| 1 | UPS Installation |
| 2 | OD108082/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with 120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range : 160V -280V with cut off e) THD < 10% f) Overall Efficiency >.9 % g) Ambient Temperature : 0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j) LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge, Temperature, frequency q) Approved UPS make : APC/Delta/Numeric, r) Approved C10 rated battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied. |
| 3 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 4 | 90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture |
| 5 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)12 way, Double door |
| 6 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)8 way, Double door |
| 7 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 8 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 9 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 10 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 11 | OD180712/2025-2026:Supplying and fixing DP sheet steel enclosure on surface/ recess, complete with din bar powder painted etc. as required. |
| 12 | OD108090/2025-2026:Supply and fixing 32A, HRC Fuse with HRC Fuse link with connections, in existing meter board |
| 13 | OD108086/2025-2026:Supplying and fixing 32 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board |
| 14 | OD108083/2025-2026:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly , door interlock pad and locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary nuts&bolts, fixing the unit to wall, making good damages, colour washing etc. including giving necessary connections as required. 32Amp SP&N AC 23A with ISI marked HRC fuse |
| 15 | OD108085/2025-2026:Supply & installation of dust and vermin proof, 1 Phase Syntax Meter Board( GS-MB- 3525)and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making goodthe damages colour washing etc. as required. |
| 16 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 17 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 18 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 19 | 1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm |
| 20 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 21 | 1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 22 | 1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 23 | 1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm) |
| 24 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 25 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 26 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 27 | OD108084/2025-2026:Supply and providing test joint for the earthing system using 2 Nos of the following sizes ofstrips including cutting and bending to shape, drilling necessary holes and fixed to the wateringpipe etc as required. 2 x 25 x 3 mm GI strip |
| 28 | OD108088/2025-2026:Supply and providing earth lead from the test joint to the earth electrode using the followingsizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) andfixing firmly with plate test joint etc as required.25 mm X 3 mm G.I. strip |
| 29 | OD108091/2025-2026:Supplying and providing 25x3m brass nut and bolt etc as required |
| 30 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 31 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 32 | OD108089/2025-2026:Supply and fixing 32 mm dia 6Kgff/cm2 PVC pipe including fixing the pipe with clamp/clips at 60cm spacing. etc as required (For Service Pipe) |
| 33 | OD108080/2025-2026:Supply and providing suitable Iron Hook grouted on wall for binding the service wire Please Enable Macros to View BoQ information |