| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of pipe, cable etc. and getting out in soft/loose soil, complete all as specified and/or as directed by Engr-in-Charge. |
| 2 | Returning, filling in including spreading leveling watering and well ramming in layers not exc. 25 cm thick, complete all as specified and/or as directed by Engr-in-Charge. |
| 3 | Removing surplus soil to a distance not exc. 50M and depositing where directed at a level not exceeding 1.5 Mtr above the starting point, complete all as specified and/or as directed by Engr-in-Charge. |
| 4 | Material and labour for Sand cushioning to under ground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I, 2009. complete all as specified and/or as directed by Engr-in-Charge. Note : Punned thickness only will be measured and paid. |
| 5 | Supply and laying of factory made, machine pressed, unreinforced, precast concrete cable cover class LV type-1 flat size 250 mm x 150 mm x 50mm, complete all as specified and/or as directed by Engr-in-Charge. |
| 6 | Dismantling steel tubular pole, complete all as specified and/or as directed by Engr-in-Charge. |
| 7 | M&L for steel tubular swaged poles type 410 SP-31 (9mtr long) complete with cast iron base plate, finial taper plug, bolts, nuts & screws including two coats of aluminium paint over one coat of red oxide zinc chrome primer including portion above coping shall be painted in alternative bands of black and yellow colour starting with yellow colour (each band of 20 cm wide) by two coats of super enamelled paint upto 1.5m height, complete in all respect conforming to IS-2713, complete all as specified and/or as directed by Engr-in-Charge. Note : Excavation and earthwork, cement concrete etc. will be measured and paid separately under relevant items of this schedule) |
| 8 | M&L in replacement of stay assembly complete with stay plate bow, stay rod of dia 20 mm and galvanised iron stay wire stranded of size 7/4mm and accessories as shown in electrical plate No 1 of SSR part-I (loop type insulator, stay clamps, excavation and concrete shall be measured separately), complete all as specified and/or as directed by Engr-in-Charge. |
| 9 | Dismantling of ACSR or AAC conductors, complete all as specified and/or as directed by Engr-in-Charge. |
| 10 | M&L for supply and installation, overhead, aluminium conductor, steel reinforced, weasel, including making connections and fixing on poles with all necessary arrangements, complete all as specified and/or as directed by Engr-in-Charge. Note: Weight of ACSR or all aluminium conductors drawn for overhead lines is to be determined by measuring taut horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers, etc. |
| 11 | Re-Straining & tightening of existing ACSR conductor of any size on LT/HT poles including necessary aluminium binding wire, connectors, PVC sleeves for jumpers etc., complete all as specified and/or as directed by Engr-in-Charge. |
| 12 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use within 50m, complete all as specified and/or as directed by Engr-in-Charge. |
| 13 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and/or as directed by Engr-in-Charge. |
| 14 | M&L for pin type, porcelain, vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanized iron washer and one galvanised iron nut, working pressure 1100 Volts and of size 65 mm dia and 100 mm height ISI marked, complete all as specified and/or as directed by Engr-in-Charge. |
| 15 | M&L for shackle type, porcelain, vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanized iron washer and one galvanised iron nut, working pressure 1100 Volts and of size 115 mm dia and 100 mm height ISI marked, complete all as specified and/or as directed by Engr-in-Charge. |
| 16 | M&L for plain cement concrete as in foundation, filling and mass concrete around poles etc., 1:4:8 type D-2 using 40mm graded crushed stone aggregate, complete all as specified and/or as directed by Engr-in-Charge. |
| 17 | M&L for PCC (1:3:6) type C-1 with 20mm graded crushed stone aggregate for copping of poles pedestal or mass filling (CM 1:4) including necessary formwork, complete all as specified and/or as directed by Engr-in-Charge. |
| 18 | Supply and laying in replacement of XLPE insulated, armoured, heavy duty electric cables with stranded aluminium conductor rating 1100 volts grade of under mentioned sizes :- |
| 19 | 400 sqmm 3.5 core |
| 20 | 300 sqmm 3.5 core |
| 21 | 185 sqmm 3.5 core |
| 22 | 150 sqmm 3.5 core |
| 23 | 95 sqmm 3.5 core |
| 24 | 70 sqmm 3.5 core |
| 25 | 50 sqmm 3.5 core |
| 26 | 35 sqmm 3.5 core |
| 27 | 25 sqmm 3.5 core |
| 28 | 16 sqmm 4 core |
| 29 | 10 sqmm 2 core |
| 30 | M&L in replacement of GI Pipe light grade for cable protecton in road crossing and making good surface road to filling with PCC (1:2:4) type B-1 of size 80 mm dia, complete all as specified and/or as directed by Engr-in-Charge. |
| 31 | All as per Srl Item No 19.00 above but of size 50 mm bore. |
| 32 | All as per Srl Item No 19.00 above but of size 40 mm bore. |
| 33 | Supply, installation, testing and commissioning in replacement of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54, CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 600 Amp rating capacity, Three Phase and 400 Amp for Neutral with minimum clearance 75 mm, all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points inside panel for housing the following accessories :-(i) MCCB 4 pole 400 Amp 36 KA, Make : L&T, Cat No CM98403OOROOG - 02 Nos. (ii) Change over switch 250 Amp capacity, Make : L&T, Cat No CO32500OOOO - 01 No.(iii) MCCB 4 pole 200 Amp 25 KA, Make : L&T, Cat No CM90642OOPO - 01 No.(iv) MCCB 4 pole 100 Amp 25 KA, Make : L&T, Cat No CM90642OOLO - 01 No.(v) MCCB 4 pole 63 Amp 25 KA, Make : L&T, Cat No CM91712OOHOOG - 02 Nos.(vi) LED Voltmeter, Make : L&T, Cat No WL132010OOOO(vii) LED Ammeter, Make : L&T, Cat No WL131010OOOO(viii) Voltmeter Selector Switch, Make : L&T, Cat No 61313 SAB13TDYR(ix) Ammeter Selector Switch, Make : L&T, Cat No 61325 SAB13TDYR(x) CT 200/5, 5VA, Matrix tape wound ring type bar primary(xi) LED Indicating lamps Red/ Yellow, Make : L&T(xii) LED Indicating lamps Blue, Make : L&T(xiii) MCB SPN 20A, 10 KA, 'C' curve, Make : L & T, Cat No : AU10S20203C - 01 No. |
| 34 | Supply, installation, testing and commissioning in replacement of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54, CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 600 Amp rating capacity, Three Phase and 300 Amp for Neutral with minimum clearance 75 mm, all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points inside panel for housing the following accessories :-(i) MCCB 4 pole 350 Amp 36 KA, Make : L&T, Cat No CM98403OOROOG - 01 No. (ii) MCCB 4 pole 100 Amp 25 KA, Make : L&T, Cat No CM90642OOLO - 01 No.(iii) MCCB 4 pole 63 Amp 25 KA, Make : L&T, Cat No CM91712OOHOOG - 04 Nos.(iv) LED Voltmeter, Make : L&T, Cat No WL132010OOOO - 01 No.(v) LED Ammeter, Make : L&T, Cat No WL131010OOOO - 01 No.(vi) Voltmeter Selector Switch, Make : L&T, Cat No 61313 SAB13TDYR - 01 No.(vii) Ammeter Selector Switch, Make : L&T, Cat No 61325 SAB13TDYR - 01 No.(viii) CT 250/5, 5VA, Matrix tape wound ring type bar primary(ix) LED Indicating lamps Red/ Yellow, Make : L&T(x) LED Indicating lamps Blue, Make : L&T(xi) MCB SPN 20A, 10 KA, 'C' curve, Make : L & T, Cat No : AU10S20203C - 01 No. |
| 35 | Supply, installation, testing and commissioning in replacement of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54, CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 400 Amp rating capacity, Three Phase and 200 Amp for Neutral with minimum clearance 75 mm, all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points inside panel for housing the following accessories :-(i) MCCB 4 pole 200 Amp 36 KA, Make : L&T, Cat No CM98403OOROOG - 01 No. (ii) MCCB 4 pole 100 Amp 25 KA, Make : L&T, Cat No CM90642OOLO - 01 No.(iii) MCCB 4 pole 63 Amp 25 KA, Make : L&T, Cat No CM91712OOHOOG - 03 Nos.(iv) LED Voltmeter, Make : L&T, Cat No WL132010OOOO - 01 No.(v) LED Ammeter, Make : L&T, Cat No WL131010OOOO - 01 No.(vi) Voltmeter Selector Switch, Make : L&T, Cat No 61313 SAB13TDYR - 01 No.(vii) Ammeter Selector Switch, Make : L&T, Cat No 61325 SAB13TDYR - 01 No.(viii) CT 250/5, 5VA, Matrix tape wound ring type bar primary(ix) LED Indicating lamps Red/ Yellow, Make : L&T(x) LED Indicating lamps Blue, Make : L&T(xi) MCB SPN 20A, 10 KA, 'C' curve, Make : L & T, Cat No : AU10S20203C - 01 No. |
| 36 | Supply, installation, testing and commissioning in replacement of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54, CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 800 Amp rating capacity, Three Phase and 400 Amp for Neutral with minimum clearance 75 mm, all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points inside panel for housing the following accessories :-(i) MCCB 4 pole 400 Amp 36 KA, Make : L&T, Cat No CM98403OOROOG - 01 No. (ii) Change over switch 250 Amp capacity, Make : L&T, Cat No CO32500OOOO - 01 No.(iii) MCCB 4 pole 100 Amp 25 KA, Make : L&T, Cat No CM90642OOPO - 01 No.(iv) MCCB 4 pole 63 Amp 25 KA, Make : L&T, Cat No CM91712OOHOOG - 01 No.(v) LED Voltmeter, Make : L&T, Cat No WL132010OOOO(vi) LED Ammeter, Make : L&T, Cat No WL131010OOOO(vii) Voltmeter Selector Switch, Make : L&T, Cat No 61313 SAB13TDYRviii) Ammeter Selector Switch, Make : L&T, Cat No 61325 SAB13TDYR(ix) CT 200/5, 5VA, Matrix tape wound ring type bar primary(x) LED Indicating lamps Red/ Yellow, Make : L&T(xi) LED Indicating lamps Blue, Make : L&T(xii) MCB SPN 20A, 10 KA, 'C' curve, Make : L & T, Cat No : AU10S20203C - 01 No. |
| 37 | S&F in replacement of twin core flat or round sheathed stranded copper conductor cable 1.5 Sqmm, complete all as specified & directed by Engr-in-Charge. |
| 38 | S&F junction box made of mild steel 1.6 mm thick of size 250mmx200mmx105mm incl 4 Nos aluminium bus bar of 2 mm thick duly fitted on the suitable insulator fixing with 35x6mm MS flat iron with nut, bolt and washer including one MCB SP 6 Amp with rail fitted in MS box incl suitable size cable hole, gland duly painted with two coats of aluminium paint over a coat of red oxide etc., complete all as specified and/or as directed by Engr-in-Charge. |
| 39 | S&F LED street light fitting 60 Watt 230V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including taking down the existing fitting, complete all as specified and/or as directed by Engr-in-Charge. |
| 40 | S&F Pole Street light bracket fabricated out of GI Tubing light grade 40/50 mm bore bend to the shape as directed and not less than length 1.0 mtr complete with Mounting MS Clamp of Flat Iron size 40x5mm of suitable length of 02 Nos including nut, bolts etc. of suitable size, complete all as specified and/or as directed by Engr-in-Charge. |
| 41 | M&L for installing, testing and commissioning of factory made bus bar chamber with 160 Amps MCCB comprising of 4 Nos aluminium bus bar of 200 Amp rating supported on insulator and enclosed with sheet steel enclosure out door type made out of 3.15 mm thick CRCA sheet, with top edge tappered, dust and vermin proof, having locking arrangement at front and opening arrangement from front & rear both including fixing arrangement on pole/grouting in floor, with colour coded FRP with compression cable glands for entry & exit of cables, powder coated, complete all as specified and directed by Engr-in-Charge. |
| 42 | M&L for earthing complete with galvanised steel earth plate electrode 600 X 600 X 6mm thick buried directly in ground vertically to a depth not less than 2.25 meters deep below ground level with top edge of the earth plate not less than 1.5 meter deep below normal ground level, connected with and including galvanised iron strip of size 25 x 4mm connected to main test point as directed as earthing lead by means of nuts, bolts and washers of galvanised iron protected by 40mm dia (medium grade) GI tubing, funnel, wire mesh, 20mm bore GI tubing (light grade) watering pipe, including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:2:4) type B-1 cover slab of size 350 x 350 x 50mm reinforced with 8mm dia TMT bars @ 15cm c/c in both ways and 10mm dia MS handle (01 No) of suitable size for lifting of cover slab, charcoal and salt in alternate layers including necessary excavation and earth work in soft/loose soil all as shown in Electrical plate No 3 of SSR Part-I and testing on completion, complete all as specified and/or as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |