| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 19-06-2026 | Addendum and Corrigendum No. 1 | BOQ | 16-07-2026 |
| Sl. No. | Item Description |
| 1 | NATIONAL CAPITAL REGION TRANSPORT CORPORATION LTD. Bid No. DM/MS/CPM-GZ/313: Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre at Sarai Kale Khan Namo Bharat Station. Price Bid NATIONAL CAPITAL REGION TRANSPORT CORPORATION LTD Gatishakti Bhawan INA, New Delhi –110 023 Preamble Name of Work: Bid No. DM/MS/CPM-GZ/313: Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre at Sarai Kale Khan Namo Bharat Station. S.No. Description |
| 2 | The Price bid shall be read in conjunction with the Bidding Documents. |
| 3 | There are 4 Schedules in the Financial Bid as follows : (i) Schedule - A (DSR-2023 Civil Items)(ii) Schedule - B (DSR-2023 Civil Finishing Items)(iii) Schedule - C (NDSR Civil Items)(iv) Schedule - D (DSR-2025 E&M Items)The bidder is required to quote a flat percentage \\"Excess\\" (+) / \\"Less\\" (-) / \\"At par\\" with respect to the Total amount of all the Schedules in the \\"BoQ1\\" Sheet and further discount if any may be Quoted in the \\"BOQ2\\" Sheet along with methodology of discount if any. The percentage quoted by the Bidder in \\"BoQ1\\" sheet and discount (if any) quoted by the Bidder in the \\"BoQ2\\" will be applied on the individual rate for all schedules for the purpose of payment to the Contractor. |
| 4 | The quantities for various items provided in the Price Bid are estimated quantities and are given to provide a common basis for Bidding. During the execution of works, the same may vary based upon \\"Good for Construction\\" (GFC) drawings approved by the Engineer and as per the site conditions. The basis of the payment will be the actual quantities of the work executed and accepted by the Engineer or quantities as per the GFC drawings whichever is less and shall be paid / valued as per the accepted rates. |
| 5 | The quoted rates for various items are for completed and finished items of work complete in all respects. It will be deemed to include all the cost involved in the execution of the items and shall include all duties, taxes [except Goods and Service Tax (GST) and Custom Duty] royalties, cess, overheads, profit and other levies payable by the Bidder under the Contract, or for any other cause etc. The Bidder shall be required to consider this aspect while quoting rates. It shall include all general risks, liabilities and obligations set out or implied in the Contract shall and including remedy of any defects during the Defect Liability Period, unless otherwise provided in the Contract. The whole cost of complying with the provisions of the Contract shall be deemed to have been included in the quoted rates. GST as prevalent will be paid extra. |
| 6 | Bidder may please note that to perform this contract nothing extra shall be payable on account of field constraints, non-availability of uninterrupted front, cost of project management, monitoring, coordination and supervision, cost of adhering to quality requirements (QA/QC), cost of adhering to SHE requirements, cost of preparing drawings and documents, as-built records and documentation, preparation of detailed scheme for taking necessary clearance and approval from the concerned authority and other local bodies etc. |
| 7 | Income Tax and any other statutory taxes to be deducted at source will be deducted by the Employer from the due payments of the contractor in accordance with the prevailing rules in force. |
| 8 | Bidder should not tamper the Price Bid. If the Price Bid is found to be modified by the bidder, then the same will be treated as incomplete and non-responsive and may result in the rejection of the Bid. |
| 9 | Method of Quoting the Price in the Price Bid:The Price Bid is in Excel Format and the Quoting the Price in the Price Bid should be as Follows: (i) Whole Excel Worksheet is Locked except the Cells which are highlighted in Blue. (ii) Bidders are required to fill these cells which are highlighted in Blue only. (iii) Bidder is required to quote a flat percentage Excess/Less/At par on 'Total Amount of all the Schedules' in \\"BOQ1'' Sheet of Price Bid and further discount if any in BOQ2 of Price Bid along with methodolodgy of discount if any. (iv) All 'blanks' in the Pricing Document, where the Bidder is permitted to quote shall be filled in. (v) If some % is quoted inspite of marking 'At par' that % will not be considered and it will be taken as \\"At par\\" on basic amount. Failure to quote the % in case of excess or less for the \\"Total amount of Schedule\\" shall be treated as \\"At Par\\" and shall be evaluated accordingly. (vi) Bidder is required to quote Rates in INR only. |
| 10 | Errors will be corrected by the Employer for any arithmetic errors in computation or summation as per contract conditions. |
| 11 | For Calculation of rates (excluding GST) of DSR 2023 Civil & Civil finishing items, following Methodology issued by CPWD vide Office Memorendum (OM) dated 08.08.2024 have been adopted:As per CPWD OM the rates of individual items of DSR 2023 has been multiplied with correction factor on account of GST @ 0.973 to the existing rate of DSR 2023 item in order to achieve modified DSR rate and then reduced the corrected rate by 18% for making DSR item excluding GST.Note:The above Methodology shall be applicable for calculating the rate of Individual Items of DSR 2023 in Schedule A & B (to be executed under Lump Sum amount).Based on the above Methodology and price quoted by the bidder payment shall be made for the individual items executed under Lump Sum amount of DSR 2023 in Schedule A & B. For Calculation of rates of Schedule - D (excluding GST) of E&M DSR -2025, reduced the rate by applicable GST% for the item for making DSR item excluding GST. Note:The above Methodology shall be applicable for calculating the rate of Individual Items of DSR 2025 in Schedule D (to be executed under Lump Sum amount). NOTE: The work may have to be done during the block periods (during non-operational hours) as per direction of the Engineer-in-charge. |
| 12 | SCHEDULE-A |
| 13 | SCHEDULE-B |
| 14 | SCHEDULE-C |
| 15 | SCHEDULE-D |
| 16 | Total Amount of Schedules.(Excluding GST) |
| 17 | Total amount of schedule Letter of Price Bid / R1 Bid No.: DM/MS/CPM-GZ/313 To National Capital Region Transport Corportation Limited GatiShakti Bhawan,INA, New Delhi- 110023 We, the undersigned, declare that: (a) We have examined and have no reservations to the Bidding Documents, including Addenda issued in accordance with Instructions to Bidders (ITB) 8. (b) We offer to execute in conformity with the Bidding Documents and the Technical Bid submitted for the following Works: Name of Work: Bid No. DM/MS/CPM-GZ/313: Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre at Sarai Kale Khan Namo Bharat Station. (c) The total price of our Bid, excluding any discounts offered in item (d) below is: [amount in INR in figures] 0.0 DISCOUNT (IN %age ) Discount methodology (d) The discounts offered and the methodology for their application indicated in BoQ2 sheet are:- 0.0 0.0 Discount Amount 0.0 (e) The total price of our Bid, including discounts offered in item (d) above is: [Amount in INR in figures] 0.0 [Amount in INR in words] INR Zero Only (f) (g) If our Bid is accepted, we commit to obtain a performance security in accordance with the Bidding Documents. (h) We understand that this bid, together with your written acceptance thereof included in your notification of award, shall constitute a binding contract between us, until a formal contract is prepared and executed. (i) We understand that you are not bound to accept the lowest evaluated bid or any other bid that you may receive. Name of the authorized representative of the bidder Desiganation of the authorized representative Name of the Bidder/ Bidding Firm / Company : 0.0 Date: (DD/MM/YYYY) Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre at Sarai Kale Khan Namo Bharat Station 1.0 SCHEDULE- A : Civil Structures DSR 2023 Items 1.0 S. No. DSR 2023 Item No. DESCRIPTION OF ITEMS UNIT QTY DSR RATE(Incl. GST) DSR 2023 Rate after multiplying correction factor of 0.973 (Excluding GST @ 18 %) (INR) AMOUNT (Excl.GST) In INR 1.03 Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col (8)=col (5)X col (7) Concrete Work Reinforced Cement Concrete |
| 18 | 5.9.2 |
| 19 | 5.9.3 |
| 20 | 5.9.5 |
| 21 | 5.9.6 |
| 22 | 5.9.7 |
| 23 | 5.11.1 |
| 24 | 5.22A |
| 25 | 5.22A.6 |
| 26 | 5.33.2 |
| 27 | 5.33.2.5 |
| 28 | 5.33.2.4 |
| 29 | Total (excluding GST ) 343800844.72 Add CPWD cost index (103 *101/(100*100) 13855174.04 TOTAL OF SCHEDULE (A) (Excl GST including CPWD index) 357656019.0 Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre at Sarai Kale Khan Namo Bharat Station 1.0 SCHEDULE- B : Civil Finishing DSR 2023 Items 1.0 S. No. DSR 2023 Item No. DESCRIPTION OF ITEMS UNIT QTY DSR RATE(Incl. GST) DSR 2023 Rate after multiplying correction factor of 0.973 (Excluding GST @ 18 %) (INR) AMOUNT (Excl.GST) In INR Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8= Col 5 X Col 7 Masonary Work 0.0 0.0 |
| 30 | 6.4.1 Cladding Work |
| 31 | 8.2 8.2.2 Granite stone slab colour black, Cherry/Ruby red. 0.0 0.0 |
| 32 | 8.2.2.2 |
| 33 | 8.3 8.3.2 Granite work metre 120.0 510.95 421.32 50558.4 |
| 34 | 8.5 8.11 Providing and fixing machine cut, mirror/ eggshell polished , Marble stone work for wall lining (veneer work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with white cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-Charge. 0.0 0.0 |
| 35 | 8.11.1 |
| 36 | 8.20.1 |
| 37 | 8.31 Wood Work 0.0 0.0 |
| 38 | 9.21.1 |
| 39 | 9.96.1 |
| 40 | 9.97.4 |
| 41 | 9.100.1 |
| 42 | 9.101.2 |
| 43 | 9.103 |
| 44 | 9.127.2 Steel Work 0.0 0.0 10.16 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. 0.0 0.0 |
| 45 | 10.16.1 10.25 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. 0.0 0.0 |
| 46 | 10.25.2 10.26 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. 0.0 0.0 |
| 47 | 10.26.1 |
| 48 | 10.28 Flooring Work 0.0 0.0 |
| 49 | 11.41A 11.41A.2 Glazed vitrified floor tiles polished finish of size 0.0 0.0 |
| 50 | 11.41A.2 .1 |
| 51 | 11.41A.3 |
| 52 | 11.41A.3.1 11.46 Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. 0.0 0.0 |
| 53 | 11.46.2 |
| 54 | 11.56.1 Roofing Work 0.0 0.0 12.31 Providing 10 mm thick plaster of Paris (gypsum anhydrous) ceiling up to a height of 5 m above floor level, over first class kail wood strips 25x6 mm with 10 mm gap in between and reinforced with rabbit wire mesh fixed to wooden frame (frame work to be paid separately): 0.0 0.0 |
| 55 | 12.31.1 |
| 56 | 12.31.2 |
| 57 | 12.32 |
| 58 | 12.33 12.45 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 0.0 0.0 |
| 59 | 12.45.1 |
| 60 | 12.55 Finishing work 0.0 0.0 13.41 Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : 0.0 0.0 |
| 61 | 13.41.1 13.52 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. |
| 62 | 13.52.1 13.62 Painting with synthetic enamel of approved brand and manufacture of required colour to give an even shade 0.0 0.0 |
| 63 | 13.62.1 |
| 64 | 13.8 13.82 Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. 0.0 0.0 |
| 65 | 13.82.2 13.85 Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content 0.0 0.0 |
| 66 | 13.85.3 Water Proofing Work 0.0 0.0 |
| 67 | 22.22 Structural Glazing 0.0 0.0 |
| 68 | 25.8 False Ceiling 0.0 0.0 |
| 69 | 26.22 |
| 70 | 26.22.1 Total (excluding GST) 34869791.72 Add CPWD cost index (103 *101/(100*100) 1405252.61 TOTAL OF SCHEDULE (B) (Excl GST including CPWD index) 36275044.0 Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre at Sarai Kale Khan Namo Bharat Station Schedule- C : NDSR Civil Items for Level 1 and 2 S.NO NDSR ITEMS DESCRIPTION OF ITEMS UNIT QTY RATE(Excl. GST) RATE (Excl. GST) after discount and escalation AMOUNT (Excl.GST) In INR Reference LOA Calculation Reference Reference Item No 2.5 |
| 71 | NDSR 1 |
| 72 | NDSR 2 |
| 73 | NDSR 3 |
| 74 | NDSR 4 |
| 75 | NDSR 5 |
| 76 | NDSR 6 |
| 77 | NDSR 7 NDSR 7 Carpet Flooring Supplying PP Carpet Tiles. Size of tile should be combination of 600x600mm carpet tiles & 180x1200mm plank as per approved make & designs including aluminium profile at the floor transition places, complete as per approval / direction of Engineer-inCharge sqm 1342.0 1440.68 1552.33 2083226.86 LOA no. NCRTC/ESTATE/DUHAI/2023/10 dt 01/04/2023 (CP 27 - 28) 'Escalation included as per WPI Index (CP 57 & 60) (BOQ rates = 1440.68), % Quoted above = 1.25% NDSR 12, CP 21 NDSR 8 Providing and Pasting Decorative wall paper of approved Quality,Shade,Design,Colour on walland/Other SurfaceComplete as per Direction Of Engineer-in Charge. sqm 200.0 863.6 930.53 186106.0 LOA no. NCRTC/ESTATE/DUHAI/2023/10 dt 01/04/2023 (CP 27 - 28) 'Escalation included as per WPI Index (CP 57 & 60) (BOQ rates = 863.6), % Quoted above = 1.25% NDSR 16, CP 21 NDSR 9 Providing and fixing vinyl sheet signage, as per direction of Engineer in charge. sqm 250.0 3710.5 2672.17 668042.5 LOA no. DM/MS/COR-OF/242 dt 09.08.2024 (CP 56).'Escalation included as per WPI Index (CP 57 & 59) (BOQ rates = 3710.5), % Quoted below = 30.85% Item - 161, CP34 30.85 69.15 0.0 0.0 |
| 78 | NDSR 10 |
| 79 | NDSR 11 |
| 80 | NDSR 12 |
| 81 | NDSR 13 |
| 82 | NDSR 14 |
| 83 | NDSR 15 |
| 84 | NDSR 16 |
| 85 | NDSR 17 |
| 86 | NDSR 18 |
| 87 | NDSR 19 |
| 88 | NDSR 20 |
| 89 | NDSR 21 |
| 90 | NDSR 22 |
| 91 | NDSR 23 |
| 92 | NDSR 24 |
| 93 | NDSR 25 |
| 94 | NDSR 26 |
| 95 | NDSR 27 |
| 96 | NDSR 28 |
| 97 | NDSR 29 |
| 98 | NDSR 30 |
| 99 | NDSR 31 |
| 100 | NDSR 32 |
| 101 | NDSR 33 |
| 102 | NDSR 34 |
| 103 | NDSR 35 |
| 104 | NDSR 36 |
| 105 | NDSR 37 |
| 106 | NDSR 38 |
| 107 | NDSR 39 |
| 108 | NDSR 40 |
| 109 | NDSR 41 |
| 110 | NDSR 42 |
| 111 | NDSR 43 |
| 112 | NDSR 44 |
| 113 | NDSR 45 |
| 114 | NDSR 46 |
| 115 | NDSR 47 |
| 116 | NDSR 48 |
| 117 | NDSR 49 |
| 118 | NDSR 50 |
| 119 | NDSR 51 |
| 120 | NDSR 52 |
| 121 | NDSR 53 |
| 122 | NDSR 54 Concrete of M55 grade with minimum cement content of 430 kg /cum cum 361.0 9093.94 9093.94 3282912.34 |
| 123 | P-11 L1 PVC P-11 L1 Discount GST rate@12% Pkg-5B discount CC contract discount GST rate@18% PVC, Pkg-5B CC Contractor Escalation factor 1.12698 0.885 1.12 0.9411 0.7349 1.18 1.05 1.0455904334828099 SCHEDULE-D Execution of Civil, Architectural finishing, MEP and other Miscellaneous works for Construction of Operation Control Centre E&M Works of Operation Control Centre (OCC) Area at Sarai Kale Khan S.No. Item Reference No. Description Unit Qty. Estimated Rate (INR) Including GST Awarded Rate (INR) Including GST Awarded Rate (INR) Excluding GST Awarded Rate (INR) with Escalation Excluding GST Amount (Rs.) Excl. GST Remarks E.00 General 1.0 The BOQ specified below include the latest relevent standards, specifications, drawing details and the contractor is required to go through them as referred in tender document while quoting the rates All the samples/ material intended to be used in the works shall be subject to approval before use as the Employer's representative may opt. 2.0 Sub-letting of work by the contractor shall only be permitted in accordance with Special Conditions of Contract. 3.0 The items indicating one quantity can also be operated and variation clause shall be applicable as stipulated in GCC / SCC. 4.0 Bus Bar Sizing calculations shall be submitted for approval of Employer or Employer's representative. 5.0 Contractor's shall quote reasonably rates against each item of BOQ (both in word and figure) 6.0 For approved list of makes, refer specifications. 7.0 The description as mentioned in BOQ, Specifications,Special Conditions, GCC, Drawing and the conditions mentioned therein whichever is stringent shall be applicable, acceptable and complied with. E.01 M V SWITCHGEAR |
| 124 | 1.0 Supply, installation, testing & commissioning of front operated front access cubical type indoor duty floor / wall / recess/ surface mounting, totally enclosed dust and vermin proof (minimum protection IP 54) panels with neoprene gaskets, fabricated from 2 mm thick Cold Rolled Close Annealed CRCA sheets with powder coated finish (minimum thickness 50 micron) suitable for 415 volts 3 phase 4 wire 50 Hz system to withstand symmetrical fault level of 50kA at 415 V including interconnections, bonding to earth etc. and flush doors conforming to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLS PVC wires. All panels shall be of Totally Type tested Assemblies (TTTA) confirming to IEC 61439 (TTTA with Form 4B, type-5) including Earth fault protection complete as per specifications. a) The Switchboards shall be provided with detachable gland plates minimum of 3mm thick for entry of cables from the top/bottom as required. b) All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position. c) The panel shall have tinned copper busbars with bar type feeder connections, spacers etc. and neutral busbar shall be of 100% capacity. d) Earthing all components, frame etc. to a common internal earth bar of copper/aluminium as per earth fault calculation. Approval from Engineer shall be obtained by the Contractor e) All accessories & supporting structures such as channels, ISMC base frame, mounting brackets, lifting lugs, panel heaters, ventilation arrangement etc as required. f) Each incomer and outgoing feeder shall be provided with suitably rated MCB controlled multiple LED lamps (Red, Yellow, Blue) for Phase indication and (Red, Green, Amber) for ON, OFF & Trip status with all required accessories suitable for 230 VAC operation as approved. g) Space provision @ 15% for future expansion and Spare Breakers @ 20-25% shall be provided. h) The makes of components and accessories shall, to the extent practically feasible, be same for panels and boards for uniformity, standardization and replace ability and shall be applicable to all panels/ boards under the scope of work i) Switchboard including interconnections, labelling, earthing, associated foundation/masonry work & erection etc. complete as required. j) All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics) suitable for isolation conforming to latest IEC60947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values. k) All 4P MCCB has inbuilt feature of earth fault protection, whereas all TP MCCB's shall have external CT for neutral overload protection and earth fault protection. All TP MCCB's shall have external neutral for neutral overload protection and earth fault sensing as specified in BOQ. l) MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles (higher shall be preferred) for capacity of 100-250 amps. m) All the Electrical Panels shall be equipped with required accessories for establishing BMS connectivity through open protocol i.e. Ethernet-IP at a single location in each panel's Marshalling Chamber and shall be able to remotely read or control the parameters through BMS. This provision to be ensured. n) MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for motor application duty, with minimum Electrical endurance of the order of 20000 operation cycles. o) Panel/board design shall be compact and components / accessories of compact sizes be used to economies the room space available. Employer reserve the right to seek compact items in place of larger ones p) All incomer ACB's shall be provided with minimum 2 NO + 2 NC auxiliary contacts and all MCCBs shall be provided with 2 NO + 2 NC auxiliary contacts, and there should be provision to add min. 6 Auxiliary contacts. q) The panels shall be fitted with Clean Agent based panel flooding system. Payment for fire tube system shall be made under separate item. Scheme of fire tube system shall be got approved by Engineer before proceeding with manufacturing and assembly. Contractor shall interface with OEM of Panel and fire tube and ensure that the provision for fitting of cylinder and tube shall be made in the Panel during manufacturing of Panel without compromising the Compliance of relevant IEC. r) All incomers of Main Panel and Sub Panels shall be provided with surge protection devices as per NBC 2016, in compliance with IEC 61643. s) Internal control wiring in the Starters shall be done with FRLS PVC insulated cables of adequate size. Internal wiring, contactors, relay contacts, push button contacts should be rated not less than 2.5 sq. mm. All MCCB shall have Ethernet-IP communication port for BMS/SCADA functioning & integration. Various panels/boards as given below: Schedule-C/R3: |
| 125 | 1.2 1.1.1 1.2 (b) Main LT Panel No. 1.0 2191913.0 1939843.01 1732002.69 1951932.0 1951932.0 Pkg-11-L-1/3302 0.115 252070.0 1939843.0 1732002.68 A INCOMER (Normal Supply) a) Incoming from B1 with 630 A, 415V, Ics=35 kA, 4P, Motorised MCCB complete with variable overcurrent and short circuit releases for Normal Supply b) Incoming from B2 with 630 A, 415V, Ics=35 kA, 4P, Motorised MCCB complete with variable overcurrent and short circuit releases bus for Normal Supply c) Contactor-relay based automatic changeover system complete. d) 2 set of Red/Green ON/OFF indicating lamps e) 2 set of three phase indicating lamps (red, yellow, blue) f) Amber healthy/ trip indicating lamps for above feeders. B INCOMING FROM DG PANEL 1 nos. 630 A, 415V, Ics= 35 kA, 4P, Motorised MCCBs complete with variable overcurrent and short circuit releases a) 1- set of Red/Green ON/OFF indicating lamps b) 1- set of three phase indicating lamps (red, yellow, blue) c) Amber healthy/ trip indicating lamps for above feeders C1 BUSBAR-1 a) Electrolytic high conductivity tinned copper three phase and neutral busbars rated at 630 A having a maximum current density of 1.2A as per sq mm suitable to withstand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same capacity. b) All incomers shall be interlocked electrically & mechanically with contactor based automatic changeover system so that only one Supply is switched on at a time and fail safe restoration. C2 BUSBAR-2 a) Electrolytic high conductivity tinned copper three phase and neutral busbars rated at 200 A having a maximum current density of 1.4A as per sq mm suitable to withstand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same capacity. D1 Metering (at Busbar-1) a) 230V, AC operated integral type Digital meter with RS-485 port for measuring Amps ,Voltage, Energy, kWH, kVRH, frequency, Maximum Demand & power factor etc with TOD facility conforming to specifications, latest IEC/ EMC and EMI standards/criterion, with necessary Circuit MCBs and suitable size summating CTs for metering of all incomers and outgoing feeders supporting SCADA/BMS connectivity D2 Metering (at Busbar-2) a) 230V, AC operated integral type Digital meter with RS-485 port for measuring Amps ,Voltage, Energy, kWH, kVRH, frequency, Maximum Demand & power factor etc with TOD facility conforming to specifications, latest IEC/ EMC and EMI standards/criterion, with necessary Circuit MCBs for metering of all outgoing feeders and supporting SCADA/BMS connectivity E1 OUTGOING UNITS (From Busbar-1) a) 3 2 no. 200A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases. b) 2 20 no. 63A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases. c) 24 10 nos. 40A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases with multifunction meter. E2 OUTGOING UNITS (From Busbar-2) a) 19 13nos. 40A, 415V, Ics=25 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases. E3 Total Addition-Deletion ( 2 no. 200A in place of 3 nos., 20 nos. of 63A in place of 2 nos. and 23 nos. of 40A in place of 43 nos TP MCCBs set 1.0 -65413.7 -61560.83 -54965.03 -57713.0 -57713.0 Pkg-5B/08834 E4 Main LT Panel (1.2(b)+ E3) No. 1.0 1894219.0 |
| 126 | Sch C1, E01-3.10 One A C distribution board (ACDB) unit with respective incoming TPN MCBs, and outgoing SP MCBs each having indications for incoming feeder status as per specifications and as under: INCOMER a) 1 no. 40A TPN MCB b) 1 set of (ON) indicating lamps for each. OUTGOINGS with feeder (ON) indication LED lamps a) 42 Nos of 6 A SP MCB arranged in three rows . |
| 127 | Sch D1, E01, 1.12 1.3.1 Supply & fixing of 200 Amp on load, four pole Automatic Transfer switch (ATS) as per relavent IEC standards with HRC fuses and indications as required, suitable for 415 V, 3 phase, 4 wire, supply with suitable MS enclosure for E&M UPS. No. 1.0 121953.14 114770.1 102473.3 107597.0 107597.0 Pkg-5B/08832 158.0 |
| 128 | 2.0 1.4.1 2.1 Supply and fixing of the following safety equipments in Aux. Sub.Station/MDB room as per detailed descriptions given below and as per relevant IE rules & code of standard practice Set 1.0 48436.85 45583.92 40699.93 42735.0 42735.0 Pkg-5B/08832 159.0 a) 1000 mm wide Insulating mat,confirming to IS 15652-2006 suitable to withstand 11 kV in front of all panels in ASS building & Pump room as required. b) Laminated standard shock treatment charts in English & Hindi in ASS, ESR, DG room and Pump room in each station. c) Danger plate as per approved Style & sample written in English & Hindi for MV installations as required as per IE rules, IES and IS 2551 (latest) - 8 nos. per station d) 2 nos. per station First Aid Box Complete as approved by St. John ambulance or Indian Red Cross. e) 4 nos. per station of 3-fire-buckets set each painted red with 'fire' written complete with sand filling, floor/wall mounting brackets/stand complete as per elevant IS and as required. f) One Tool kit per station comprising 1 set of flat spanner (Taparia / Jalan), 1 set of box spanner, 1 no. Hacksaw frame with 10 No. blades, 1 no. large, medium, small screw drivers, 1 no. insulated plier, 1 no nose plier, 1 no. hand crimping tool upto 16 sq.mm, 1 no. digital multimeter, 1 no. test lamp and 1 no. tester. Screw driver set for all types of screw heads also to be provided. |
| 129 | 1.5.1 1.14 Adjustment rates for addition/deletion of supply & fixing of following including making of suitable holes/space in the panel/DBs and making good all external finishes, terminations etc. complete as required. a) Multiple LED/neon type indications No. 1.0 1680.11 1581.15 1411.74 1482.0 1482.0 Pkg-5B/08833 159.0 b) Astronomic digital Timer No. 1.0 4276.93 4025.02 3593.77 3773.0 3773.0 Pkg-5B/08833 159.0 c) Ammeter/Voltmeter (3.5 digit display) No. 1.0 4538.7 4271.37 3813.72 4004.0 4004.0 Pkg-5B/08833 159.0 d) TP Contractor - 40/32 Amp. No. 1.0 4987.15 4693.41 4190.54 4400.0 4400.0 Pkg-5B/08833 159.0 e) Aux. Contact 1 NO + 1NC for MCB No. 1.0 1126.33 1059.99 946.42 994.0 994.0 Pkg-5B/08833 159.0 |
| 130 | 1.15B 1.7.1 c) 400A, 415V, Ics=35 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue) No. 1.0 63396.85 59662.78 53270.34 55934.0 55934.0 Pkg-5B/08834 160.0 1.7.2 e) 250A, 415V, Ics=35 kA, 4P, MCCB with variable over current and short circuit releases and 1-set of three phase indicating lamps (red, yellow, blue) No. 1.0 54644.83 51426.25 45916.29 48212.0 48212.0 Pkg-5B/08834 160.0 1.7.3 h) 250/200 A ,415V, Ics=35kA, TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps No. 1.0 49576.34 46656.29 41657.4 43740.0 43740.0 Pkg-5B/08834 160.0 1.7.4 I) 160 A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps No. 1.0 32614.61 30693.61 27405.01 28775.0 28775.0 Pkg-5B/08834 160.0 1.7.5 j) 125 A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps No. 1.0 32208.92 30311.81 27064.12 28417.0 28417.0 Pkg-5B/08834 160.0 1.7.6 k) 100/63 A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps No. 1.0 27639.98 26011.99 23224.99 24386.0 24386.0 Pkg-5B/08834 160.0 1.7.7 l) Less than 63A to 40A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps No. 1.0 25667.85 24156.01 21567.87 22646.0 22646.0 Pkg-5B/08834 160.0 1.7.8 m) Electrical Operating mechanism (Motorised mechanism) for all types of above MCCBs No. 1.0 24774.09 23314.9 20816.88 21858.0 21858.0 Pkg-5B/08834 160.0 1.7.9 n) 5-32A FP MCB 10 kA No. 1.0 4320.73 4066.24 3630.57 3812.0 3812.0 Pkg-5B/08835 161.0 1.7.10 o) 40-63A FP MCB 10 kA No. 1.0 5082.05 4782.72 4270.29 4484.0 4484.0 Pkg-5B/08835 161.0 1.7.11 p) 5-32A TP MCB 10 kA No. 1.0 4013.08 3776.71 3372.06 3541.0 3541.0 Pkg-5B/08835 161.0 1.7.12 q) 40-63A TP MCB 10 kA No. 1.0 4741.02 4461.77 3983.72 4183.0 4183.0 Pkg-5B/08835 161.0 1.7.13 r) 5-32A DP MCB 10 kA No. 1.0 2111.87 1987.48 1774.54 1863.0 1863.0 Pkg-5B/08835 161.0 1.7.14 s) 40-63A DP MCB 10 kA No. 1.0 2564.49 2413.44 2154.86 2263.0 2263.0 Pkg-5B/08835 161.0 1.7.15 t) 5-32A SP MCB 10 kA No. 1.0 971.98 914.73 816.72 858.0 858.0 Pkg-5B/08835 161.0 1.7.16 u) 40-63A SP MCB 10 kA No. 1.0 1289.02 1213.1 1083.13 1137.0 1137.0 Pkg-5B/08835 161.0 1.7.17 v) 16-32Amp DP RCCB, 30 mA No. 1.0 3745.05 3524.47 3146.85 3304.0 3304.0 Pkg-5B/08835 161.0 1.7.18 w) 40-63Amp DP RCCB, 30 mA No. 1.0 4398.95 4139.85 3696.29 3881.0 3881.0 Pkg-5B/08835 161.0 1.7.19 x) 16-32Amp DP RCCB, 100 mA No. 1.0 3776.34 3553.91 3173.13 3332.0 3332.0 Pkg-5B/08835 161.0 1.7.20 y) 40-63Amp DP RCCB, 100 mA No. 1.0 4433.37 4172.24 3725.21 3911.0 3911.0 Pkg-5B/08835 161.0 1.7.21 z) 16-32Amp DP RCCB, 300 mA No. 1.0 3776.34 3553.91 3173.13 3332.0 3332.0 Pkg-5B/08835 161.0 1.7.22 aa) 16-32Amp DP RCBO, 30 mA No. 1.0 4287.36 4034.83 3602.53 3783.0 3783.0 Pkg-5B/08835 161.0 1.7.23 ab) 40-63Amp DP RCBO, 30 mA No. 1.0 5312.53 4999.62 4463.95 4687.0 4687.0 Pkg-5B/08835 161.0 1.7.24 ac) 16-32Amp DP RCBO, 100 mA No. 1.0 4318.65 4064.28 3628.82 3810.0 3810.0 Pkg-5B/08835 161.0 1.7.25 ad) 40-63Amp DP RCBO, 100 mA No. 1.0 5344.86 5030.05 4491.12 4716.0 4716.0 Pkg-5B/08835 161.0 1.7.26 ae) 16-32Amp DP RCBO, 300 mA No. 1.0 4318.65 4064.28 3628.82 3810.0 3810.0 Pkg-5B/08835 161.0 |
| 131 | 1.24 1.10.1 a) 4 - 6 A No. 1.0 1805.26 1698.93 1516.9 1593.0 1593.0 Pkg-5B/08836 1.10.2 b) 6 - 12 A No. 1.0 1839.68 1731.32 1545.82 1623.0 1623.0 Pkg-5B/08836 1.10.3 c) 9 - 15 A No. 1.0 1839.68 1731.32 1545.82 1623.0 1623.0 Pkg-5B/08836 1.10.4 d) 30 - 40 A No. 1.0 2725.1 2564.59 2289.81 2404.0 2404.0 Pkg-5B/08836 1.10.5 e) 40 - 65 A No. 1.0 4612.75 4341.06 3875.95 4070.0 4070.0 Pkg-5B/08836 1.10.6 f) 63 - 100 A No. 1.0 4529.31 4262.53 3805.83 3996.0 3996.0 Pkg-5B/08836 |
| 132 | 1.28 Total Schedule-E-01 2809534.0 Sch-D1 E.02 DISTRIBUTION BOARDS |
| 133 | 1.0 a) MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for motor application duty, with minimum Electrical endurance of the order of 20000 operation cycles. b) RCCB /RCBO conforming to IS 12640 shall be provided with 30mA sensitivity and electrically connected rated current capacity MCB for short circuit and over load protection as required c) All incomer MCBs of boards /panels shall be provided with NO/NC contacts as specified in specifications and drawings d) All the contactors shall be provided with potential free contacts for remote monitoring and control. e) Various distribution boards as given below: |
| 134 | 1.2 One lighting distribution board (LDB) unit consist of 2 compartments with respective incoming TPN MCBs, DP MCB RCCBs/ELCBs, set of contactors and outgoing SP MCBs each having indications for incoming & outgoing feeder status e.g. LDB-2 is combination of LDB 2/N and LDB 2/U connected to incoming Supplies from Normal & UPS respectively as per specifications and as shown on Drawing and as under:(Operational Rooms-Concourse Level) A Normal INCOMER a) 1 no. 40A TPN MCB b) 1 set of (ON) indicating lamps for each OUTGOINGS with feeder (ON) indication LED lamps a) 24 nos. 10A/20A SP MCB arranged in three rows and each row controlled by one no. 32A DP MCB ELCB/RCCB with feeder ON indication lamps a) UPS INCOMER B 1 no. 25A DP MCB ELCB/RCCB 1 set of (ON) indicating lamps for each OUTGOINGS with feeder (ON) indication LED lamps a) 10 nos. 10A SP MCB b) 1 set of (ON) indicating lamps for each OUTGOINGS with feeder (ON) indication LED lamps a) 10 nos. 10A SP MCB |
| 135 | One lighting distribution board (LDB) unit consist of 2 compartments with respective incoming TPN MCBs set of contactors and outgoing SP MCBs each having indications for incoming & outgoing feeder status e.g. LDB-3 is combination of LDB 3/N and LDB 3/G connected to incoming Supplies from Normal & DG respectively including a set of time switches as per specifications and as shown on Drawing and as under:(External Lighting & ancillary Building- Road Level) A Normal INCOMER a) 1 no. 40A TPN Contactor with astronomic digital timer b) 1 no. 40A TPN MCB c) 1 set of (ON) indicating lamps for each OUTGOINGS with feeder (ON) indication LED lamps a) 18 nos. 10A/20A SP MCB arranged in three rows and each row controlled by one no. 32A DP MCB ELCB/RCCB with feeder ON indication lamps b) 3 nos. 32A DP MCB ELCB/RCCB with feeder ON indication lamps tapped from above contactor (non timer-controlled feeders) B DG INCOMER a) 1 no. 40A TPN Contactor with astronomic digital timer b) 1 no. 40A TPN MCB c) 1 set of (ON) indicating lamps for each OUTGOINGS with feeder (ON) indication LED lamps a) 9 nos. 10A SP MCB arranged in three rows and each row controlled by one no. 32A DP MCB ELCB/RCCB with feeder ON indication lamps b) 3 nos. 32A DP MCB ELCB/RCCB with feeder ON indication lamps tapped from above contactor (non timer-controlled feeders) |
| 136 | NDSR 6 Supply, installation, testing and commissioning of Main LT panel / Main distribution panels / sub-distribution panels fabricated out of 3mm thick for structural members and 2mm thick for door and covers CRCA sheet steel in cubicle compartmentalised free standing floor mounted, dust and vermin proof, fully bolted type (modular design) for indoor and welded type for outdoor, with reinforcement of suitable size angle iron, channel T irons and/or flats wherever necessary. Panels shall be treated with all anticorrosive process before painting with 14 stage pretreatment process and final approved shade of enamelled paint. 2Nos. earthing terminals shall be provided for all distribution panels. All covers and doors to be provided with foam sealing PU gasket with no cut and joints. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system and with 20% spare space, lifting hooks shall also be provided in case of large panels. All panels shall comply to IEC 61439 and Shall be FORM 4A, Type-3 . Approval shall be taken for each panel before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. The panels to confirm IP-42 for indoor & IP-54 for outdoor. Calculation of Bus-bar to be submitted with the drawings of panels for approval. All CPRI test report to be submitted. All internal wiring in the panels shall be carried out using high temperature FRLS wires. All Switchboards shall be provided with detachable gland plates for ease entry of cables from the top/bottom as required and specified. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves/as per manufacturer's type tested proven design. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position. All panels shall have hot Spares @ 25% and shall have provision of space @ 20% for future expansion etc. All panels shall have aluminium busbars of 100% current ratings. Earthing all components, frame etc. to a common internal earth bar of minimum size 50 x 6 mm aluminium bar of suitable size All accessories & supporting structures such as channels, ISMC base frame, mounting brackets, lifting lugs, panel heaters, ventilation arrangement etc as required. Each incomer and outgoing feeder shall be provided with multiple LED status indication lamps suitable for 230 V, AC.. The makes of components and accessories shall, to the extent practically feasible, be same for panels and boards for uniformity, standardisation and replaceability and shall be applicable to all panels/ boards under the scope of work Switchboard including interconnections, labelling, earthing, associated foundation/masonary work & erection etc. complete as required. All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics) suitable for isolation conforming to latest IEC947- 2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle, indicating On/Off/Trip position. The breaking capacity as mentioned shall be Ics values. All 4P MCCB has inbuilt feature of earth fault protection, whereas all TP MCCB's shall have external CT for neutral overload protection and earth fault protection All incoming and outgoing MCCBs shall have minimum ON/OFF/Trip indication (Red, Green, Amber) with suitable rating MCB,similarly all incoming and outgoings of main LT panel and Main emergency panel, ESR / Pump Room panels shall have potential free contacts for connectivity to PLC for ON/OFF/TRIP status and control, as required, from BMS workstation through BUSNET/MODBUS protocol Panel/board design shall be compact and components / accessories of compact sizes be used to economies the room space available. Employer reserve the right to seek compact items inplace of larger ones All incomer ACB's shall be provided wih NO+NC auxiliary contacts as per specifications and all MCCBs shall be provided with 2 NO + 2 NC auxiliary contacts and there should be provision to add min. 6 Auxilary contacts. All 4-pole ACBs shall have fully rated neutral pole The panels shall have a provision to fit an independent clean agent/gas flooding system using linear heat sensing tubes, for the fire suppression of the panel, cost of the same shall be paid under a seprate head, however the scheme and calculation of the same shall be approved by the Engineer before proceeding with manufacturing and assembly. Also note that the design doesn't affect on IP rating of the panel. 2.3.1 6.5 Starter Panel suitable for 7.5 to 11KW ventilation/pressurisation fans SET 1.0 20662.77 15185.07 15185.07 15877.36 15877.36 Pkg-M/s CC- Club House,page-89 0.2651 5477.7 15185.07 63 A TPN MCB with suitable rating Star Delta starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. 2.3.2 6.6 Starter Panel suitable for 7.5 KW ventilation/pressurisation fans SET 1.0 17581.57 12920.7 12920.7 13509.76 13509.76 Pkg-254, page-000078 40 A TPN MCB with suitable rating Star Delta starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. 2.3.4 6.7 Starter Panel suitable for 5.6 KW ventilation/pressurisation fans SET 1.0 13407.21 9852.96 9852.96 10302.16 10302.16 Pkg-254, page-000078 32 A TPN MCB with suitable rating Star Delta starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. 2.3.5 6.8 Starter Panel suitable for 2.2 KW ventilation/pressurisation fans SET 1.0 13076.04 9609.58 9609.58 10047.68 10047.68 Pkg-254, page-000079 20 A TPN MCB with 16 A DOL starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. Set - 01 NOTE: The contractor shall provide suitable contacts wherever necessary along with auto / manual mode selector switch for Ventilation & Pressurization fan etc. to take fire input signal (Potential Free Contact) 250740.48 Sch-D1 E.03 MV CABLING |
| 137 | 1.1 Note 1: All cables 16 sq mm and above are Al Conductor unless specified otherwise. 3.1.1 a) 3.5 core 300 sq mm Al Conductor M 375.0 1231.09 1158.58 1034.45 1086.0 407250.0 Pkg-5B/08845 171.0 3.1.2 b) 3.5 core 240 sq mm Al Conductor M 225.0 1013.3 953.62 851.45 894.0 201150.0 Pkg-5B/08845 3.1.3 c) 3.5 core 185 sq mm Al Conductor M 125.0 810.84 763.08 681.32 715.0 89375.0 Pkg-5B/08845 3.1.4 d) 3.5 core 150 sq mm Al Conductor M 10.0 670.76 631.25 563.62 592.0 5920.0 Pkg-5B/08845 3.1.5 e) 3.5 core 120 sq mm Al Conductor M 50.0 578.74 544.65 486.29 511.0 25550.0 Pkg-5B/08845 3.1.6 f) 3.5 core 95 sq mm Al Conductor M 20.0 465.24 437.84 390.93 410.0 8200.0 Pkg-5B/08846 172.0 3.1.7 g) 4 core 95 sq mm Al Conductor M 10.0 527.71 496.63 443.42 466.0 4660.0 Pkg-5B/08846 3.1.8 h) 3.5 core 70 sq mm Al Conductor M 300.0 380.37 357.97 319.62 336.0 100800.0 Pkg-5B/08846 3.1.9 I) 3.5 core 50 sq mm Al Conductor M 10.0 302.66 284.83 254.31 267.0 2670.0 Pkg-5B/08846 3.1.10 j) 3.5 core 35 sq mm Al Conductor M 155.0 247.17 232.61 207.69 218.0 33790.0 Pkg-5B/08846 3.1.11 k) 3.5 core 25 sq mm Al Conductor M 200.0 215.88 203.16 181.39 190.0 38000.0 Pkg-5B/08846 3.1.12 l) 4 core 25 sq mm Al Conductor M 515.0 225.97 212.66 189.88 199.0 102485.0 Pkg-5B/08846 3.1.13 m) 4 core 16 sq mm Al Conductor M 500.0 172.8 162.62 145.2 152.0 76000.0 Pkg-5B/08846 3.1.14 n) 3 core 16 sq mm Al Conductor M 100.0 155.39 146.24 130.57 137.0 13700.0 Pkg-5B/08846 3.1.15 o) 2 core, 16 sq mm Al Conductor M 10.0 135.58 127.59 113.92 120.0 1200.0 Pkg-5B/08846 3.1.16 p) 4 core 10 sq mm Cu Conductor M 10.0 404.91 381.06 340.23 357.0 3570.0 Pkg-5B/08846 3.1.17 q) 4 core 6 sq mm Cu Conductor M 10.0 296.18 278.73 248.87 261.0 2610.0 Pkg-5B/08846 3.1.18 r) 4 core 4 sq mm Cu Conductor M 10.0 221.88 208.81 186.44 196.0 1960.0 Pkg-5B/08846 3.1.19 s) 3 core 10 sq mm Cu Conductor M 10.0 350.41 329.77 294.44 309.0 3090.0 Pkg-5B/08846 3.1.20 t) 3 core 6 sq mm Cu Conductor M 10.0 244.04 229.67 205.06 215.0 2150.0 Pkg-5B/08846 3.1.21 u) 3 core 4 sq mm Cu Conductor M 390.0 187.72 176.66 157.73 166.0 64740.0 Pkg-5B/08846 3.1.22 v) 2 core 50 sq mm Cu Conductor M 10.0 849.96 799.9 714.2 750.0 7500.0 Pkg-5B/08846 3.1.23 w) 3 core 2.5 sq mm Cu Conductor M 145.0 140.79 132.5 118.3 124.0 17980.0 Pkg-5B/08846 |
| 138 | 1.1 A 3.2.1 a) 3.5 core 300 sq mm Al Conductor No. 8.0 3049.1 2869.51 2562.06 2690.0 21520.0 Pkg-5B/08846 172.0 3.2.2 b) 3.5 core 240 sq mm Al Conductor No. 8.0 2655.43 2499.03 2231.28 2343.0 18744.0 Pkg-5B/08847 173.0 3.2.3 c) 3.5 core 185 sq mm Al Conductor No. 4.0 1874.24 1763.85 1574.87 1654.0 6616.0 Pkg-5B/08847 173.0 3.2.4 d) 3.5 core 150 sq mm Al Conductor No. 2.0 1734.16 1632.02 1457.16 1530.0 3060.0 Pkg-5B/08847 173.0 3.2.5 e) 3.5 core 120 sq mm Al Conductor No. 24.0 1643.16 1546.38 1380.7 1450.0 34800.0 Pkg-5B/08847 173.0 3.2.6 f) 3.5 core 95 sq mm Al Conductor No. 2.0 1434.57 1350.07 1205.42 1266.0 2532.0 Pkg-5B/08847 173.0 3.2.7 g) 4 core 95 sq mm Al Conductor No. 2.0 1469.45 1382.9 1234.73 1296.0 2592.0 Pkg-5B/08847 173.0 3.2.8 h) 3.5 core 70 sq mm Al Conductor No. 4.0 1149.29 1081.6 965.71 1014.0 4056.0 Pkg-5B/08847 173.0 3.2.9 I) 3.5 core 50 sq mm Al Conductor No. 8.0 1024.55 964.2 860.89 904.0 7232.0 Pkg-5B/08847 173.0 3.2.10 j) 3.5 core 35 sq mm Al Conductor No. 4.0 730.03 687.03 613.42 644.0 2576.0 Pkg-5B/08847 173.0 3.2.11 k) 3.5 core 25 sq mm Al Conductor No. 4.0 650.77 612.44 546.82 574.0 2296.0 Pkg-5B/08847 173.0 3.2.12 l) 4 core 25 sq mm Al Conductor No. 16.0 640.09 602.39 537.85 565.0 9040.0 Pkg-5B/08847 173.0 3.2.13 m) 4 core 16 sq mm Al Conductor No. 52.0 563.4 530.22 473.41 497.0 25844.0 Pkg-5B/08847 173.0 3.2.14 n) 3 core 16 sq mm Al Conductor No. 8.0 475.56 447.55 399.6 420.0 3360.0 Pkg-5B/08847 173.0 3.2.15 o) 2 core, 16 sq mm Al Conductor No. 2.0 473.48 445.59 397.85 418.0 836.0 Pkg-5B/08847 173.0 3.2.16 p) 4 core 10 sq mm Cu Conductor No. 2.0 492.85 463.82 414.13 435.0 870.0 Pkg-5B/08847 173.0 3.2.17 q) 4 core 6 sq mm Cu Conductor No. 2.0 464.22 436.88 390.07 410.0 820.0 Pkg-5B/08847 173.0 3.2.18 r) 4 core 4 sq mm Cu Conductor No. 2.0 461.15 433.99 387.49 407.0 814.0 Pkg-5B/08847 173.0 3.2.19 s) 3 core 10 sq mm Cu Conductor No. 2.0 470.35 442.65 395.22 415.0 830.0 Pkg-5B/08847 173.0 3.2.20 t) 3 core 6 sq mm Cu Conductor No. 2.0 457.06 430.14 384.05 403.0 806.0 Pkg-5B/08847 173.0 3.2.21 u) 3 core 4 sq mm Cu Conductor No. 20.0 385.87 363.14 324.23 340.0 6800.0 Pkg-5B/08847 173.0 3.2.22 v) 2 core 50 sq mm Cu Conductor No. 2.0 841.62 792.05 707.19 743.0 1486.0 Pkg-5B/08847 173.0 3.2.23 w) 3 core 2.5 sq mm Cu Conductor No. 4.0 355.83 334.87 298.99 314.0 1256.0 Pkg-5B/08847 173.0 |
| 139 | 2.0 3.3.1 2.1 Supply, fabrication & installation of perforated hot dipped galvanised (Galvanisation as per latest IS 4759/6745) reverse flange double bended cable trays from 2 mm thick GI sheets continuously connected including horizontal and vertical bends, reducers, tees, and other accessories and duly suspended from the ceiling with 12 mm dia vertical GI rods supported by 40mm x 40 mm x 5 mm GI angle etc. (or installed on wall supported on suitable brackets as required) complete as per specifications, as required and as below. Note: Trays shall be supported adequately at minimum 1 m distance from the building structure / ceiling by means of painted / galvanized (as specified) MS structural members secured to the structure by dash fasteners or by grouting. This support should be capable of withstanding the weight equivalent of 3m length of the cables that can be laid in the trays. At turns the support has to be double and at both ends of the bend. 3.3.1.1 a) 600 mm wide x 40 mm deep M 200.0 1546.02 1454.96 1299.07 1364.0 272800.0 Pkg-5B/08848 174.0 3.3.1.2 b) 450 mm wide x 40 mm deep M 250.0 1250.44 1176.79 1050.71 1103.0 275750.0 Pkg-5B/08848 3.3.1.3 c) 300 mm wide x 40 mm deep M 300.0 924.34 869.9 776.7 816.0 244800.0 Pkg-5B/08848 3.3.1.4 d) 150 mm wide x 40mm deep M 1200.0 623.73 586.99 524.1 550.0 660000.0 Pkg-5B/08848 3.3.1.5 e) 100 mm wide x 40mm deep M 200.0 455.82 428.97 383.01 402.0 80400.0 Pkg-5B/08848 3.3.1.6 f) 50 mm wide x 40mm deep M 200.0 345.96 325.58 290.7 305.0 61000.0 Pkg-5B/08848 |
| 140 | 2.2 Supply, fabrication & installation of GI cable ladders continuously connected with suitable size runners horizontal and vertical bends reducers, tees, cross members, coupling plate, nut bolts washers etc and suspenders and other accessories and duly suspended from the ceiling with GI suspenders etc. complete as per specifications, as required. (Note: where required this item shall also be used making cable cum luminaries fixing tray and for fixing bus trunking to the surface along with associated fixtures, fasteners and other fixing members as approved by employers representative in advance for this purpose.) The side runners shall be 100 x 20 x 2.5 mm and centre rungs shall be of size 30 x 15 x 2.5 mm with centre to centre distance of 250 mm, as required. Note : GI suspenders and necessary anchor fasteners or any other fabricated G.I. item of any size as approved is included in this item and shall not be paid separately 3.4.1 a) 600 mm wide M 50.0 1120.21 1054.23 941.28 988.0 49400.0 Pkg-5B/08848 174.0 3.4.2 b) 450 mm wide M 50.0 1027.93 967.38 863.73 907.0 45350.0 Pkg-5B/08848 3.4.3 c) 300 mm wide M 50.0 935.65 880.54 786.2 826.0 41300.0 Pkg-5B/08848 |
| 141 | 2.3 3.5.1 2.3.1 200 mm wide & 50 mm deep M 200.0 993.87 935.33 835.12 877.0 175400.0 Pkg-5B/08849 175.0 3.5.2 2.3.2 100 mm wide & 50 mm deep M 100.0 714.39 672.31 600.28 630.0 63000.0 Pkg-5B/08849 3342336.0 E.04 CONDUIT WIRING |
| 142 | 1.0 4.0.1 a) First point controlled by one 6A Switch/ 10A MCB No. 35.0 5979.99 5627.77 5024.79 5276.0 184660.0 Pkg-5B/08849 175.0 |
| 143 | 1.2 4.2.1 a) One point controlled by 10A MCB. No. 40.0 3414.45 3213.34 2869.05 3013.0 120520.0 Pkg-5B/08850 176.0 |
| 144 | 1.3 0.0 Pkg-5B/08850 |
| 145 | 1.4 4.4.1 a) One no. 16A socket outlet point controlled by one 16A switch. No. 20.0 10385.2 9773.51 8726.35 9163.0 183260.0 Pkg-5B/08850 176.0 |
| 146 | 1.5 NOTE :- With regard to Item reference Nos. 1.1 to 1.5, for further clarifications, the sample measurement system to be followed is given below :- a) In case of 10 nos. light fixtures looped together and controlled directly from one no. MCB in DB, quantity to be paid shall be 1 No. as per Item No. 1.1 or 1.3 as applicable and quantity to be paid shall be 9 Nos. as per item no. 1.2 or 1.4 as applicable. b) In case of 5 nos. light fixtures looped together and controlled from switch located in a room, quantity to be paid shall be 1 no. as per Item No. 1.1 and quantity to be paid shall be 4 Nos. as per item no. 1.2. Conduit & wire laid from MCB in DB to first light point via switch point shall not be paid separately and is included in the rate in item no. 1.1. Same shall be the case for item nos. 1.5 as applicable. |
| 147 | 2.0 4.6.1 2.1 1 no. 6A modular switch Each 50.0 156.44 147.23 131.46 138.0 6900.0 Pkg-5B/08850 176.0 4.6.2 2.2 1 no. 6A switch & 1 no. 6A socket Each 100.0 313.91 295.42 263.77 277.0 27700.0 Pkg-5B/08850 4.6.3 2.3 1 no. 6A socket Each 100.0 285.75 268.92 240.11 252.0 25200.0 Pkg-5B/08850 4.6.4 2.4 6/16 Amp Universal socket with 16 amp modular switch Each 100.0 382.42 359.9 321.34 337.0 33700.0 Pkg-5B/08850 4.6.5 2.5 Blanking Plate for Switch/Socket Each 50.0 29.22 27.5 24.55 26.0 1300.0 Pkg-5B/08850 4.6.6 2.6 32A 3 pin industrial socket outlet with 32 A DP RCCB 30mA with MCB shall be of standard powder coated MS steel IP-55 enclosure, separately lockable. Each 2.0 8321.3 7831.18 6992.13 7342.0 14684.0 Pkg-5B/08850 4.6.7 2.7 Supplying installation testing and commissioning of Industrial Socket with 10/25/32A DP MCB in IP 54 rated surface/recessed box with the total unit having IP 54 ingress protection with incoming & outgoing cable box for AC indoor unit complete as required. No. 18.0 2893.0 2722.6 2430.89 2552.0 45936.0 Pkg-5B/08851 177.0 4.6.8 2.8 Supplying installation testing and commissioning of 63A TP Isolator with powder coated MS box in IP 55 rated surface/recessed box with the total unit having IP 55 ingress protection with incoming & outgoing cable box for AC outdoor unit complete as required. No. 3.0 12087.21 11375.27 10156.49 10664.0 31992.0 Pkg-5B/08851 4.6.9 2.9 Supply installation testing and commissioning of Occupancy sensor based movement detector with a build-in switch suitable for recessed mounting at a height of 3m with detection pattern of 6m X 8m. The sensor should have an operating voltage range of 230VAC +/10%; 50/60Hz and should be able to take upto 6A of electrical load and should be able to provide the switch off delay from 1 minute to 30 minutes range. The sensor should be in compliance with EN/IEC 60669-2-1, IEC (EN) 60669-2-1, IEC (EN) 61547, IEC (EN) 55015 and IEC (EN) 55022, class B. No. 2.0 4052.15 3813.48 3404.89 3575.0 7150.0 Pkg-5B/08851 4.6.10 2.1 Supply installation testing and commissioning of Occupancy based movement detector with a build-in switch suitable for surface mounting at a height of 3m with detection pattern of 6m X 8m. The sensor should have an operating voltage range of 230VAC +/10%; 50/60Hz and should be able to take upto 6A of electrical load and should be able to provide the switch off delay from 1 minute to 30 minutes range. The sensor should be in compliance with IEC 61547, IEC 61347-2-13, IEC (EN) 55015, Class B. No. 1.0 4052.15 3813.48 3404.89 3575.0 3575.0 Pkg-5B/08851 4.6.11 2.11 Supplying installation testing and commissioning of 6A DP MCB with powder coated MS box in IP 55 rated surface/recessed box with the total unit having IP 55 ingress protection with incoming & outgoing cable box for AC indoor unit complete as required.(From AC DB to AC indoor unit) No. 18.0 5461.16 5139.5 4588.84 4818.0 86724.0 Pkg-5B/08851 |
| 148 | 3.0 4.7.1 3.1 25 mm dia 1.6mm thick M 250.0 144.17 135.68 121.14 127.0 31750.0 Pkg-5B/08851 4.7.2 3.2 32 mm dia 1.6mm thick M 50.0 210.64 198.23 176.99 186.0 9300.0 Pkg-5B/08851 4.7.3 3.3 50 mm dia 2.0mm thick M 10.0 376.28 354.12 316.18 332.0 3320.0 Pkg-5B/08851 |
| 149 | 6.0 1117751.0 E.05 INDOOR LIGHTING AND FANS |
| 150 | 1.0 A Luminaire minimum specifications and requirements a) Luminaires should operate at +/- 6% voltage fluctuation for continuous use to comply to IEC. PF >0.90 for the electronic drivers b) All the components including the internal wiring of the luminaries to be used shall be manufactured of material, which are of FR type. All luminaires shall be manufactured to relevant sections of IEC60598 or other approved international standards and the type tests for all luminaries shall be provided. c) All internal wiring within the lighting fixtures shall be heat-resisting cables. B Electronic driver for LEDs luminaires a) All equipment shall confirm with the objective of the European Directives on EMC (89/336/EEC) and where appropriate shall be fixed with CE mark b) The radio frequency interference (RFI) levels generated by the electronic driver shall be in accordance with the requirements of standard CISPR15 or other international standards as stated in specifications. c) It shall comply with following : Electromagnetic Compatibility Emission IEC 60555 & EN55015 & IEC 61000 d) Driver for LED luminaires : power factor shall be according to manufacturers recommendation and type of luminaire. Input volt shall be 240V, 50Hz. Voltage tolerance: 140 - 270V With Tolerance Of Performance: +6% to 8% --- 202 to 254 V With Tolerance Of Safety: +/-10% --- 198 to 264 V e) All driver shall be capable of starting luminaires at ambient temperature of 0 °C and above. f) Driver shall be electronic driver type , operating lamps t a frequency of 20kHz or higher with no detectable flicker. g) Light output regulation: driver shall maintain constant light output of all LED Luminaries over operating ranges of 120Volts to 270 Volts. Luminous flux should not change more than +/-2%. h) Relative Light Output: (percentage of light emitted compared with LED chips and Luminaire) shall not be less than 95% and more than 100%. I) Input total harmonic content shall not exceed 10%. Driver shall withstand line transients as per IEC 61547. Driver case temperature shall not exceed 25 35 degree rise over 43 degree ambient. Driver power factor shall be 0.90 or above. j) The following general luminaire parameters shall be applicable unless otherwise specified in specific design data; Compliances and approvals RFI <30MHz --- CISPR15 RFI > 30MHz --- CISPR15 Harmonics --- EN 61000-3-2 Immunity --- EN 61547 Safety --- IEC 61347-2-13 Performance --- IEC 62384 Vibration & bump test --- IEC 60598 Quality standard --- ISO 9001 Environment standard --- ISO 14001 Approvals marks --- Safety marks a) LEDs Colour Rendering Index Ra> 70 for Outdoor and CRI>80 for Indoor Colour Temperature: 6500K/5700K/4000K Life: In excess of 50,000 hours Surge - 2.5kV for Indoor Luminaires /4kV for Outdoor Luminaires Note: All Light Fixtures and its drive should have free replacement for one year from date of Taking Over. All necessary arrangement at site for replacement shall be done by Contractor 5.0.1 1.1 SITC of surface/suspended mounted Trunking system including it's luminaire. The trunk shall be minimum 1134MM with compatible luminaire having maximum system wattage of 35W & Minimum system luminious efficacy of 110 lumens per watt. The housing & the trunk shall be made of Extruded Aluminium & the luminaire shall be IP54 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. The luminaire shall be BIS registered. Similar to philips Optimus or superior as per approved list. The CCT shall be 6500K. Similar to Philips:LL199X 1XDLED40-6500 PSE OD WH -IP54 (for Platform edge) No. 0.0 6621.8 6231.78 5564.09 5842.0 0.0 Pkg-5B/08854 5.0.2 1.2 SITC of surface mounted 4feet Integrated LED batten having maximum system wattage of 35W & Minimum system luminious efficacy of 120 lumens per watt. The housing shall be made of Extruded Aluminium & the luminaire shall be IP65 & IK08 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.90@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV & operating temperature -10 Degrees to 50 Degrees. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. Similar to Philips catalogue no.WT 201C LED 44S-6500 PSU L120 S2 or equivalant. It must conform to Ingress Protection Classification of IP 65 (for Staircase & Corridor/Platform edge) No. 0.0 4883.76 4596.11 4103.67 4309.0 0.0 Pkg-5B/08854 5.0.3 1.3 SITC of surface mounted 4feet Integrated LED batten having maximum system wattage of 18W & Minimum system luminious efficacy of 120 lumens per watt. The housing shall be made of Extruded Aluminium & the luminaire shall be IP65 & IK08 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.90@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV & operating temperature -10 Degrees to 50 Degrees. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. Similar to Philips catalogue no.WT 201C LED 24S-6500 PSU L 120 S2 or equivalant. It must conform to Ingress Protection Classification of IP 65 (for Staircase & Corridor) No. 0.0 3662.82 3447.08 3077.75 3232.0 0.0 Pkg-5B/08854 5.0.4 1.4 SITC of surface mounted 4feet Integrated LED batten having maximum system wattage of 35W & Minimum system luminious efficacy of 100 lumens per watt. The housing shall be made of Extruded Aluminium & the luminaire shall be IP20 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.90@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 2.5KV. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. Similar to philips BN100C LED40S-6500 PSU L120 GR S3 FRLS PXXXX or superior as per approved list No. 0.0 2118.69 1993.9 1780.27 1869.0 0.0 Pkg-5B/08854 5.0.5 1.5 Supply, Installation,Testing & Commissioning of 32W LED Surface mounted Luminaire having dimensions of 1220X150X43mm with 6500K color temperature and 50000 burning hours life with minimum 70% lumen maintenance, CRI should be greater than 80, system lumen output should be minimum 3400 lumens and efficacy of >106 lm/W. Housing should made of Extruded Aluminum with PMMA diffuser. Electronic Driver should have power factor >0.9 with THD No. 0.0 10377.99 9766.73 8720.29 9156.0 0.0 Pkg-5B/08854 5.0.6 1.6 SITC of recessed mounted LED 2X2 luminaire having maximum system wattage of 30W & Minimum system luminious efficacy of 120 lumens per watt. The housing shall be made of CRCA Powder Coated & the luminaire shall be IP20 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. The luminaire shall have class B Serviceability. Similar to Philips RC380B LED36S-6500 G5 L60W60 PSU OD FRLS PXXXX or superior as per approved list.(for false ceiling equipment room) No. 0.0 5645.05 5312.56 4743.36 4981.0 0.0 Pkg-5B/08854 5.0.7 1.7 SITC of recessed mounted LED 1200mm luminaire having maximum system wattage of 30W & Minimum system luminious efficacy of 120 lumens per watt. The housing shall be made of CRCA Powder Coated & the luminaire shall be IP20 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 2.5KV. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. The luminaire shall have class B Serviceability. Similar to PHILIPS CAT no: RC380B LED36S6500 G5 L3W12 PSU OD or equivalent (for false ceiling corridors and for public area) No. 0.0 7167.64 6745.47 6022.74 6324.0 0.0 Pkg-5B/08855 5.0.8 1.8 Supply, Installation, Testing & commissioning of 10W LED Bulkhead with a lumen package of 600 lumens in cool White color. The fixture should be THD ≤ 20% and PF ˃ 0.90, IP 66 and IK 09. Fixture should be a housing of High Pressure Die Cast aluminium and a front diffuser of polycarbonate. Similar to philips Endura LED WT202W LED6S CW PSU S3 PC FRLS PXXXX or superior as per approved list.(For Shaft, Parapet wall) No. 0.0 1884.56 1773.56 1583.54 1663.0 0.0 Pkg-5B/08855 5.0.9 1.9 SITC of Recess mounted LED downlight having maximum system wattage of 11W & Minimum system luminious efficacy of 110 lumens per watt. The housing shall be made of Pressure Die Cast Aluminium & the luminaire shall be IP20 compliant. The luminaire shall have diffuser made of polystyrene / PMMA/Polycarbonate. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 2.5KV. The luminiare shall use high power LEDs with CR≥80, SDCM≤5, CCT6500°K ± 300 °K. Similar to philips DN296B LED12S-6500 PSU WH FRLS PXXXX or superior as per approved list(For False ceiling Toilet) No. 0.0 2473.48 2327.79 2078.38 2182.0 0.0 Pkg-5B/08855 5.0.10 1.1 Supply, installation, testing and commissioning of surface mounted downlighter with system wattage of 18W LED and system lumen output of 2000 lumens . The luminaire shall have a CRI greater than 80 with rated system lifetime of 50,000 hours at L70. (Similar to Philips catalogue No.SM251C LED20S- 6500 PSU WHor equivalent as approved make) and must conform to Ingress Protection Classification of IP 20.For Toilets and corridors Non false ceiling areas ) No. 0.0 3648.46 3433.57 3065.69 3219.0 0.0 Pkg-5B/08855 5.0.11 1.11 Supply, installation, testing and commissioning of surface mounted LED flood light with a system lumen output of 3500 lumens. The luminaire shall have a aluminium pressure die-cast housing and a minimum system efficacy of 100 lumen/watt. The luminaire shall have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70.Similar to Philips catalogue no BVP120 LED 35 CW NB FG S3XT and must confirm to Ingress Protection Classification of IP 65.(For Platform staircase, Street lighting) No. 0.0 14072.41 13243.55 11824.6 12416.0 0.0 Pkg-5B/08855 5.0.12 1.12 SITC of LED Flood light having maximum system wattage of 100W & Minimum system luminious efficacy of 120 lumens per watt. The housing shall be made of pressure diecast aluminium & the luminaire shall be IP65. The luminaire shall employ a BIS registered driver with THD ≤10% @ full load, PF≥0.95. The driver shall be constant current & potted type with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV, The driver efficiency should be ≥ 85% at full load. The luminiare shall use high power LEDs with CR≥70, SDCM≤5, CCT5700°K ± 300 °K. Similar to Philips catalogue no.BVP192 LED110 CW HO NB FG GR PSU (For Platform staircase, Street lighting) No. 0.0 18763.69 17658.51 15766.53 16555.0 0.0 Pkg-5B/08855 5.0.13 1.13 25W High power LED Decorative Post Top with >2700 lm output having integral driver with closed diffuser optics protected to IP 65. Specified as philips Smart LED Post Top BGP300 LED28 757 PSU PC IN S1 FRLS PXXXX or equivalent.(Corridor, FOB) No. 0.0 21201.26 19952.51 17814.74 18705.0 0.0 Pkg-5B/08855 5.0.14 1.14 SITC of LED Highbay luminaire having maximum system wattage of 80W & Minimum system luminious efficacy of 125 lumens per watt. The housing shall be made of pressure diecast aluminium & the luminaire shall be IP65 & IK07 compliant. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current & potted type with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV, The luminiare shall use high power LEDs with CR≥70, SDCM≤5, CCT5700°K ± 300 °K. Similar to philips BY286V LED100S CW M3-S60 PSU FG WH V2 FRLS PXXXX or equivalent as per approved list.(for Street lighting) No. 0.0 12956.33 12193.2 10886.79 11431.0 0.0 Pkg-5B/08855 5.0.15 1.15 SITC of LED Highbay luminaire having maximum system wattage of 135W & Minimum system luminious efficacy of 145 lumens per watt. The housing shall be made of pressure diecast aluminium & the luminaire shall be IP65. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV, The luminiare shall use high power LEDs with CR≥70, SDCM≤5, CCT5700°K ± 300 °K. Similar to philips BY515P LED200S 5700 NB PSU GR FRLS PXXXXor equivalent as per approved list. No. 0.0 20037.78 18857.55 16837.1 17679.0 0.0 Pkg-5B/08855 5.0.16 1.16 SITC of LED Highbay luminaire having maximum system wattage of 105W & Minimum system luminious efficacy of 145 lumens per watt. The housing shall be made of pressure diecast aluminium & the luminaire shall be IP65. The luminaire shall employ a BIS registered driver with THD ≤10%@ full load, PF≥0.95@ full load. The driver shall be constant current with operating range of Input Voltage : 140-270V, inbuilt surge protection of 4KV, The luminiare shall use high power LEDs with CR≥70, SDCM≤5, CCT5700°K ± 300 °K. Similar to philips BY515P LED150S 5700 NB PSU GR FRLS PXXXXor equivalent as per approved list No. 0.0 17667.72 16627.09 14845.62 15588.0 0.0 Pkg-5B/08856 5.0.17 1.2 Supply, installation, testing and commissioning of wall decorative LED strip with 5 mtr length, minimum system wattage per mtr 12 W, & Operating voltage 12/24V DC with power controller. Similar to Instapower Cat No. Magic glow CAT No (134) and must conform to Ingress Protection Classification of IP 54.(For wall Decorative light) No. 0.0 13487.8 12693.37 11333.37 11900.0 0.0 Pkg-5B/08856 5.0.18 1.21 Supply, installation, testing and commissioning of Recessed Light with a nominal system lumen output of 4000 lumens and a minimum system efficacy of 74 lm/W. The luminaire should have a color temperature of 3000K and CRI>80 with beam angle of 24deg. The luminaire shall meet IP20 rating with THD 0.9 and should have tilting angle of +/- 30 deg. The luminaire housing should made of pressure die cast aluminum with a high efficiency diffuser. The total power consumption should not exceed 47W (including driver).Similar to Philips Make EcoAccent \\" RS271B LED40/830 PSU-E MB WH \\"\\"(For Art work at TOM) No. 0.0 10945.37 10300.69 9197.04 9657.0 0.0 Pkg-5B/08856 |
| 151 | DSR-2025: 8.5 5.1.1 DSR-2025: 8.5.3 12 -15 watt Each 1.0 1187.0 1187.0 1006.0 1016.06 1016.06 5.1.2 DSR-2025: 8.5.4 18 watt Each 25.0 1470.0 1470.0 1246.0 1258.46 31461.5 5.1.3 DSR-2025: 8.5.5 22 watt Each 25.0 1506.0 1506.0 1276.0 1288.76 32219.0 5.1.4 DSR-2025: 8.5.6 30 watt Each 1.0 2052.0 2052.0 1739.0 1756.39 1756.39 |
| 152 | DSR-2025: 8.7 5.2.1 DSR-2025: 8.7.2 18 watt Each 1.0 2240.0 2240.0 1898.0 1916.98 1916.98 5.2.2 DSR-2025: 8.7.3 22 watt Each 1.0 2695.0 2695.0 2284.0 2306.84 2306.84 5.2.3 DSR-2025: 8.7.4 36 watt Each 1.0 2962.0 2962.0 2510.0 2535.1 2535.1 5.2.4 DSR-2025: 8.7.5 40 watt Each 50.0 3685.0 3685.0 3123.0 3154.23 157711.5 5.2.5 DSR-2025: 8.7.6 45 watt Each 1.0 3913.0 3913.0 3316.0 3349.16 3349.16 |
| 153 | DSR-2025: 8.10 5.3.1 DSR-2025: 8.10.2 24-26 watt Each 1.0 745.0 745.0 631.0 637.31 637.31 5.3.2 DSR-2025: 8.10.3 36 watt Each 25.0 760.0 760.0 644.0 650.44 16261.0 5.3.3 DSR-2025: 8.10.4 40 watt Each 25.0 779.0 779.0 660.0 666.6 16665.0 |
| 154 | DSR-2025: 8.13 5.4.1 DSR-2025: 8.13.13 72 watt Each 1.0 2128.0 2128.0 1803.0 1821.03 1821.03 5.4.2 DSR-2025: 8.13.14 90 watt Each 1.0 2335.0 2335.0 1979.0 1998.79 1998.79 5.4.3 DSR-2025: 8.13.15 100 watt Each 5.0 2681.0 2681.0 2272.0 2294.72 11473.6 5.4.4 DSR-2025: 8.13.16 120 watt Each 5.0 2958.0 2958.0 2507.0 2532.07 12660.35 5.4.5 DSR-2025: 8.13.17 150 watt Each 1.0 3443.0 3443.0 2918.0 2947.18 2947.18 5.4.6 DSR-2025: 8.13.18 180 watt Each 1.0 4827.0 4827.0 4091.0 4131.91 4131.91 5.4.7 DSR-2025: 8.13.19 200 watt Each 1.0 5035.0 5035.0 4267.0 4309.67 4309.67 |
| 155 | DSR-2025: 8.16 5.5.1 DSR-2025: 8.16.1 50 watt Each 1.0 2009.0 2009.0 1703.0 1720.03 1720.03 5.5.2 DSR-2025: 8.16.2 70 watt Each 10.0 2299.0 2299.0 1948.0 1967.48 19674.8 5.5.3 DSR-2025: 8.16.3 100 watt Each 10.0 2467.0 2467.0 2091.0 2111.91 21119.1 5.5.4 DSR-2025: 8.16.4 150 watt Each 1.0 3457.0 3457.0 2930.0 2959.3 2959.3 5.5.5 DSR-2025: 8.16.5 200 watt Each 1.0 4689.0 4689.0 3974.0 4013.74 4013.74 5.5.6 DSR-2025: 8.16.6 250 watt Each 1.0 5969.0 5969.0 5058.0 5108.58 5108.58 |
| 156 | DSR-2025: 19.4 |
| 157 | DSR-2025: 19.5 |
| 158 | DSR-2025: 19.6 |
| 159 | 2.0 5.9.1 2.1 Supply and installations of 230 V, 1-phase, 1440 RPM, sweep of appx. 400mm Bracket fan including mounting bracket, blades, starters & other standard accessories complete as required. No. 1.0 1997.15 1879.52 1593.0 1673.0 1673.0 Pkg-5B/08856 182.0 5.9.2 3.0 Supplying and installations of 230 V single phase, 1400 mm sweep ceiling fans with electronic regulators including all standard accessories complete, mounting of regulator on grid plate & MS BOX etc. and suitable length down rod, duly painted, not exceeding minimum fan height of 2.4 m from floor as required and as below. No. 2.0 2330.88 2193.59 1859.0 1952.0 3904.0 Pkg-5B/08856 |
| 160 | DSR-2025: 9.2 |
| 161 | DSR-2025: 9.2.1 |
| 162 | DSR-2025: 9.2.3 |
| 163 | DSR-2025: 9.2.4 Total for Schedule-E05 471099.13 E.06 PROTECTIVE EARTHING |
| 164 | 6.0 6.3.1 6.1 75 mm x 6 mm GI strip M 1.0 326.43 307.2 274.29 288.0 288.0 Pkg-5B/08857 6.3.2 6.2 50 mm x 6 mm GI strip M 400.0 217.79 204.96 183.0 192.0 76800.0 Pkg-5B/08857 6.3.3 6.3 25 mm X 6 mm GI strip M 500.0 120.66 113.55 101.38 106.0 53000.0 Pkg-5B/08857 6.3.4 6.4 20 mm X 3 mm GI strip M 5.0 93.19 87.7 78.3 82.0 410.0 Pkg-5B/08857 6.3.5 6.5 50 x 6 mm Cu strip M 50.0 1979.22 1862.64 1663.07 1746.0 87300.0 Pkg-5B/08857 Note-1: In case of non availability of any of the sizes mentioned above, next higher size available in market shall be provided at the same rate. Note-2: No additional payment will be made for providing Test Link & Main Earth Terminals (made out of GI/Cu strips from within the above sizes). The METs will required to be fixed on walls as required and will be required to be provided with 12/16/20mm holes for connections of individual equipments including of other contractors'. |
| 165 | 9.0 Total for Schedule-E06 275727.0 E.07 LIGHTNING PROTECTION |
| 166 | 4.0 Total for Schedule-E07 219226.0 E.08 UNINTERRUPTED POWER SUPPLY SYSTEM |
| 167 | 1.0 A standby spare charger (for 1 to 6 UPS cells) and a spare cell bank with 6 nos of cells. Control transfer from one UPS to another UPS shall not cause any disruption of power supply. Overall availability of UPS system shall be better than 99.99%. Provision of suitable Earth Leakage detection both AC and DC supplies and Alarms shall be made. Temperature monitoring equipment shall be incorporated in the UPS system to optimize the charger voltage as function of battery room temperature, to generate alarm in case of room temperature exceeding the preset permissible temperature and to predict the battery back time. Alarms, health status and displays generated by each UPS shall be shown locally i.e. at SCR of station, as well at remote location in both OCCs (at Modipuram or as nominated by employer) at one separate terminal each in respective OCC. Telecommunication Contractor will provide LAN port between stations and the OCC for communication purpose, the point of Interface between TER (Telecom Equipment Room) and CER (Central Equipment Room) at OCC. E&M Contractor shall make all other necessary arrangements such as communication cards/ ports. Supply, Installation, Testing and Commissioning of lead acid sealed Maintenance free (VRLA) suitable for 4hours (2 hours+2 hours, means one battery set of 2 hours with one UPS and parallel redundant to second set of UPS + battery set of 2 hours) to the UPS System. Battery shall comply with relevant standard & regulations and Standards/Code e.g. IEEE485. Battery Racks shall be made of acid resistant material. Battery bank shall be so organized that:(i) One set shall normally function to take up the entire load of UPS, (ii) The cells shall be grouped such that touch voltage does not exceed 72V, (iii) A Separate Set shall consist of Six cell blocks each of the same voltage as in the Main Battery Bank, this set shall be maintained on charge from the charging unit such that one or more units from this set can replace faulty cell blocks of working battery bank. Note-1: The price of above item is inclusive of a contactor based ATS (Automatic Transfer Switch) suitable for terminating 2 nos. of suitable Size of Aluminium Conductor armoured cables on the incoming side of UPS. The automatic change over switch may be wall mounted in the UPS room. From automatic changeover switch to UPS, the connection should be through an adequately rated copper cable, and RS 485 port for display of ON/OFF status of UPS on BMS work station through MODBUS protocol is also included in the price. Note-2: The above price is also inclusive of Suitable Size copper Conductor, armoured cable from UPS outgoing side to Emergency lighting panel Panel (EMLP). Note-3: The above price is also inclusive of Input and output Panel for power distribution comprising of incomer from UPS of suitable rating and outgoing feeders of suitable rating to emergency lighting panel(with isolation transformer with copper winding), signalling, Telecom, PSD Labs, AFC Lab and two spare feeder. Total for Schedule-E08 7471993.0 E.09 VENTILATION & AIR CONDITIONING SYSTEM |
| 168 | (DSR-2025)31.3 (DSR-2025)31.3 Supplying, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/VariableRefrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s),minimum two compressors (with individual separate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load.The unit shall deliver the rated capacity and in confirmation as per IS18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39°C. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as perEnergy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWDspecification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building)For Cooling or Heating or Both |
| 169 | 31.3.1 |
| 170 | 31.3.2 |
| 171 | 31.3.3 Indoor Units DSR(E&M)-2025- 31.7 Supplying, Installation, Testing and Commissioning of following minimum capacity Double way VRV/VRFCassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The cooling capacity of indoor unit will be at airinlet conditions of 27 0C DB and 19 0C WB temperature.(Make will be same as of Outdoor) |
| 172 | 31.7.1 |
| 173 | 31.7.2 |
| 174 | 31.7.3 |
| 175 | 31.7.4 |
| 176 | 31.7.5 DSR(E&M)-2025- 31.11 Supplying, Installation, Testing and Commissioning of following minimum capacity and external static pressureVRF/VRV ceiling mounted mid high static ductable type Indoor unit equipped with washable synthetic media prefilter, fan section with low noise fan/dynamically balancedblower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outercabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature.(Make will be same as of Outdoor)High Static Ductable units (minimum 49 to 77 pascalexternal static pressure) |
| 177 | 31.11.1 |
| 178 | 31.11.2 |
| 179 | 31.11.3 |
| 180 | 31.11.4 |
| 181 | 31.11.5 |
| 182 | 31.11.6 |
| 183 | 31.11.7 |
| 184 | 31.11.8 |
| 185 | 31.11.9 31.12.1 High Static Ductable units (minimum 78 pascal externalstatic pressure) |
| 186 | 31.12.1 |
| 187 | 31.12.3 |
| 188 | 31.12.4 |
| 189 | NDSR-5 Supplying, installing, testing and commissioning of Ceiling Suspended Treated Fresh air Units each complete with coil, filter, etc. Air conditioners with evaporating unit comprising of cooling coil, blower with motor and 220 volt, 1 phase, 50 Hz, AC supply all as per specifications. The rate will also include entire drain pipes and nothing extra shall be payable. |
| 190 | DSR(E&M)-2025- 31.13 |
| 191 | 31.13.1 |
| 192 | 31.13.2 |
| 193 | NDSR-7 |
| 194 | NDSR 8 Supply, Installation, testing & commissioning of Main intelligent central controller with Scheduled Timer system Touch screen/Gate Way Type suitable for groups of indoor units to operate, monitor, on/off, cyclic operation setting, temperature setting etc. The controller shall be able to control up to minimum nos. of indoor units with zoning option as mentioned below. The controller shall have wide screen user friendly colour LCD Touch screen display and can be wired by a non-polar transmission cable The CRC shall be provided with suitable size metallic box with lock arrangement. The controller shall be integrated to BMS system thru software for monitoring & controlling of all above parameters including start/ stop of each indoor / outdoor unit. All necessary interface cards / units should be supplied as a part of the system to integrate to the BMS Software. |
| 195 | Notes: The vendor may offer the outdoor units as per availability from the manufacturer, however keeping the tonnage same as per BOQ subject to approval by Consultant/Client. The indoor units capacity can be also as per availability from the manufacturer but keeping the minimum capacity as required in BOQ subject to approval by Consultant/Client. |
| 196 | NDSR 9 DOUBLE SKIN FLOOR MOUNTED AIR HANDLING UNIT WITH FINE FILTER Supply, Installation, Testing and commissioning of factory built floor mounted Direct Expansion (DX Type) double skin type horizontal/vertical air handling units made of 50±1 mm thick panels consisting of pre plasticized G.I. casing of thickness 1.2mm outside layer and 1.0 mm inside layer with polyurethane foam (PUF) 48kg/m3 insulation factory injected between them by injection moulding machine of density, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for variable frequency drive applications, thermal break, drain connections, stainless steel (18G) drain pan with PUF insulation, Fire Rated Flexible Connection, necessary vibration isolation arrangement etc. complete as per specification. The cooling coil made of Aluminium finned Copper tube with coil section, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% in both the supply & exhaust side of AHU, fine filter section with filters of non woven synthetic media of 5 micron particle size in supply after fan, mixing chamber complete with fan with motor, belt drive etc. without face and bypass dampers. The AHU moter and blower shall be acoustically insulated with 25mm thick open cell nitrile rubber with 36 Kg/m³ density and covered with perforated type 0.8 mm MS farme on each sides. The motor & blower assembly shall be mounted on Aluminium extruded section. AHUs shall have air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS, the complete AHU shall conform to standard specification. The face velocity across cooling coil shall be limited to 500 FPM (2.52 MPS) maxim & Fan outlet velocity shall be not exceed 9.0 m/s. Casing shall be of panel construction; double wall type packed with pressure injected CFC free foam insulation minimum 50mm ± 1mm thick. Casing framework shall be of modular galvanized iron, aluminium or Approved equal pentapost double skin construction. Outer skin shall be minimum 1.0 mm galvanized steel sheet while inner skin shall be minimum 1.2 mm galvanized steel sheet. The sheets should have a minimum galvanisation of 275 GSM. The outer skin and inner skin should be precoated or powder coated on the exposed side. The mechanical performance of AHU shall be as per EN 1886. Rating performance for units, components and section shall be as per EN 13053. Fans shall be AMCA certified. Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional. Vendor to calculate static pressure based on drawings and pressure drop of finalized Equipment and submit for approval. The procurement shall be processed only after duly approval of calculation and selection from the Project Manager. Chemical, Biological and Radiological (CBR) filtration with dia-electric media with efficency not less than <90 % of PM .1 micron alongwith <95 % of gases contamination removal with 350 mm depth (CBR- Certification IACS for filteration efficiency, Green Pro, ISO, FDA & RoHS - refer details specifcation for CBR Filter for compliance) in the AHU along with necessary frames, Air Decontamination Chamber in the supply air/ plenum comprising of nanoX coating plasmOX having EPA approved metallic compound of five metals targeted on Alumninum matrix cell duly enclosed by a poly quartz casing tube with the capability to produce ionized Hydroxyl oxidizers having required wattage for different CFM's. The Equipment shall a microbiological testing report against Bacteriophage (MS-2 FDA) surrogate SARS Cov-2 with a minimum efficiency of 99 percent along with a Virology report from ICMR approved lab with an minimum efficiency of 99 percent against SARS COV2 within 45 minutes Cost shall be included for suitable rating Starter panel within MS enclosure near the fan with necessary power cabling & connection from Starter panel to fan motor. AHU Filter Shall be Capable of Treating fresh air up to recommended Breathing limit in Delhi NCR of PM 2.5 & PM 10(MERV 8 minimum ) EN779 |
| 197 | NDSR-10 Installation, Testing and commissioning of factory built Direct Expension (DX) Ceiling Suspended double skin air handling units made of (50±1)mm thick panels consisting of pre plasticized G.I. casing of thickness 1.0mm outside layer and 1.0 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE4 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for variable frequency drive applications, complete with motor, direct / belt drive as mentioned below, drain connections, stainless steel (18G) drain pan with PUF insulation, Fire Rated Flexible Connection, necessary vibration isolation arrangement etc. complete as per specification and of following capacities All direct driven fan motor shall be sourced from fan manufacturer & factory fitted only.The motor & blower assembly shall be mounted on Aluminium extruded section and acoustically insulated with 25 mm thick open cell elastomeric nitrile rubber with 36 Kg/m³ density and covered with perforated type 0.8 mm MS farme on each sides with suitable cable, starter panel. The complete AHU shall conform to standard specification. The face velocity across cooling / heating coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows: Casing shall be of panel construction; double wall type packed with pressure injected CFC free foam insulation minimum 50mm ± 1mm thick. Casing framework shall be of modular galvanized iron, aluminium or Approved equal pentapost double skin construction. Outer skin shall be minimum 1.0 mm galvanized steel sheet while inner skin shall be minimum 1.2 mm galvanized steel sheet. The sheets should have a minimum galvanisation of 275 GSM. The outer skin and inner skin should be precoated or powder coated on the exposed side The mechanical performance of AHU shall be as per EN 1886. Rating performance for units, components and section shall be as per EN 13053. Fans shall be AMCA certified. Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional. Vendor to calculate static pressure based on drawings and pressure drop of finalized Equipment and submit for approval. The procurement shall be processed only after duly approval of calculation and selection from the Project Manager. Chemical, Biological and Radiological (CBR) filtration with dia-electric media with efficency not less than <90 % of PM .1 micron alongwith <95 % of gases contamination removal with 350 mm depth (CBR- Certification IACS for filteration efficiency, Green Pro, ISO, FDA & RoHS - refer details specifcation for CBR Filter for compliance) in the AHU along with necessary frames, Air Decontamination Chamber in the supply air/ plenum comprising of nanoX coating plasmOX having EPA approved metallic compound of five metals targeted on Alumninum matrix cell duly enclosed by a poly quartz casing tube with the capability to produce ionized Hydroxyl oxidizers having required wattage for different CFM's. The Equipment shall a microbiological testing report against Bacteriophage (MS-2 FDA) surrogate SARS Cov-2 with a minimum efficiency of 99 percent along with a Virology report from ICMR approved lab with an minimum efficiency of 99 percent against SARS COV2 within 45 minutes Cost shall be included for suitable rating Starter panel within MS enclosure near the fan with necessary power cabling & connection from Starter panel to fan motor. |
| 198 | NDSR 11 Supply, Installation, Testing and Commissioning of VRV Kits for AHUs having all controllers & Electronic Expansion Valve (EEV) and temperature set arrangement. It Shall have cut off arrangement after a particular set value of Supply air Temperature. |
| 199 | NDSR 12 Supply , installation, testing & Commissioning of ceiling suspended DX type split AC units with air cooled condenser complete with 5 Star Inverter type scroll/rotary compressor ,condenser ,wiring & accessories . Indoor units shall be ceiling suspended/wall mounted type complete with evaporator ,fan, filter ,drier, expansion devices & microprocessor control panel along with all accessories with refrigerant & oil charge , corded remote controls. The unit shall be suitable for working at 240 ± 10% ,50 Hz,1 phase AC supply .The unit shall be designed to take care of minimum vertical head 5mt & horizontal length of 15 mt & necessary oil separator shall be included ,Necessary supporting arrangement for both indoor & outdoor units ( Powder Coated /Epoxy painted MS stand for ODU units as per approved make, shade by Architect) with necessary vibration isolation arrangement as per site condition etc. (without condensate drain pipe ,electrical power & control cabling between indoor & outdoor unit which shall be paid separately ). The coil in the outdoor units shall be provided with anti corrosive treatment. Necessary corrosive treatment of copper coil of the ODU with Bly gold Polu Al (Aluminium hydroxide, 25-microns thickness) to protect from corrosion, sulphur and other chemical contaminants present in the air. Coating should be done in presence of OEM representative. The coating shall be carried-out by the authorized applicator of coating manufacturer. The Outdoor unit Compressor must be provided with 5 Year Warranty Period. Silver Ion Filter, Dust Filter Civil Work such as wall hole making , wall chiselling ,refilling of chiselling part with mortar etc. as per site condition. Nitrogen pressure testing for leakages & flushing during installation & after commissioning between IDU & ODU with flare nuts Removable Covers for all indoor & Outdoor units shall be supplied & put on the units after installation & commissioning. Incoming power supply shall be provided near each indoor units |
| 200 | NDSR 13 |
| 201 | NDSR 15 AXIAL FLOW FANS (SMOKE EXTRACTION/EXHAUST FAN) Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung exhaust air tube axial flow fans of following capacity with GSS casing and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE3 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, including all accessories complete as required and as per specifications. Motor shall be of high temperature resistance \\"Class H Smoke Spill\\" 250° C for 2 hrs. Motor make shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%, noise level should not be more than 78 db. @ 3 m distance when measured in hemispherical reverberant room conditions. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating. Entire fan model & AMCA Seal shall appear in technical submittal of fan. Air moving capacity shall be as follows: Cost shall be included for suitable rating Starter panel within MS enclosure near the fan with necessary power cabling & connection from Starter panel to fan motor. Fan shall be supplied with Spring Isolators, Fire Rated Flexible Connection, GI gravity louvers, bird screen and fan guard. Note: Contractor Has to take approval on computer generated selection charts and fan curves showing power input and fan motor etc. prior to order the fans,(a) Noise level @ 3m from Fan shall be not more than 78 dB. Back draft Damper : Where required for system design roof-mounted fan shall be equipped with a rattle-free back draft damper to prevent air from re entering the fan when fan is not in operation, thus sealing completely in closed position. Damper shall be chatter proof under all conditions. Note:-These fans would be connected to the fire alarm system & BMS system of the building and would start automatically in case of Fire Note 1. Outlet Velocity for normal mode fans not to exceed 10.0 MPS(Meter/Second) 2. Outlet Velocity for Fire mode fans not to exceed 12.0 MPS (Meter/Second) 3. Fan motor shall meet IE3 or above standard as per IS-12615 4. Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional. Vendor to calculate static pressure based on drawings and pressure drop of finalized Equipment and submit for approval. The procurement shall be processed only after duly approval of calculation and selection from the Project Manager. 5. Thickness of casing : for dia( 315-630 )mm - 2.5mm , dia ( 710-1120)mm - 3mm , dia (1250-1400)mm - 4mm & dia 1600mm - 5mm. 6. In case of attenuator , calculation of reduction of sound level with insertion loss of attenuator is to be submitted. |
| 202 | NDSR 16 Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung Supply/ Pressurisation tube axial flow fans of following capacity with GSS casing and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE3 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'F' insulation etc. including all accessories complete as required and as per specifications. . Motor make shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%, noise level should not be more than 78 db. @ 3 m distance when measured in hemispherical reverberant room conditions. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating. Entire fan model & AMCA Seal shall appear in technical submittal of fan. Air moving capacity shall be as follows: Cost shall be included for suitable rating Starter panel within MS enclosure near the fan with necessary power cabling & connection from Starter panel to fan motor. Fan shall be supplied with Spring Isolators, Fire Rated Flexible Connection, GI gravity louvers, bird screen and fan guard. Back draft Damper : Where required for system design roof-mounted fan shall be equipped with a rattle-free back draft damper to prevent air from re entering the fan when fan is not in operation, thus sealing completely in closed position. Damper shall be chatter proof under all conditions. Note: Contractor Has to take approval on computer generated selection charts and fan curves showing power input and fan motor etc. prior to order the fans,(a) Noise level @ 3m from Fan shall be less than 78 dBA. with starter panel Note:-These fans would be connected to the fire alarm system & BMS System of the building and would start automatically in case of Fire Note 1. Outlet Velocity for normal mode fans not to exceed 10.0 MPS(Meter/Second) 2. Outlet Velocity for Fire mode fans not to exceed 12.0 MPS (Meter/Second) 3. Fan motor shall meet IE3 or above standard as per IS-12615 4. Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional. Vendor to calculate static pressure based on drawings and pressure drop of finalized Equipment and submit for approval. The procurement shall be processed only after duly approval of calculation and selection from the Project Manager. 5. Thickness of casing : for dia( 315-630 )mm - 2.5mm , dia ( 710-1120)mm - 3mm , dia (1250-1400)mm - 4mm & dia 1600mm - 5mm. 6. In case of attenuator , calculation of reduction of sound level with insertion loss of attenuator is to be submitted. |
| 203 | NDSR 17 Supply, installation, testing, commissioning of Single Skin Inline fan with Backward Curved SISW Fan, vibration isolators, speed regulator, GI gravity louvers, Bird Screen and required cable as per specification and drawing. The Motor shall be suitable to run on 1 phase/50 hz/ 220 v electrical power Supply including fire retardant non-porous double layer flexible connection of the following capacity. Thickness of casing : Upto 1000 CFM - 2mm , above 1000 CFM - 3mm The louvers & bird screen shall be made of 24G & 16G metallic construction respectively. |
| 204 | NDSR 18 METALLIC TYPE PROPELLER FAN Supply, installation, testing and commissioning of wall mounted Propeller type heavy duty exhaust Fan of metallic construction complete with speed regulator, bird screen, gravity louvers, vibration isolators, required cable, plug & other accessories compete as required, suitable for single phase, 240± 10 volts, 50Hz AC. supply of following capacities: |
| 205 | NDSR 19 Supply, installation, testing & commissioning of Wall mounted Propeller type exhaust air fans of high grade ABS plastic construction complete with electric motor suitable for operation on 230 V+ 10%,50 Hz, 1 phase AC supply fitted with speed regulator, mountings frames, louvers and bird screen, required cable & plug to connect with socket etc. complete as required of following capacities. |
| 206 | NDSR 20 Supplying, installing, testing and commissioning of Shielded control cum transmission wiring of 2 core x 1.5 sqmm copper FRLSH, XLPE insulated cable in suitable GI conduits accessories between indoor and outdoor units. Necessary securing of conduit shall be made by contractor. After completion of work wall and floor shall be repaired and brought to its original finish. The rate will also include cost of laying of GI conduit between indoor and outdoor units. |
| 207 | NDSR 21 Supply, fixing, testing and commissioning of interconnecting soft/hard drawn copper refrigerant pipe work of following outer diameter duly insulated with fire rated class'O' closed cell elastomeric nitrile rubber insulation (19mm/13mm thick) between indoor & outdoor units & protected with cladding as per specifications. All piping should be laid on Galvanized/Powder Coated tray supported by Galvanized M S Hangers & Clamps and all external piping shall run in covered cable trays. The rate includes all the items required to complete the piping work and nothing extra should be payable except the cable tray. Vaccumiazation & Nitrogen pressure testing for leakages & flushing during installation & after commissioning between IDU & ODU. Civil Work such as wall hole making , wall chiselling ,refilling of chiselling part with mortar etc. as per site condition. Covering of External refrigerant piping insulation shall be done with 26 G aluminium sheet cladding as per specifications. Internal Refrigerant piping insulation shall be covered with Aluminium Foil as per specifications. |
| 208 | 21.11 |
| 209 | 21.12 |
| 210 | NDSR 22 Providing and fixing of cPVC drain water piping complete with fittings, flexible connection to IDU, necessary support as per specification and insulated with 6 mm thick fire rated class'O' closed cell elastomeric nitrile rubber insulation. |
| 211 | 22.2 TOTAL OF Refrigerant /Drain Piping & Control Cabling |
| 212 | NDSR 23 FACTORY FABRICATED GALVANIZED SHEET METAL DUCTS (GSS) Supply, installation, testing and commissioning of factory fabricated Galvanized Steel (GSS) Sheet metal ducts complete with flanges, neoprene rubber gasket, elbows, Splitter Damper, vanes, hangers & support etc. as required as per IS/DW144/SAMACNA standard & confirming to specification. Duct shall be furnish at site in \\"L\\" shape or box shape from factory. The rates shall include all materials of the duct and labour for suspension and supporting arrangement for plenums, ducts, complete with fire retardant flexible connection as required and as per specifications. Note : Splitter Shall be a part of ducting. |
| 213 | NDSR 24 Supply, Fabrication, installation and testing of Galvanized Steel (GS) sheet metal ducts & finally applying fire rated paint as per BS 476 Part 24 (Site FABRICATED DUCTS For Connection /Plenum etc.) in accordance with the approved shop drawings complete with all accessories like vanes, flanges, suspension rods , anchor bolts, GI bolts & nuts, etc., as per specifications. Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 |
| 214 | NDSR 25 Supply. Installation, testing and commissioning of Fire rated sheet metal ducts with flanges complete with supports, vanes, dampers, links, levers and quadrants etc. as per specifications and drawings. Supporting distance shall not exceed 1.2 Mtr with 6mm thick fire retardant gasket suitable for 250 deg C 2 hr shall be used in duct joints along with fire sealants. The rates shall include all materials of the duct and labour for suspension and supporting arrangement for plenums, ducts, complete with fire retardant flexible connection as required and as per specifications. |
| 215 | NDSR 26 Supplying , installation, testing & commissioning of external thermal insulation on ducts with duly laminated 28G aluminium foil of mat finish Closed Cell Elastomeric Nitrile Rubber Insulation of density not less than 50±5 Kg/m³ & thermal Conductive not exceeding 0.032 W/mK at an average Temperature of 0°C and . The Material Shall be Class O as per BS476 part6 for fire propagation test. The Material shall have Fire Approval from CBRI - Roorkee & no toxicity under flaming and non- flaming condition as per AITM 3.000 (1993). Adhesive used for setting the insulation shall be non - flammable, Vapour Proof. All Joints should be sealed with 3 mm thick 50 mm wide PE tape and Flange to be overlapped by 6\\" width of the same material thickness. Finally Duct insulated should be strapped by 12mm metallic Packing strip at every random meter & conforming to standard and Specification. All Ducts insulated internally on oval shaped and externally insulated on rectangular ducts. |
| 216 | NDSR 27 AHU ROOM ACCOUSTIC LINING Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications. |
| 217 | NDSR 28 Supply and fixing of acoustic lining of supply air duct and plenum with thick Engineered Nitrile Rubber open cell foam having a Noise Reduction Coefficient of 0.55 with Density 160 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in antimicrobial protection. The material should pass Fungi Resistance Test as per DIN EN ISO 846 Method A and Bacterial Resistance Test as per DIN EN ISO 846 Method C; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents. protected with 26 G aluminium sheet cladding as per specifications. Acoustic lining in ducts/plenum up to 5.0 Running meter from Fan Outlet as per specification and drawings. |
| 218 | NDSR 29 VOLUME CONTROL DAMPER |
| 219 | NDSR 30 Supply. Installation, testing and commissioning of powder coated extruded aluminium section grills with aluminium dampers for supply air terminal and grilles without damper for return air for air-conditioning as per specification. |
| 220 | 30.2 Diffusers |
| 221 | NDSR 31 |
| 222 | NDSR 32 Supply. Installation, testing and commissioning of thermal flexible aluminium duct of following sizes duly supported at regular interval as per site requirement & speciation's. |
| 223 | NDSR 33 Supply. Installation, testing and commissioning of slot diffusers with/without damper as specified below and as per specification. |
| 224 | NDSR 34 Supply. Installation, testing and commissioning of powder coated extruded aluminium Linear Grille. |
| 225 | NDSR 35 |
| 226 | NDSR 36 Motorized Fire Dampers With Actuator Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Duct/Wall mounted multi blade, motorised fire & smoke dampers with spring return actuator. The damper shall be of at least 1.5 hr. fire rating and actuated with the help of 24 V electric actuator excluding. The damper shall be as per UL listed UL 555; 1995 and CBRI approved. The damper shall be constructed out of 16G galvanised steel sheet & as per specification with Control Cable to Potential Free Contact for tripping of AHU fan motor. Supply, installation, testing and commissioning of Motorised Spring Return Actuator for devices up to 0.8 sq. meter with control panel & temperature sensor. |
| 227 | NDSR 37 Supply, Installation, Testing & Commissioning of following Switchgears as an Isolator in IP-65 rated in power coated 16 SWG sheet steel enclosure . |
| 228 | NDSR 39 Supplying and installation for following size of perforated Hot Dipped Galvanised Iron Covered cable tray With Bends, Tee, Cross Member & Reducer (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 229 | 39.3 9307180.73 E.10 FIRE DETECTION & ALARM SYSTEM |
| 230 | A A FIRE ALARM SYSTEM DSR(E&M)-2025-28.2 INTELLIGENT FIRE ALARM SYSTEM |
| 231 | 28.2.1 43.1.1 28.2.1.2 Two Loop Panel. No 1.0 250420.0 250420.0 212220.0 214342.2 214342.2 43.1.2 DSR(E&M)-2025- 28.2.3 Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete asrequired. Each 1.0 113734.0 113734.0 96385.0 97348.85 97348.85 43.1.3 DSR(E&M)-2025-28.2.4 Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. Each 30.0 3004.0 3004.0 2546.0 2571.46 77143.8 43.1.4 DSR(E&M)-2025-28.2.5 Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED,metallic cover complete with all connections etc as required. Each 10.0 306.0 306.0 259.0 261.59 2615.9 43.1.5 DSR(E&M)-2025-28.2.6 Supplying, installation, testing & commissioning of intelligent addressable programmable sounder complete as required. Each 10.0 2787.0 2787.0 2362.0 2385.62 23856.2 43.1.6 DSR(E&M)-2025-28.2.7 Supplying, installation, testing & commissioning of fault isolator complete with base as required. Each 5.0 3434.0 3434.0 2910.0 2939.1 14695.5 43.1.7 DSR(E&M)-2025-28.2.9 Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required Each 2.0 2866.0 2866.0 2429.0 2453.29 4906.58 43.1.8 DSR(E&M)-2025-28.2.10 Supplying, installation, testing & commissioning of addressable fire control module complete as required. Each 5.0 3156.0 3156.0 2675.0 2701.75 13508.75 43.1.9 DSR(E&M)-2025-28.2.14 Supplying, installation, testing & commissioning of addressable manual call point (Plunger type ) complete as required. Each 6.0 4063.0 4063.0 3443.0 3477.43 20864.58 43.1.10 DSR(E&M)-2025-28.2.15 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. Each 10.0 3682.0 3682.0 3120.0 3151.2 31512.0 43.1.11 h) Intelligent Addressable Monitoring Modules Each 2.0 2573.88 2422.28 2162.75 2271.0 4542.0 Pkg-5B/08864 43.1.12 j) Intelligent Addressable Flow Switch Input Module . Each 1.0 2387.6 2246.97 2006.22 2107.0 2107.0 Pkg-5B/08864 43.1.13 4.0 Supplying, Laying, Termination, Testing &Commisioning of Fire Survival Cables (confirming to BS: 7629 and Section specifications for perfomance requirements of Fire Survival Cables) armoured, 1 pair 1.5 sq.mm, screened / shielded, Copper conductor cable complying the CWZ category along with necessary conduits and accessories. ( for power ) RMT 580.0 38.17 35.92 32.07 34.0 19720.0 Pkg-5B/08864 43.1.14 5.0 Supplying, Laying, Termination, Testing &Commisioning of Fire Survival Cables (confirming to BS: 7629 and specifications for perfomance requirements of Fire Survival Cables) armoured, 1 twisted pair 1.5 sq.mm, screened / shielded copper conductor cable complying the CWZ category for looping of detection units along with necessary conduits and accessories etc. ( For loop Control ) RMT 1080.0 38.17 35.92 32.07 34.0 36720.0 Pkg-5B/08864 563883.36 |
| 232 | DSR(E&M) -2025.29.1 44.1.1 29.1.12 320KVA 1.0 2447399.0 2447399.0 2074067.0 2094807.67 2094807.67 2094807.67 E.12 Fire Fighting System |
| 233 | 1.0 Supply, installation and testing of fire pumps, electrically driven generally as specified and shown in equipment schedule complete with: i) all accessories ii) vibration mounts iii) test connection excluding starter panel iv) The pump heads specified on the Drawings and / or Equipment Schedules are for guidance and information only and are calculated based on assumed equipment pressure drops. The exact pump head based on the pipe run and the offered equipment shall be carefully checked and re-calculated for each pump before ordering the equipment. Calculation shall be submitted for approval. No modification to the piping system shall be allowed without prior approval. Any additional cost for the modification of the system (pumps, motors, switchgears, cables, panel boards, switchboards, etc.) necessary to meet the specified duties, special conditions and the offered equipment shall be provided at no extra cost to the Employer. 45.1.1 1.3 Supply, installation, testing, trial run and commissioning of hydrants all complete as required and as approved Set 6.0 33440.72 31471.06 28099.16 29504.0 177024.0 Pkg-5B/08870 Internal hydrants/landing valves generally as specified and all complete with below mentioned accessories i) 63mm dia Single headed landing valve IS marked (Stainless steel) ii) First aid hose reel with 25 mm dia, 45 m long thermoplastic hose as per IS 12585 rubber hose, ball valve, piping and 7-8mm nozzle as required iii) 38mm synthetic synthetic hoses (UL Listed) with 63mm instantaneous SS coupling, IS marked- 15 m x 2 lengths with suitable arrangement of connecting the hose pipe with coupling as required. iv) branch pipe and nozzle IS marked (Stainless steel) v) Pressure gauge with stop cock. |
| 234 | 1.4 Hose cabinet as approved or as per site conditions with universal locking arrangement. Glazed with 5.5mm clear glass Powder coated Stainless Steel shutter door as appropriate with universal locking arrangement with grill of following sizes and types : 46.1.1 1.4.1 Size 1500 x 1850 in 2 mm thick stainless steel sheet Set 2.0 23104.14 21743.31 19414.0 20385.0 40770.0 Pkg-5B/08870 46.1.2 1.4.2 Size 2100 x 1200 in 2 mm thick stainless steel sheet Set 4.0 20672.13 19454.54 17370.0 18239.0 72956.0 |
| 235 | 1.5 47.1.1 1.6 Supply and Installation of Orific Plate complete as required -80 to150mm Dia. Each 16.0 1702.41 1602.14 1430.0 1502.0 24032.0 |
| 236 | 1.7 48.1.1 1.8 Providing and fixing standard Fire man AXE with heavy rubber handle as complete. Each 6.0 729.6 686.63 613.0 644.0 3864.0 |
| 237 | 1.9 49.1.1 1.9.1 80 mm dia Each 1.0 10093.38 9498.88 8481.0 8905.0 8905.0 Pkg-5B/08871 49.1.2 1.9.2 65 mm dia Each 1.0 5147.15 4843.98 4325.0 4541.0 4541.0 49.1.3 1.9.3 150 mm dia Each 4.0 9081.12 8546.24 7631.0 8013.0 32052.0 |
| 238 | 2.1 i) All pipes and all heavy grade fittings conforming to IS 1239 together with welded joints, flanges, gaskets, bolts & nuts, washers, fittings, adapter pieces etc.including necessary Excavation as required 50.1.1 2.1.1 150 mm nominal bore M 25.0 2370.96 2231.31 1992.0 2092.0 52300.0 Pkg-5B/08871 50.1.2 2.1.2 100 mm nominal bore M 20.0 1678.61 1579.74 1410.0 1481.0 29620.0 50.1.3 2.1.3 80 mm nominal bore M 20.0 1240.85 1167.76 1043.0 1095.0 21900.0 |
| 239 | 2.2 51.1.1 2.2.1 200 nominal bore Each 20.0 17875.83 16822.94 15020.0 15771.0 315420.0 Pkg-5B/08871 51.1.2 2.2.2 150 nominal bore Each 6.0 7174.96 6752.35 6029.0 6330.0 37980.0 51.1.3 2.2.3 100 nominal bore Each 2.0 4986.15 4692.47 4190.0 4400.0 8800.0 51.1.4 2.2.4 80 nominal bore Each 17.0 3891.22 3662.03 3270.0 3434.0 58378.0 51.1.5 2.2.5 65 nominal bore Each 1.0 3526.94 3319.2 2964.0 3112.0 3112.0 |
| 240 | 2.2.6 |
| 241 | 2.2.7 |
| 242 | 2.2.8 |
| 243 | 2.2.9 |
| 244 | 2.3 56.1.1 With F.P.S. bricks Each 1.0 12160.08 11443.85 10218.0 10729.0 10729.0 Pkg-5B/08871 |
| 245 | 3.1 57.1.1 3.1.1 25 mm nominal bore RMT 50.0 376.7 354.51 317.0 333.0 16650.0 Pkg-5B/08872 57.1.2 3.1.2 32 mm nominal bore RMT 100.0 486.4 457.75 409.0 429.0 42900.0 57.1.3 3.1.3 40 mm nominal bore RMT 50.0 547.46 515.21 460.0 483.0 24150.0 57.1.4 3.1.4 50 mm nominal bore RMT 35.0 765.83 720.72 644.0 676.0 23660.0 57.1.5 3.1.5 80 mm nominal bore RMT 56.0 1131.15 1064.53 950.0 998.0 55888.0 57.1.6 3.1.6 100 mm nominal bore RMT 100.0 1556.49 1464.81 1308.0 1373.0 137300.0 57.1.7 3.1.7 150 mm nominal bore RMT 300.0 2432.02 2288.77 2044.0 2146.0 643800.0 57.1.8 3.1.8 200 mm nominal bore ( 6 mm wall thickness ) RMT 5.0 2979.48 2803.99 2504.0 2629.0 13145.0 |
| 246 | 3.3 59.1.1 3.3.1 Size 150 mm Each 4.0 18283.43 17206.54 15363.0 16131.0 64524.0 Pkg-5B/08872 59.1.2 3.3.2 Size 80 mm Each 4.0 4072.19 3832.34 3422.0 3593.0 14372.0 |
| 247 | 3.6 60.1.1 3.6.1 25 mm dia Each 3.0 2188.81 2059.89 1839.0 1931.0 5793.0 Pkg-5B/08872 |
| 248 | 3.7 61.1.1 3.7.1 25mm to 40 mm nominal bore Each 4.0 2554.13 2403.69 2146.0 2253.0 9012.0 Pkg-5B/08872 61.1.2 3.7.2 50 mm nominal bore Each 3.0 4742.95 4463.59 3985.0 4184.0 12552.0 |
| 249 | 3.8 Providing and fixing electrically operated Flow Indicating switches including 1.5 mm thick gasket, nuts and bolts complete as per M & W Specification. Nos 2.0 1518.53 1429.09 1276.0 1340.0 2680.0 Pkg-5B/08872 62.1.1 For 80mm to 150 mm dia pipes Nos. 4.0 350.43 329.79 294.0 309.0 1236.0 |
| 250 | 4.0 63.1.1 4.1 Providing, fixing, testing and commissioning of UL listed Pendant / Upright type Sprinkler Head rated at 68 degree centigrade Each 10.0 365.32 343.8 307.0 322.0 3220.0 Pkg-5B/08872 63.1.2 4.2 Providing and fixing sprinkler drain with 25 mm dia ball valve. Each 2.0 1167.37 1098.61 981.0 1030.0 2060.0 63.1.2 4.3 Providing and fixing UL listed Flow Switch of 80 / 100 / 150 mm dia on Sprinkler Header complete with flexible full bore paddle, U clamp and NO / NC contact terminals Each 6.0 6323.24 5950.8 5313.0 5579.0 33474.0 |
| 251 | 5.0 Supply and installation of portable fire Extinguishers as described below: 64.1.1 5.1 Providing and fixing portable fire extinguisher, stored pressure dry powder type with cylinder initially fully charged with dry powder (ABC type) of 6 Kg, complete with pressre guage, standard discharge valve with tube, CI bracket for wall mounting etc. Each 13.0 2197.69 2068.25 1847.0 1939.0 25207.0 Pkg-5B/08873 64.1.2 5.2 Carbon dioxide extinguisher conforming to relevant IS with high pressure discharge tube, horn, control valve, IS marked including clamps etc. 64.1.3 5.3 Providing and fixing initially fully charged Portable Fire Extinguisher of 4.5 Kg. capacity, carbon dioxide type with cylinder with CO2 gas, complete with squeeze lever Discharge Valve, Discharge Tube Horn including CI bracket for wall mounting etc. Each 13.0 4986.15 4692.47 4190.0 4400.0 57200.0 Pkg-5B/08873 64.1.4 5.4 Mechanical foam type 9.0 liter capacity fire extinguisher (for DG room) Each 2.0 1824.53 1717.07 1533.0 1610.0 3220.0 64.1.5 5.5 Providing and fixing fire extinguishers water type of Capacity 9 liter with internal plastic fitting and ISI marked as per IS-940 with Gun metal Cap co2 cartridge and Initial refil. Each 2.0 2067.73 1945.94 1737.0 1824.0 3648.0 64.1.6 5.6 Providing and Fixing Co2 gas type trolley mounted fire extinguisher of capacity 22.5 kg with ISI marked and as Item IS 2878with discharge nozzle and initial refil. Each 2.0 15687.01 14763.05 13181.0 13840.0 27680.0 64.1.7 5.7 Providing and fixing trolley mounted fire extinguisher of capacity 50 liters with IS marked as per IS 13385 or Equivalent Standard with nozzle and Initial refil. Each 1.0 7174.96 6752.35 6029.0 6330.0 6330.0 |
| 252 | 6.1 Supply, fixing, testing and commissioning of UL 521, UL listed Polymer Tube Detection based Clean Agent System for Electrical Panels, consisting of the following components: 65.1.1 6.1.2 5 LB CAPACITY Clean agent system complete with all necessary gas ,fitting ,support ,and accessories,connected with valve. NOS. 4.0 76608.47 72096.23 64372.0 67591.0 270364.0 Pkg-5B/08873 65.1.2 6.1.3 End of Line adaptor NOS. 4.0 8390.97 7896.74 7051.0 7404.0 29616.0 Pkg-5B/08873 65.1.3 6.1.4 Pressure Switch NOS. 4.0 4134.43 3890.91 3474.0 3648.0 14592.0 65.1.4 6.1.5 Flexible Polymer Detection Tube with all necessary fittings & supports. MTR. 100.0 1154.95 1086.92 970.0 1019.0 101900.0 65.1.5 6.1.6 Master Control Unit for connecting each system with electronic hooters and productivity input to Scada /Fire Alarm system including all necessaries +electrical wiring to make each entire system functional NOS. 4.0 17024.11 16021.39 14305.0 15020.0 60080.0 Note: The items indicated above are notable items. The vendor to include all allied and implid items in required quantity at no extra cost. |
| 253 | 66.1.1 1.0 120 Ltr Cylinder/Valve Assembly & Pressure Gauge ( CCOE approved) including piping in compliance to the requirements specified in clause no.4.2.1 of NFPA-2001 NOS. 2.0 154169.9 145089.29 129544.0 136021.0 272042.0 Pkg-5B/08815 66.1.2 1a Clean Agent (Novec 1230/Equivalent) filled in above cylinder (Kgs) KGS 300.0 3776.95 3554.49 3174.0 3333.0 999900.0 66.1.3 1b Master cylinder kit comprising Solenoid actuator, Manual actuator, adapters, discharge hose, warning sign etc. NOS. 1.0 77895.87 73307.8 65453.0 68726.0 68726.0 66.1.4 1c Slave cylinder kit comprising Pneumatic actuator, Actuation hose, Discharge hose, connectors etc. NOS. 3.0 56061.89 52759.84 47107.0 49462.0 148386.0 66.1.5 2.0 Manifold check valve NOS. 4.0 30981.9 29157.07 26033.0 27335.0 109340.0 66.1.6 3.0 Discharge pressure switch KGS 1.0 27293.06 25685.5 22933.0 24080.0 24080.0 66.1.7 4.0 Discharge nozzles NOS. 11.0 6786.46 6386.74 5702.0 5987.0 65857.0 66.1.8 5.0 Cylinder bracket NOS. 4.0 1327.38 1249.2 1115.0 1171.0 4684.0 66.1.9 6.0 Manifold for connecting 8 cylinders LOTS 1.0 121713.38 114544.46 102272.0 107386.0 107386.0 66.1.10 7.0 Gas release Panel including smoke detector ,MCP , Abort switch & Strobe cum sounder NOS. 1.0 279940.78 263452.27 235225.0 246986.0 246986.0 4958990.0 E.13 Any Other DSR (E&M-2025) 1644163.36 Total Cost 34527431.0 Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail