| 1 | Tender Inviting Authority: Superintending Engineer, Electricity 765/400 KV Substation Design Circle, U.P. Power Transmission Corporation Limited, 11th Floor, Shakti Bhawan Extension, 14-Ashok Marg, Lucknow-226001 SCHEDULE OF QUANTITIES & PRICES FOR SUPPLY OF SYSTEM PROTECTION SCHEME SCHEDULE-3 Tender Specification No. ESD-8/230 Name of Bidder : SUMMARY PRICE SCHEDULE SI. No. Description Amount (in Rs.) |
| 2 | Total Price for Supply of SPS [Schedule-I ](With GST) Date: Place: Signature Name: Designation: Tender Inviting Authority: Superintending Engineer, Electricity 765/400 KV Substation Design Circle, U.P. Power Transmission Corporation Limited, 11th Floor, Shakti Bhawan Extension, 14-Ashok Marg, Lucknow-226001 SCHEDULE OF QUANTITIES & PRICES FOR SUPPLY OF SYSTEM PROTECTION SCHEME SCHEDULE Tender Specification No. ESD-8/237 Name of Bidder Supply SPS for 400kV Sub-Station SR NO DESCRIPTION Units QTY for SPS to be installed at various 400kV S/s Total Qty Quoted unit prices in Rs. (exclusive of GST) Unit FORDestination prices Total FORDestination prices Jehta Shamli Sahupuri Ex. Works Packing & Forwarding Freight Transit & Insurance |
| 3 | System Protection schemes (SPS) wit all associated items. a For 400kV Jehta S/s ,System Protection Scheme(SPS) for ICT-1, and ICT-2(current based with over current relays)including all associated items, transducer, software etc.This also includes designing and engineering of SPS,manufacturing of SPS as per approved drawings, factory acceptance tests for SPS. No. 1.0 0.0 0.0 1.0 0.0 0.0 b For 400kV Shamli S/s ,System Protection Scheme(SPS) for ICT-1, and ICT-2(current based with over current relays)including all associated items, transducer, software etc.This also includes designing and engineering of SPS,manufacturing of SPS as per approved drawings, factory acceptance tests for SPS. No. 0.0 1.0 0.0 1.0 0.0 0.0 c For 400kV Sahupuri S/s ,System Protection Scheme(SPS) for ICT-1, and ICT-2(current based with over current relays)including all associated items, transducer, software etc.This also includes designing and engineering of SPS,manufacturing of SPS as per approved drawings, factory acceptance tests for SPS. No. 0.0 0.0 1.0 1.0 0.0 0.0 |
| 4 | Supply of FO cable Armoured ,SM 6 core |
| 5 | Supply of Media Converter switch RJ45 to optical. Product approvals EMI-CISP322, EN 55032, Temp. -40 to 85 degree centegrate (fanless) . |
| 6 | Patch cords of dufferent types, |
| 7 | 4-20 mA signat cable for Transducer output from C&R Panels of Line ICT-1 , ICT-2 & ICT-3 to SPS Controller .6 core stranded copper (0.5mm2) Armoured (shielded) |
| 8 | 4-20 mA signat cable for Transducer output from C&R Panels of Line ICT-1 , ICT-2 & ICT-3 to SPS Controller .3 core stranded copper (0.5mm2) Armoured (shielded) |
| 9 | Digital input cable to PLC for main breaker statuss o f ICT -1,2 220kV Hardoi road -I and II,Mallawan and 132kV Rahimabad,Bharawan,Mehtabbagh,Jehta-I & II(6 core 2.5 sqmm armoures control cable) |
| 10 | Digital input cable to PLC for main breaker statuss of ICT -1,2 220kV 220kV Badhai Kalan Ckt-I,II,220kV Deoband Ckt-I,II 220kV Nmauta,220kV Shamli,220kV Modipuram-I,II,132kV Thanabhawan,132kV Kaniyan,132kV Jasala(spare)(,132kV Budhana,132kV Kharad,132kV Spare Bay-3(5C*1.5 sqmm) armoured copper control cable) |
| 11 | Digital input cable to PLC for main breaker statuss of ICT -1,2 (5C*1.5 sqmm) armoured copper control cable) |
| 12 | Digital Output Cable from RTU Panel to CRP 6 core (2.5mm2) standard copper armoured cable |
| 13 | 220 VAC/VDC Power Supply Cable from 220 VDC source to RTU 3 Core 2.5mm2 standard copper armoured cable |
| 14 | Transducer CT Input (R,Y,B Phase) cable in C&R Panels & Feeders single core wire 2.5 mm2 amoured copper control cable |
| 15 | Transducer Power Supply Single core wire (1.5mm2) |
| 16 | Transducer Power Supply cable (2Cx2.5 mm2) armoured copper control cable |
| 17 | LAN Cable between RTU and Computer (CAT6) |
| 18 | Supply of 06 core outdoor armoured cable |
| 19 | Supply of HDPE Pipe, 40mm Dia |
| 20 | Supply of 6 Port LTU with fully populated |
| 21 | Fiber to Ethrnet Media Convertor |
| 22 | RTU Programming Software |
| 23 | SCADA Software with license and IPC grade computer of minimum configuration as Intel Xeon CPU 4core, 2.80 Ghz, 16 GB main memory, 1 TB SATA HDD, 19.5 inch colot TFT monitor, Key Board, Mouse, 2 Nos. 10/100/1000 mbps Ethernet port, USB Port, 600VA UPS, AC Power Extension Board, (Furniture supply under the scoper of contractor). |
| 24 | 3 Phase Multifunction Current Transducer 220VDC, 4-20mA Output, Class-0.2 as per IEC 60688, CTR- 5A, Auxillary Supply - 220 VDC. The device shall communicate with RTU and support THD measurement up to the 31st harmonic. |
| 25 | Microprocessor based Monitoring system on SPS Panel. |
| 26 | Supervision for Erection, Testing & Commising of SPS & associated items. 0.0 0.0 Total (withou GST) 0.0 GST @ 18% 0.0 Total with GST 0.0 Date: Signature Place: Name: Designation: * |