| 1 | Pollution Control Unit |
| 2 | Supply & delivery at site, installation, testing and commissioning of M.S. Self supported chimney of 30 Mtr. Length having PCD :- 1425mm, bottom dia:- 1250mm & 8 mm thick on existing R.C.C foundation, top dia:- 600mm & 5 mm thick FDN bolt- M36 ( RCC foundation is within the scope of work of the civil department & RCC foundation height should not be less than 600mm from actual GL), M.S. ladder, inspection door, operating platform, aviation lamp, lightning arrestor etc. complete. |
| 3 | Supply, delivery at site. Installation, testing of S.S. (Grade-304) Fabricated Ventury Scrubber having 2Mtr height, dia not less than 700mm, 2.5 mm thick & Packed wet scrubber having width 900mm, 2.5mm thick with specially design brass made nozzle, fume discharge 1800 cu.m per hour dialing with interconnection SS pipe of 300mm, 1.5 inch water pipe line & outlet pipe line having dia 75mm to 80mm with pressure release valve accessories complete and S&F of AISI SS-304(2.5 mm thick )piping interconnection between scrubber to mist eleminator as required including foundation as per technical specification. |
| 4 | Supply, delivery at site, installation, Testing of S.S. (Grade-304) 2.5 mm thickness fabricated dropler separator/Mist eliminator with all accessories Complete incl suitable foundation (L X B X H) at a height of not less than 600mm from GL as per technical specification. |
| 5 | Supply and delivery at site, installation, testing and commissioning of Squirell cage Inuction motor not less than rating of 415V 7.5/10 (KW/HP) Centrifugal for Induced draught air fan having capacity not less than 2200 CFM, impeller SS 316, rpm 2800 along with S&F of suitable dia & length of SS 304 duct line interconnection between delivery of ID fan & chimney body inel cutting of suitable diemension of chimney body for inertion of duct along with suitable rain protecting hood for ID fan complete including suitable foundation (L X B X H as desired by EIC depending upon site condition) at a height of not less than 600mm from GL as per technical specification. |
| 6 | Supply, erection of SS (Grade 304) duct line (300mm) having 2.5 mm tickness de length not less than 6 mtr. complete with bend, and making wall support for the same along with Manual Damper control arrangement and connection with ceramic brick lime. |
| 7 | Supply, delivery at site, installation, testing and commissioning of Recirculation water pump not less than rating of 415V, 1.5/2 (KW/HP) having head 18 to 30 mtr., & capable to discharge water at least 15 LPS of accumulated water containing suspended solids up to dra 15mm to 20mm, impeller Cl, degree of protection IP-866 wuh suitable rain protecting hood complete elincluding all suitable foundation (LXBXH) and height along with necessary pipe line and accessories, incl S&F of DOL starter arrangement nearer to pollution control unit along with necessary pipe line connection (1.0 inch to 2.0 inch) from slurry tank to pump & pump to individual scrubber units & Scrubber unit to Slurry tank. |
| 8 | Supply & delivery at site, installation, testing and commissioning of Electrical control panel for pollution control unit as per technical specification. 160A Incoming Feeder I no Outgoing Feeders A 10HP S/D Feeder 1 no. (ID Fan) & its accessories Outgoing 7 Feeders-B 3.0 HP DOL Feeder 1 no. (Re-Circulation) Outgoing Feeders C Aviation Lighting Feeder 1 no (Aviation Lighting) & 1 spares feeder unit incl. space heater arrangement with all accessories. |
| 9 | Supply & delivery at site, installation, testing and commissioning of Electrical control console panel for housing and interconnected with the following Components as per technical specification. i)Heater I & II Start/Stop Push button 4 nos.ii)Heater I & II On/Off Indicating Lamps, 240V AC 4 nosiii) ID. Fan/FD Fan Start/Stop Push button 4 nos.iv) ID Fan/FD Fan On/Off Indicating Lamps, 240V AC 4 nosv) scrubber pump start/stopvi) Door open/close |
| 10 | Design & Construction of underground storage reservoir and recirculation multistage shurry water tank having capacity not less than 17 M3 with necessary soak pit arrangement of adequate capacity and protected M.S structure consisting of (25-30) mm x6 mm MS. angle/flat, wire mesh netting to cover the top of slurry tank & construction of requisite capacity of soak pit and other necessary materials pipe 3 inch to 4 inch for draining the waste water to soak pit as required. |
| 11 | Furnace |
| 12 | Suppls, erection, testing and commissioning of main control panel for furnace including group controlling arrangement as per technical specification 250A Incoming Feeder 1 no Outgoing Feeders A 27KW Heater Control Power Feeder 3 nos B. Outgoing Feeders -B13 HP DOL Feeder 1 no. (FD Fan) incl. space heater arrangements. |
| 13 | Supply crection, testing of Body Charging Trolley (Max load upto 150 kg) along with guide rail arrangement for coffin charging trolley including carraige as per design & direction of EIC. |
| 14 | Supply, erection testing and commissioning of Mechanism for door lifting arrangement with Door (Both hand & Motor Operated).with S.S. rod, Grade -310, Ceramic fiber Blanket, 128 density 1400 degree C temperature carrying capacity including S&F of chain(3/4\\" 2.4 M) for counter weight and door lifting arrangement and S&F of bearing for handle complete. |
| 15 | Supply, fitting, fixing of heating elements (coils), 4.5 KW each, shall be made of 80/20 nickel chromium wire, 9 SWG & resistivity shall be 108 micro ohms at 20 degree C in addition 10 mm dia SS rod AISI-304 shall be provided along with brush connector (Coil connecting elements). Thermocouple and Compensating cables including connection between thermocouple and temperature controller card incl testing, necessary Ceramic Blanket shall be provided wherever necessary. |
| 16 | Development of R.C.C. Structure for the furnace bed incl. supplying of all raw materials as per requirement for proper alignment of furnace. |
| 17 | Supply and delivery at site, installation, testing and commissioning of 3 Ø, 415V, 50Hz. Induction Motor of rating not less than 0.75/1 (kW/HP) for Fresh air injection system including Forced draft Fan, Mild steel ducting, butterfly valve etc. complete. |
| 18 | Supply, erection testing and commissioning of Mild Steel structural work having thickness not less than 3mm for Furnace chamber including charge door, ash door as per design, drawing & direction of EIC. |
| 19 | Supply, erection, testing and commissioning of a furnace by using all shorts of Insulations, refractoriness like Heavy duty Fired bricks, Rose bricks & other necessary items etc. as per IS-08 as suitable for furnace ready. |
| 20 | Main L.T. Panel, Cables, wiring and accessories |
| 21 | Supply, delivery at site of 1.1 KV grade XLPE insulated PVC outer sheathed armoured copper/ aliminium conductor cable of following size as required and as per technical specification. |
| 22 | a) 3 ½ core X 120 mm2. (Al.) |
| 23 | b) 4 core X 95 mm2. (Al.) |
| 24 | c) 3 core X 50 mm2. (Al.) |
| 25 | d) 4 core X 16 mm2. (Al.) |
| 26 | e) 4 core X 10 mm2. (Al.) |
| 27 | f) 3 Core X 2.5 mm2 Flat Cu. Flexible Cable. |
| 28 | g) 12 core X 2.5 mm2 Control Cable.(Cu.) |
| 29 | Supply, delivery at site of 1.1 KV grade single core Un-armoured copper conductor of size 16 mm2 power cable for heater connection. |
| 30 | Supply & Fixing of perforated Gl cable tray with perforation not more than 17. 5% suspended from ceiling anel S&F Gl connector, 6mm dia MS suspender, bolts & nuts, steel fastener ete as required of the following size. Incl. Al painting of MS support, With 25x25x3mm angle iron support. |
| 31 | a) 300x50xl 25mm (18SWG) |
| 32 | Supply & Fixing of perforated GI cable tray hend with perforation not more than 17.5% suspended from ceiling with two nos suspenders & 25x25x3 mm angle iron for supporting the cross member mel S&F Gl connector, 6mm dia MS suspender, bolts && nuts, steel fastener ete as required of the following size. Inel. Al painting of MS support. |
| 33 | a) 300x50x1.25mm (18SWG) |
| 34 | Supply & Fixing of perforated Gl cable tray tee with perforation not more than 17.5% suspended from ceiling with two nos suspendersa 25x25x3 mm angle iron for supporting the criss member incl. S&F Gl connector, 6 mm dia MS suspender, bolts& nuts, steel fastener etc, as required of the following size Inel Al painting of MS support. |
| 35 | a) 250x50x1.25mm (18SWG) |
| 36 | Laying of cable as below, on existing Cable Tray and binding with suitable size Gl wire |
| 37 | a) From 70mm2 to 150mm2 |
| 38 | b) Upto 50 mm2 |
| 39 | Laying of one No cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre,including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. |
| 40 | Laving of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy mending good damages and painting. |
| 41 | Laying only Cable upto 50 sqmm through existing RCC/Hume/Gl Pipe/open masonary trench for single, 2, 3, 3½ & 4 core. |
| 42 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below: |
| 43 | a) 3 ½ core X 120 mm2. (Al.) |
| 44 | b) 4 core X 95 mm2. (Al.) |
| 45 | c) 3 core X 50 mm2. (Al.) |
| 46 | d) 4 core X 16 mm2. (Al.) |
| 47 | e) 4 core X 10 mm2. (Al.) |
| 48 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials. |
| 49 | a) 3 ½ core X 120 mm2. (Al.) |
| 50 | b) 4 core X 95 mm2. (Al.) |
| 51 | c) 3 core X 50 mm2. (Al.) |
| 52 | d) 4 core X 16 mm2. (Al.) |
| 53 | e) 4 core X 10 mm2. (Al.) |
| 54 | f) 2.5 mm2. 3 Core Flat Cu. Flexible Cable. |
| 55 | g) 12 core X 2.5 mm2 Control Cable.(Cu.) |
| 56 | Supply, installation, testing and commissioning of floor Mounting, self supporting Industrial cublical pattern, dust & vermin proof,IP 54, generally conforming to IP 54 degree of protection indoor duty, industrial type LT PDB made of 2mm thick CRCA sheet steel, painted with powder coating finish paint with 1 no. 400A TP+N MCCB (16KA) with Microprocessor based with O/L, S/C release, with indication and metering as Inesmer feeder and outgoing feeders are 03 nos 250A TP MCCB (25KA) with Thermo Magnetic based O/L, S/C release Spreaders & Extended Rotary Handle with Aux+Trip Contact with medication and metering, 2 no 160A Power Feeder 1 no each (For Pollution Control Panel) comprising 100A ТР МССВ (25KA) with Thermo-Magnetic based O/L, S/C release Spreaders with indication and metering, 63A/32A Power Feeder 3 nos ( For Lighting & Misc. Use) each comprising 63A /32A 4P MCB with indication as out going and 10 KVAR APFC panel as per technical specification. Approx dimension (W-1100 X H 1600 X D-500 mm).Busbar suitable for 400Ampl/C |
| 57 | Supply of TMC 501 Conventional Industrial Batten Philips LED Tube, model no: TMC 501 P 2×T-LED 22W P3242 with 2 nos. Mas LED tube 1200mm 18W865 T8 I- 2100 lm including necessary connection. |
| 58 | Fixing only single /twin fluorescent light fitting complete with allaccessories directly on wall/ceiling/HW round block and suitable size of MS fastener. |
| 59 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single corestranded 'FR' PVC insulated & unsheathed copper wire(Brand approved by EIC) in 20mm size PVC rigid conduit 'FR'(Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3mm thick and incl. 175mmx100mmx65mm inspection box,making earthing attachment, painting the MS box and mending good the damages to original finish |
| 60 | a) Average run 6 mtr |
| 61 | a) Average run 8 mtr |
| 62 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish. |
| 63 | a) On Board |
| 64 | b) Avg. Run 4.5 Mtr. |
| 65 | Supply and fixing 415 V, 6 - 32 A per way, TPN MCBDB with SS enclosure double door with IP-42/43 protection with four Pole isolators as incomer and SPMCBs ('C Curve, 10 kA) as out going, concealed in wall after cutting the wall and mending good the damages to original ifnish incl inter connection with suitable size of copper wire and neutral link & provision earthing attachment. (Legrand / Seimens) 4 Way Enclosure (607715), 63A FP Isolator, 6 no. DPMCB. |
| 66 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (2+8way) complete with Ino.-40A DP MCB & 08 nos. (6-32)A SP MCB. |
| 67 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. |
| 68 | a) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 69 | b) 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC |
| 70 | Supply & Fixing 240 V, 4 nos. 6A, plug socket with separate 4 nos. 6 A Piano key type switch, indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mmthick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 71 | S&F 250V AC 1200 mm sweep ceiling fan high speed 1 star, air delivery 225 CMM, power i/p-55W, speed 380 rpm, blade Aluminium (1.02mm), capacotor -1.7MFD, Down rod 265mm, safety wire 650mm & regulator complete with blades, Step type electronic regulator, canopy, fork, rubber bush etc. inel. S & F 2 X 1.40 PVC wire for down rod upto 30 cm. incl. painting the rod with approved paint and making necessary connection as required as per specification & direction of EIC (make-Usha or Crompton, havells or equivalent) |
| 72 | Supply, delivery and fixing of 450mm Heavy duty 1400 RPM 230V Exhaust fan with Air delivery-6120 CMH. 300 mm Gl sheet (20SWG) metal Cowl on wall with necessary bolts de nuts as per direction of EIC (6 mm dia 62 mm long )as per specification & direction of EIC (make Usha or Crompton, havells or equivalent) |
| 73 | Supply and fixing of smart bright essential street light (70 Watt) complete with all accessories to be fixed/ projected from the wall of the building or on pole incl. making holes/ providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe(ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. lenght of 1.5 sqmm. PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. |
| 74 | a) Make: Philips, 68 watt |
| 75 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts.long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm diax 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: |
| 76 | By TATA-Medium GI pipe |
| 77 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 78 | a) MS flat 50 mm X 6mm |
| 79 | b) MS flat 25 mm X 6mm |
| 80 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages |
| 81 | a) No. 8 SWG Solid G I Wire |
| 82 | Portable Fire Extinguisher |
| 83 | Supply, delivery, fitting, fixing of 6 Kg. capacity (ABC type) fire extinguisher complete in all respect i.e. with first change of refill, mounting bracket etc. as per direrction of EIC. |
| 84 | Supply, delivery, fitting, fixing of 4.5 Kg capacity with ISI marked Co2 type fire extinguisher squeeze grip type conforming to IS:15683:2006 made from seamless cylinder conforming to IS:7285 duly approved by Chief controller of explosive, Nagpur, fitted with ISI marked controller of explosive, Nagpur, fittet with ISI marked controlled valve conforming to IS:3224, high pressure 1 mtr. long discharge hose and horn complete with initial gas charged with carrying handle and wall mounting bracket suitable for operating between (-)30ºC to (+)55ºC. Fire rating -13B. |
| 85 | General |
| 86 | Supply, installation and commissioning of LED Signage on ACP panel boardof size 10'x5' with all necessary connections and earthing attachment as per direction of EIC. |
| 87 | Painting of the whole installation incl. scaffolding arrangements if necy. |
| 88 | Commissioning and trial run of the cremation furnace including all other units of pollution control unit as per direction of EIC. |
| 89 | Operation and maintenance of all the equipments described above incl. other accessories for a period of 6 months except the responsibility of security guard and maintenance of register. |
| 90 | Spares for smooth operation |
| 91 | heating elements (coils) |
| 92 | Roast Bricks. |
| 93 | Fuses. |
| 94 | Thermocouple |
| 95 | Obtaining necessary NOC from WBPCB for the whole system |
| 96 | Installation of Pump Motor Set |
| 97 | Supply, delivery, installation, testing and commissioning of 2HP, 3 Phase, 2840 RPM, 415V Submersible Pump-Motor set having Discharge capacity 24.5 CMPH at a Head of 13 to 25 M complete as per direction of EIC. along with Power & Control cable, impeller CF8M, Make: KSB Equivalent Model of reputed manufacturer also with G.I. pipes of TATA make with all necessary accessories, specials viz, socket, bend, tee, union, cross, elbo, nipple, longserew, redneling socket, reducing tee, short piece ete. fitted with holder bats clamps, including cutting pipes, making threads, fitting, fixing etc. complete in all respect including cost of all necessary fittings as required jointing materials and two coats of painting with approved paint & also S&F of the following G.I.fittings including G.I.Pipe, G.M. Wheel Valve, G.M. Peet's Valve, G.I. Tee, (ISI mark), G.I. short piece of length 1 mtr. (ISI mark), G.I. Bend (ISI mark), G.I. flanged, M.S. Well Cover duly 2\\" Socket welded, Enlarger, G.I. Nipple, Suspension Clamp, G.I.reducing socket, G.I.Socket, G.I. Union, G.M. vertical Check Valve, G.M. Wheel Valve, N.R.V. etc. as required as per direction of the EIC. |
| 98 | Outdoor Illumination Work |
| 99 | Supplying & Erection of Small size feeder pillar boy of Size (900 mm x 600 mm x 450 mm) made up of 2 mm thick MS Plate alongwith suitable MS. Angle The P.B. have double hinge door at the front & back with suitable locking arrangement. The box will he painted by 2 coats of aluminiam paint over 1 coat of red oxide paint. Suitable arrangement should be provided incl. Supply & fixing of Contractor Unit MNX 70, Timer unit, S&F 100A Re wireable kat kat & 63A rewireable Kit Kat, S&F Terminal Block 3 way & 2 Nos Earthing of Pillar Box with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long. Leg of the pillar box will be 900 mm in length by made up of 35 x 35 x 3 mm MS Angle with suitable base Plate. Legs of the Pillar box will be erected at 300 mm below the ground level with cement concrete (6:3:1). Rest portion covered by 5'' Brick Wall with plastering & net cement & bottom portion filled with silver sand as drawing & direction of EIC. |
| 100 | Supplying of Swaged Steel Tubular pole (IS 2713, Pt. II 1980) for following designation and of following dimensions |
| 101 | a) 410-SP-33; 9.0mtrs: 164 Kg |
| 102 | Erection of single steel tubular pole up to 9m including MS sole plate (25 m dia 6 m thick) cap etc over flyover bridge ete with CC foundation (4:3:1) with graded stone chip (3/4\\" down) surrounding the pole base 2\\" 2' up to a height of 1.35 m (4.1/2\\") from the pole base with 2 coats of black paint and then fixing the pole by means of 3 nos 4 11/24 clamps to the fencing of the bridge at a suitable distance and providing the passage of wire/cable leading through hard polythene pipe (1.1/2\\") and also ebonite sheet 4-way ebonite terminal connector block including connection with lug by crimping arrangement and also neat cementing of pole base and finishing. |
| 103 | Supply & Delivery of 1100 volt Grade PVC/XLPE insulated armoured aluminium conductor cables of following sizes |
| 104 | a) 4 core X 10 mm2 |
| 105 | Supply fitting and fixing of 40 mm dia High Density Poly ethylene Pipe conforming to IS: 4984-1985 for under ground work including cost of Jointing materials paints ere fitting and fixing all necessary specials, cutting pipes, making threads, cutting holes in walls, it necessary, including the cost and fitting and fixing holder bat clamps(any floor) or for underground work including cutting trenches and refilling the same complete as per direction of the Engineer in charge. |
| 106 | Laying only Cable upto 50 sqmm through existing RCC/Hume/Gl Pipe/open masonary trench for single, 2, 3, 3½ & 4 core. |
| 107 | Supplying & fixing medium gauge 40 mm dia GI Pipe ( ISI- Medium) Protection with necessary fittings and jointing metarials as required. |
| 108 | S/F of special head type MS loop box (3 mm thick) with connecting bar and other accessories fixed on the top the poleas required and as per direction of Engineer-In-Charge For 3 phase connection. |
| 109 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below: |
| 110 | a) 4 core X 10 mm2 |
| 111 | Supplying cable socket(lug) and making core termination including soldering/crimping etc. suitable for the following PVC insulated AL/CU conductor as required including making connection (cable socket made of aluminium) |
| 112 | a) 4 core X 10 mm2 |
| 113 | Supply and wiring in 3 x 22/0.3 (1.5 sqmm) Cu. conductor single core PVC insulated 250V grade wire from cable termination block to luminaires with earthing attachment Gl wire including making necessary connection complete as per direction of the EIC. |
| 114 | Excavation of soil and Earthing with 50 mm dia Gl pipe 3.64 mm thick x 3.04 Mts long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long Gl bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mtrs. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level. |
| 115 | Add G.S.T. @ 18% on Total Amount over item no 1.00 to 114.00 |
| 116 | Add Cess @1% on Total Amount over item no 1.00 to 114.00 Please Enable Macros to View BoQ information |