| 1 | Improvement /Revamping of 33/11kv - (3x10 MVA) Receiving Station Reasi Trintha |
| 2 | Laying of Compound boundary wall of out door switch yard by way of mass concrete in foundation and brick work of reqd. height |
| 3 | Face lifting / Repair work /Roof Treatment of existing control room building and SBA Room along with painting /replacement of Broken doors and window / window panes/Electric fitting along with replacement of old power point with modular switches ,sockets and MCB'S . |
| 4 | Extension of existing control room building /Battery Room / SBA Room along with construction of new washroom with septic tank/Sanitary works/plumbing complete job |
| 5 | 33KV Lightening Arrestors(33 KV 10 KA Polymer, ZnO, Gapless) |
| 6 | LT Cable 3.5 Core 95 mmsq |
| 7 | Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories at receving station Dharmari . |
| 8 | Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A),Rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories at receving station Dharmari . |
| 9 | 11Kv Gapless surge arrestor 9kv , 10KA,LA with polymer housing station type . |
| 10 | Earthing with 600mm*600mm GI plate , GI Flat 50*6mm, GI pipe ,40mm dia with charcoal salt and good earth 10 feet deep pit etc as per REC Standard complete3 job. of Switch Yard and control Room |
| 11 | 33 KV isolator with earthing blade ( 36KV,1250A, Outdoor 3Pole ,25KA along with Fabrication laying MS steel as per REC Standard |
| 12 | RainCoats |
| 13 | Digital Meggar 5000 mega Ohm |
| 14 | Multimeter |
| 15 | Table |
| 16 | Ceiling Fans |
| 17 | Exaust Fans for control room |
| 18 | Tool Kit/ Crimping Tool Kit (various sorts) |
| 19 | Fire Extinguisher |
| 20 | Extendable Aluminium Ladder 25 feet |
| 21 | Survey, Supply, Installation , Testing and Commissioning for 33 kV Line BAY (LILO) of existing Dadua Line at Receiving Station Pouni |
| 22 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Crompton Greaves, Electricfield or Equvalent . |
| 23 | 33kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 24 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 25 | 33 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase |
| 26 | 30 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less |
| 27 | 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 28 | 33 KV voltage transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase |
| 29 | 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m station type |
| 30 | CONTROL CABLES : i) 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. a |
| 31 | ii) 4 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 32 | iii) 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 33 | Galvanised Pipe/ Steel Structures |
| 34 | Galvanised Nuts & Bolts |
| 35 | 33 KV yard concreting and metalling providing supply and laying 100 mm thick PCC1:4:8 using 20 mm normal course aggregating and spreading 100 mm three layer of 20 mm single size crushed / broken stone (One Line Bay) |
| 36 | Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay) |
| 37 | Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat. |
| 38 | Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering |
| 39 | Survey, Supply, Installation , Testing and Commissioning for Erection of 33 kV Alternate Line On 11 METER ST Poles (20 ckt KM approx) |
| 40 | Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 41 | GI Channel iron X-arm of different sizes including clamps,Ties and braces for multi pole structures |
| 42 | GI Channel iron V cross-arm with top bracket of different sizes including clamps,Ties and braces for single pole structures |
| 43 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 44 | 33kV Polymeric composite Disc Insulator with fitting 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 45 | PG clamps for 150 mm2 ACSR Conductor |
| 46 | FI Ties |
| 47 | Galvinized Nuts and Bolts |
| 48 | Danger Plates with Clamps |
| 49 | Anti-Climbing Device with Clamps |
| 50 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 51 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 52 | Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) including 5 No existing Poles |
| 53 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 54 | 150 mm2 ACSR conductor |
| 55 | Guard netting |
| 56 | Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job. |
| 57 | Survey, Supply, Installation , Testing and Commissioning for Erection of Overhead 33 kV Line on Single Core 240 mm sq. Armoured XLPE Cable ON 11 Meter ST Pole |
| 58 | SITC for Laying of Overhead 33 kV Line on Single Core 240 mm sq. Armoured XLPE Cable ON 11 Meter ST Pole including GI clamps /Hooks/cable cleats and other hardware items for laying of overhead cable as required with 1 spare cable/(1.75*4) |
| 59 | Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc for laying of overhead cables. |
| 60 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 61 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 62 | Straight through Joints for Cables |
| 63 | Cable termination kits ( indoor /outdoor) |
| 64 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 65 | Creation of Isolation points along the line by way of 33 KV Isolators with earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job. |
| 66 | Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) including 5 No existing Poles Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0 |