (for 415 V) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider. |
| 62 | Supply only shunt release / under voltage release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider. |
| 63 | Supply only cluster contact suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: L&T/C&S/ GE/ABB/Havells/Hager |
| 64 | Supply only trip coil suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing of Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider. |
| 65 | Supply only microprocessor based relay suitable for Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider |
| 66 | Supply only of RS 485-ETHERNET converter of existing unserviceable spares parts suitable for Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed. |
| 67 | Supply only of UV coil 3WT9853-IJN00-415 Volt of existing unserviceable spares parts suitable for Make: Siemens/L&T/C&S/ GE/ABB/Havells/Hager/ Schneider air circuit breakers of rating 800 Amps to 1250 Amps complete all as specified and as directed. |
| 68 | Supply and fixing as in repair service wire aluminium conductor Weather Proof 10 Sqmm two core complete all as specified and as directed |
| 69 | Supply and laying broken stone or Boulders filling of Gauge not exc. 63 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and as directed |
| 70 | Material and labour for cross arms, bracing, supports, clamps and back plate fabricated from structural MS section for gate including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of taking down complete all as specified and as directed |
| 71 | M & L for Cutting vegetation around the LT panel upto 1.5m distance and surface dressing not exceeding 15 cm deep including removing the materials to a distance not-exc 60 mtr complete all as specified and directed Please Enable Macros to View BoQ information |