| 1 | S & F in repair for Air termination, single pointed copper rod 12mm dia and 300mm long with DNB insulators complete all as specified and directed. |
| 2 | S & F in repair for Air termination, single pointed aluminium rod 12mm dia and 300mm long with DNB insulators complete all as specified and directed. |
| 3 | M & L for earthing complete with Gl electrode 600 mm x 600 mm x 6.00mm thick buried directly in ground vertically in pit of depth not less than 2.25 mtr below normal ground level with top edge of the earth plate not less than 1.50 mtr below normal ground level connected to Gl earth strip 32 mm X 6mm(up to 7.5 mtr length on earth plate) as earthing lead by means of bolts, nuts, check nuts and washer of galvanized iron or steel including excavation and earth work and disposal of surplus soil including provision of 40 mm dia light grade pipe up to 7.5 mtr length and necessary fitting for protection of Gl strip including laying of charcoal, dust and common salt ,PCC (1:3:6) type C-l( using 20 mm graded crushed stone aggregate) earth pit with 40x40x6mm mild steel angle iron frame & 50mm thick pre cast RCC cover (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) reinforced with 8mm dia TMT bars @ 75mm C/C both way with mild steel handle 12 mm dia round bars ,10mm thick plastering with cement mortar (1:4) internally and upto 150 mm below ground level externally, PGI funnel with wire mesh 20mm dia Gl pipe for watering complete all as shown on electrical plate No.3 of SSR Part -1 2009 and connected in earth testing point including testing cincluding taking down old/ unserveciable existing earthing & making good disturbed surface of wall ,floors etc.complete all as directed. Notes: -(i) Earth lead & protection pipes length upto & including 7.50 metre. (ii) Earth filling shall be done by vegetable soil. (iii) Soil should be free from stone, boulders, aggregate, gravels etc. (iv)The rate is inclusive of necessary earth work, returning, filling in and removal etc |
| 4 | M&L for pipe in pipe chemical earthing with GI pipe electrode 3.0 m long having outer pipe dia 80 mm & inner pipe dia 50 mm duly filled with highly conductive and anti corrosive compound of required quantity having chemical composition Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% burried in ground by digging a bore of 150 mm dia surrounded by soil friendly backfill compound non soluble in water including connection with Gl earth strip 32 mm X 6mm(up to 7.5 mtr length on earth plate) as earthing lead by means of bolts, nuts, check nuts and washer of galvanized iron or steel, making PCC pit of size 0.3 m x 0.3 m x 0.3 m (inner size) in mix PCC (1:3:6) type C-l( using 20 mm graded crushed stone aggregate) with 50mm thick pre cast RCC cover (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) reinforced with 8mm dia TMT bars @ 75mm C/C both way with mild steel handle 12 mm dia round bars ,10mm thick plastering with cement mortar (1:4) internally and upto 150 mm below ground level externally, and testing on completion to achieve value not more than 2.0 ohm complete. (Note - GI strip size 32x6 mm upto 7.5 m included in the item). |
| 5 | Material and labour for chemical earthing complete with copper earth plate electrode 900mm x 600mm x 5mm thick buried directly in ground vertically to a depth not less than 4m below normal ground level with top edge of the earth plate at a depth not less than 2.25m below ground level connected to and including copper strip of size 32x6 mm by means of nuts, bolts, check nuts and washer etc, made of copper and connected to test point and earth dolly all as shown in electrical plate No. 03 SSR Part-I 2020 and specified or indicated including providing charcoal dust 1000 Kgs, common salt 500 Kg, magnesium Sulphate 150 Kgs and all around the plate 15 CM depth RCC 50 mm thick in cement and wide and upto 650 mm height in continuous layers, balance pit will be filled with vegetable soil upto ground level including excavation and earthwork in any type of soil, PCC pit of size 0.3 m x 0.3 m x 0.3 m (inner size) in mix PCC (1:3:6) type C-l( using 20 mm graded crushed stone aggregate), 50mm thick pre cast RCC cover (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) reinforced with 8mm dia TMT bars @ 75mm C/C both way with mild steel handle 12 mm dia round bars ,10mm thick plastering with cement mortar (1:4) internally and upto 150 mm below ground level externally,, 80mm bore light grade GI watering pipe, lugs, 80mm bore light grade GI protection pipe upto 7.5 metre etc. complete all as specified and directed. NOTE :- The rate of above Item includes the cost of earth lead and GI protection pipe up to 7.5 Metres. Copper strip beyond 7.5 Metre shall be measured and paid for separately. |
| 6 | M&L for spreading 40 mm graded stone aggregate deposited, spread and levelled in layers not exceeding 15 cm thick through out the sub station open areascomplete all as specified and directed. |
| 7 | S& F in repair for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 mm X 6 mm galvanised iron strip including necessary clamps ,nuts,bolts ,DNB insulators& hylem sheet block complete all as specified and directed. |
| 8 | Excavation in trenches in all of kind of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables /pipes,foundations ,laying of cable, shafts, well, cesspits, manholes etc.& not exceeding 10 M² on plan complete all as specified and directed. |
| 9 | Returning, filling in including spreading, leveling, watering and well ramming in layers of not exceeding 25 cm thick after the cables & pipes etc. are laid, jointed & tested and foundations complete all as specified and directed by Engineer-in-Charge. |
| 10 | S & F in repair 15 mm dia Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed. |
| 11 | S&F in repair self closing tap of cast iron or malleable cast iron, Galvanised, screwed for iron pipe and fixed 15mm bore complete all as specified and directed. |
| 12 | M&L for cutting of existing steel tubing for alteration or additions of size 15 mm complete all as specified and directed. |
| 13 | S&F for GI water tubing medium grade, ISI marked, galvanised, 15 mm bore with all fittings, (such as tee, elbow, socket, union & short pieces) fixed to walls and ceiling or laid in floors , laid in trenches including cutting chases for brick walls and making good the surface in cement mortar 1:3 complete all as specified & directed. |
| 14 | M&L for steel structure,cross arms bracing supports,clamps,back plates of any type,section incl, nuts,bolts washers,welding bending cold or hot in any size and shape all as directed incluking two coats of alumminium paints over a coat of red oxide primer including preparation of surface all as directed by Engr - in -Charge.(For construction of HT bay,Structure for GOD & LA) |
| 15 | M&L for in replacement of 20 to 25 mm thick kota stone as in earth pit cover (size 600 mm x 600 mm) complete all as specified and directed by Engr - in -Charge. |
| 16 | S& F in repair for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 100 mm X 10 mm galvanised iron strip including necessary clamps ,nuts,bolts ,DNB insulators& hylem sheet block complete all as specified and directed. Note :- Main earthing strip shall be buried under ground and earthi work will be measured and paid separately under respective items of BOQ. |
| 17 | Disconnecting and taking out the defective / non-functional desert cooler of any description and in any position and any floor installed at direct approach, strip opening of desert cooler, cleaning, servicing, oiling & greasing etc of desert cooler, taking out and removing unserviceable / defective parts and internal wiring, replacement of unserviceable & damaged parts and internal wiring, re-assembling & testing of the desert cooler all as specified and directed by Engineer-in-Charge. Note: -(i) The replacement of defective / non functional parts shall be measured & paid for separately as “Supply only” under appropriate item of BOQ’ and fixing charges for new items are deemed to be included under this item and replacement of unserviceable / damaged body portions i.e. panels / switch board / bottom / top / grills / frame etc. of the desert cooler shall also be measured and paid for separately under appropriate item of BOQ. (ii) Burnt out windings replaced, shall be measured and paid for separately under appropriate item of BOQ’ for rewinding. (iii) The rates for above items are deemed to include for transportation to & fro of vertical pumps/fan motors to workshop as approved by Engineer-in-charge for necessary repairs, alignment and testing of pump and motors at workshop & replacement of necessary unserviceable screws/ nuts/ bolts/ washers/ packing etc with new one. |
| 18 | Supply only PVC flexible water Pipe 15 mm dia complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply only PVC distributor 3 way, suitable for 15mm dia water distribution all as specified and directed by Engineer-in-Charge. |
| 20 | Supply only new 3 core PVC insulated copper cable size 1.5 Sq mm round 1100 volt grade as in connection to desert coolers all as specified and directed by Engineer-in-Charge. (Make : plaza / Finolex /National /Polycab/Gloster ) |
| 21 | Supply only shaft for fan motor of desert cooler all as specified and directed by Engineer-in-Charge. |
| 22 | Supply only gun metal bushes for fan motor of desert cooler all as specified and directed by Engineer-in-Charge. |
| 23 | Taking out & removing old burnt out windings of fan motor and rewinding the fan motor of any description and in any capacity with using existing size copper super enameled wire as approved by the engineer-in-charge including insulating material such as luminous paper, Letherized paper, cotton tape, glass sleeving insulating varnish etc complete all as specified and directed by Engineer-in-Charge. NOTE: (i) Fixing, connecting and testing charges of the repaired motor are deemed to be included under respective item above). (ii) Replacement of unserviceable shaft / GM bushes, fan blades etc shall be measured and paid for separately under appropriate item of Schedule `A' as supply only |
| 24 | Supply only submersible pump for desert cooler 1.5 mtr head.(Make : Crompton / AUE / Khaitan/ Bajaj |
| 25 | Supply only blower fan motor Copper winding for desert cooler single phase 230V, 150w to 180w.(Make : Crompton / AUE / Khaitan/ Bajaj) |
| 26 | Supply only aluminium fan blade ( set of three blades) for cooler motor of any description to suit existing motor all as specified and directed by Engineer-in-Charge. . |
| 27 | S & F in repair chicken wire mesh with using new hexagonal wire mesh having 15mm size mesh and 0.5mm dia of wire for supporting to the wood wool pads all as specified and directed by Engineer-in-Charge. |
| 28 | S&F Grass Wool Pad (as approved) suitable for Desert Cooler and best quality of required size (three in each on desert cooler)including taking out/ down unserviceable one, complete all as specified and as directed. |
| 29 | S&F in repair for Front Grill Double Partition type of 20 SWG metal grill, best quality (as approved) of existing shape and size for Desert Cooler including taking out/ down unserviceable one, complete all as specified and directed by Engineer-in-Charge. |
| 30 | M&L preparing old surfaces of Desert Cooler Body by descaling, rubbing, brushing, cleaning and applying one coat of synthetic enamel paint (as approved) with spray gun machine (Blue) on all exterior surfaces of cooler and inner side of tank with one coat of black bituminous paint complete all as specified and as directed. |
| 31 | S & F in replacement of unserviceable 15mm dia Ball brass valves, high pressure, with polythene float and fly nut complete, screwed for iron pipe or brass ferrule all as specified and directed by Engineer-in-Charge. |
| 32 | Cleaning and re-filling of fire extinguisher, 1 Kg, DCP (dry chemical powder) type including filling media/material and replacement of required accessories for ready to use complete all as specified and as directed. |
| 33 | Cleaning and re-filling of fire extinguisher,6 Kg, DCP (dry chemical powder) type including filling media/material and replacement of required accessories for ready to use complete all as specified and as directed. |
| 34 | Cleaning and re-filling of fire extinguisher, 22.5 Kg, CO2 type including filling media/material and replacement of required accessories for ready to use complete all as specified and as directed. |
| 35 | Servicing of Transformer Protection panel by removing dust and cleaning by CRC solution. carrying out serviceability check of all components and refixing of all servicable components complete including connection with internal wiring. Replacement of all unserviceable components as per existing type/make and rating of equivalent type assembling the protection panel, including connecting with power Transformenr and testing complete to the entire satisfaction of EIC. Note:- (i) All components/spares required to be replaced shall be measured and paid seperately under respective item as 'Supply only as detailed hereafter. (ii) The internal wiring of suitable size shall be of copper including terminal, lugs and screw to be replaced as per requirement and cost there of is deemed to be included in item rate. |
| 36 | Supply only W.T trip relay 110 V DC of suitable size. |
| 37 | Supply only O.T.I trip relay 110 V DC of suitable size. |
| 38 | Supply only BCZ trip relay 110 V DC of suitable size. |
| 39 | Supplying, laying, jointing and testing LT 1100 volt grade armoured copper Cable of size 2.5 Sq mm,12 core. including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc including taking down existing cable complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. |
| 40 | Disconnection of LT APFC panel from main distribution panel. Segregation of all serviceable and unserviceable components like capacitors, contactors, auxilary block, CT coil, multifunction meters, relays, indicators, push button etc, carrying out servicing of complete APFC panel, by removing dust and cleaning by CRC solution. carrying out serviceability check of all components and refixing of all servicable components complete including connection with internal wiring. Replacement of all unserviceable components as per existing type/make and rating of equivalent type assembling the APFC panel, including connecting with LT distribution panel board and testing complete to the entire satisfaction of EIC. Note:- (i) All components/spares required to be replaced shall be measured and paid seperately under respective item as 'Supply only as detailed hereafter. (ii) The internal wiring of suitable size shall be of copper including terminal, lugs and screw to be replaced as per requirement and cost there of is deemed to be included in item rate. (iii) Inspection note indicating involvement of repair work and replacement of components is to be prepared and submitted by Contractor for each APFC panel |
| 41 | Supply only Type MO C3, 10A rated operational current (AC-1) capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-datching auxilary contacts 1NO/1NC and damping resistors complete . |
| 42 | Supply only Type MO C5, 10A rated operational current (AC-1) capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-latching auxilary contacts 1NO/1NC and damping resistors complete . |
| 43 | Supply only Type MO C10, 25A rated operational current (AC-1) capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-latching auxilary contacts 1NO/1NC and damping resistors complete . |
| 44 | Supply only Type MO C12.5, 40A rated operational current (AC-1) capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-latching auxilary contacts 1NO/1NC and damping resistors complete. |
| 45 | Supply only Type MO C15, 40A rated operational current (AC-1)capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-latching auxilary contacts 1NO/1NC and damping resistors complete . |
| 46 | Supply only Type MO C20, 50A rated operational current (AC-1)capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-latching auxilary contacts 1NO/1NC and damping resistors complete . |
| 47 | Supply only Type MO C25, 50A rated operational current (AC-1) capacitor duty contactor, 3 phase, 415V, 50Hz, built in de-latching auxilary contacts 1NO/1NC and damping resistors complete. |
| 48 | S&F in repair APFC Controller for contactor switching with CT input, step 5 step having the feature of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. Make:- L&T, Legrand, siemens, Havells. |
| 49 | S&F in repair APFC Controller for contactor switching with CT input, 8 step (7+1) with the combination of 5 step APFC controller + 3 step plug in module of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. Make:- L&T, Legrand, siemens, Havells. |
| 50 | S&F in repair APFC Controller for contactor switching with CT input, 10 step (9+1) with the combination of 8 step APFC controller + 2 step plug in module.of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. Make:- L&T, Legrand, siemens, Havells. |
| 51 | S&F in repair APFC Controller for contactor switching with CT input, 10 step (9+1) with the combination of 12 step (11+1) with the combination of 8 step APFC controller + 2 step plug in module + 2 step plug in module.of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. Make:- L&T, Legrand, siemens, Havells. |
| 52 | S&F in repair single phase, current transformer, indoor, tape insulated, round type for measuring instrument having CT ratio as required at site according to the load or as directed by Engr-in-Charge. Make:-AE/ Kappa/Havells |
| 53 | S&F in repair Power Factor Correction capacitor heavy duty cylindrical series LTCCH type, gas filled, and rating 1 KVAR to 4 KVAR including internal connection complete all as directed. Make:- L&T or equivalent in Legrand, siemens, Havells. |
| 54 | S&F in repair Power Factor Correction capacitor heavy duty cylindrical series LTCCH type, gas filled, and rating 5 KVAR to 15 KVAR including internal connection complete all as directed. Make:- L&T or equivalent in Legrand, siemens, Havells. |
| 55 | S&F in repair Power Factor Correction capacitor heavy duty cylindrical series LTCCH type, gas filled, and rating 20 KVAR to 25 KVAR including internal connection complete all as directed. Make:- L&T or equivalent in Legrand, siemens, Havells. |
| 56 | S&F in repair dual source multifunction meter having Accuracy Class 1.0, 0.5, input voltage measurement range 50-520 VAC (P-P), Aux supply 80-300 VAC/DC, CT secondary site selectable 1A/5A, DG sensing input 230 VAC, Flush mounting 96 x 96 mm, CT/PT site programmable, parameters: V, A, F, PF, kW, kVA, Run hours, kWh (EB and DG), old energy, Site selectable kWh/kVAh complete all as directed. Make:- L&T, Legrand, siemens, Havells. |
| 57 | S&F in repair Bolted fuse link , type HG, HRC fuse of rating 2A including fuse base bolted type 20A complete all as specified and as directed. Make:- L&T, Legrand, siemens, Havells. |
| 58 | S&F in repair Bolted fuse link , type HG, HRC fuse of rating 2A including fuse base bolted type 32A complete all as specified and as directed. Make:- L&T, Legrand, siemens, Havells. |
| 59 | S&F in repair indicator lamp LED type (RYBG) complete all as specified and as directed. |
| 60 | Supply and fixing Push button (Red & Blue)complete all as specified and as directed. |
| 61 | S&F in repair 240V, 10KA 'C' curve miniature circuit breaker (MCB) of single poles (SP) and current carrying capacity 6 amp to 32 Amp with breaking capacity 10 KA ,in the MCB DB with connection testing and commissioning complete all as specified and as directed. Make:- L&T,Legrand, siemens, Havells. |
| 62 | S&F in repair 240V, 10KA 'C' curve miniature circuit breaker (MCB) of tripple poles (TP) and current carrying capacity 32 Amp with breaking capacity 10 KA ,in the MCB DB with connection testing and commissioning complete all as specified and as directed. Make:- L&T,Legrand, siemens, Havells. |
| 63 | S&F in repair 240V, 10KA 'C' curve miniature circuit breaker (MCB) of tripple poles (TP) and current carrying capacity 40 Amp to 63 Amps with breaking capacity 10 KA ,in the MCB DB with connection testing and commissioning complete all as specified and as directed. Make:- L&T,Legrand, siemens, Havells. |
| 64 | S&F in repair Fan and thermostat assembly having range of temperature 30-110°C,complete all as specified and as directed. Make:- L&T, Legrand, siemens, Havells. |
| 65 | M & L for repainting of APFC panel of different size using two coat of synthetic enamel spray painting after preparation of surface and carrying out minor repair to APFC panel enclosure by welding of hinges and replacement of locking arrangement and complete all as directed by Engineer-in-charge. |
| 66 | M & L for repair to battery by replacement of lead acid batteries each of 12 Volts, 150 AH complete connected in series suitable for invetors / UPS with battery complete all as directed by Engineer-in-charge. |
| 67 | M & L for Repair, maintenance, cleaning, servicing, and calabration of battery charger at main receiving station including replacement of faulty spares such as 220/110V AC transformer having current rating 5 Amps, PCB for main supply, PCB for float and boosting charging, variac variable transformer of suitable size, HRC fuses with fuse base, MCBs, indicator, voltmeter, ammeter etc. or any other spare required to made serviceable the battery charger complete all as specified and as directed.Note: Contractor may be visit the site before quoting the rate and work has to be completed upto entire satishfaction of Engr-in-Charge and not any claim at later stage on this account. |
| 68 | M & L for repair/ Servicing to Online UPS of rating 30 KVA Capacity suitable for 415 Volts, AC, 50 Hz, three phase complete of any make/type all as specified and directed including cleaning and segregation of serviceable and unserviceable components. |
| 69 | M&L for in replacement of Electronic sencing card (PCB) for Online UPS 30 KVA, 415 Volts, ac, 50 Hz, three phase complete as specified and directed |
| 70 | M & L for repair/ Servicing to Online UPS 12/15 KVA Capacity suitable for 415 Volts, ac, 50 Hz,Single phase complete as specified and directed |
| 71 | M&L for in replacement of Electronic sencing card (PCB) for Online UPS 12/15 KVA, 415 Volts, ac, 50 Hz, Single phase complete as specified and directed |
| 72 | Material & labour for replacement of laminated sheet board at installations, made out of 3.15 mm thick sheet steel box, PVC acrylic glow sign board with reflector night vision of size 3.0 m x1.0 m x.0.60 m, complete with fixing material i.e. hole fastner, long screw, nut, bolts, washer, MS chain, clamps etc of suitable size as per site requirement for completion of work ,including necessary PCC 1:2:4 ,type B-1(using 20 mm graded crushed stone aggregate), written with name of installation in proper size of letter as directed by Engineer-in charge or as per existing size and shape , testing complete all as specified and as directed.Note :- Colour of board and size of letter is to be approved by GE before making order by Contractor. |
| 73 | M&L for retro reflective installation sign board of size 1.20 m x 0.90 m made of 18 gauge thick stainless steel sheet framed with 25 mm dia stainless steel pipe having front side entire surface fully bonded with retro reflective sheeting of high intensity prismatic grade having pressure sensitive adhesive, background in blue colour and writing matter in white colour tape mentioning text to be provided by department including fixing arrangement with two post of 50 mm dia round stainless pipe(Grade 304) each 3.0 m long and erecting/embedded in PCC 1:3:6 ,type B-1(using 20 mm graded crushed stone aggregate) flush with GL after below 0.50 m below GL complete all as specified and directed |
| 74 | Material and Labour for Display boards made out of ABC Acrllic material of size 5'x3'x0.5 ' ( L B T ), containig blue back ground with white colour capital letters/symbols of 50 mm hights showing layout of Electric network of station. Details/layout as given by Engr in charge including fixing at wall of variour Power House along with fixing arrangement as list given by EIC complete all as specified and directed Note : Dispaly details/Drgs/of boards list shall be approved before finalise the printing at Engr - In Charge. |
| 75 | Taking Down Solar Lights by removing from existing position and refixing the same after replacement of unserviciable parts.All components/spares required to be replaced shall be measured and paid seperately under respective item of BOQ as 'Supply only' of item as detailed hereafter. |
| 76 | Supply and fixing in repair of Solar Charge Controller 10Amp with protection circuits for 24wattSolar Lights System: 12V NominalCapacity: 100Wp MaxRegulation: Low Loss, Shunt TypeOVD: Output Voltage Drop<200mV at 2.1A LoadIVD: Input Voltage Drop<330mV at 10A ChargeLVD: Low Voltage Disconnect, 10.8VHVD: High Voltage Disconnect,14.2VLVR: Low Voltage Reconnect, 12.3VHVR: High Voltage Reconnect, 14.15VBattery Charging Type: PWMShort Circuit and Overload at loadReverse polarity of battery and panelReverse current flow from battery to panel complete all as specified and directed |
| 77 | Supply only of PIR Motion Sensor 170uA for 24Watt Solar Light, Standard Detection 5m Lens complete all as specified and directed . Color : White, Movement speed : 1.0m/s. |
| 78 | Supply & Installation of Lithium Battery 11.1V/ 28.6Ah with BMS Circuit and other necessary wires and connectors suitable for 24watt Integrated Solar Lights Warranty 3 Years including taking out/ down unserviceable one, complete all as specified and directed |
| 79 | Supply & Installation of Rocker Switch 6Amp including taking out/ down unserviceable one, complete all as specified and directed |
| 80 | Supply & Installation of LED Lamp Cover including taking out/ down unserviceable one, complete all as specified and directed |
| 81 | Material & Labour for repairing of LED PCB Board of size 24watt including taking out/ down unserviceable one, complete all as specified and directed |
| 82 | Note:- (i) All items in BOQ are for \\"Materials and labour / Supply and fix\\" and to be executed in \\"Repairs/Replacement unless otherwise specifically mentioned as \\"Supply only\\" or Fixing only\\" in BOQ Bidders are required to quote their rates accordingly.(ii) The contract sum shall be arrived at after duducting amount of schedule of \\"Credit\\" from the Total quoted amount(iii) Makes of materials will be approved by GE in writing before commencement of work. Please Enable Macros to View BoQ information |