Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Dismantling Works |
| 2 | OD345364/2025-2026:Dismantling of existing SSB panels from the site and placing it at a new location, as per directions, without interrupting the working of the plant including extending of the cable to the new location in clear water pump house |
| 3 | OD345365/2025-2026:Dismantling existing starter panel from the existing location and placing it in the new location without interrupting the water supply arrangement as per the direction of the department head in charge |
| 4 | OD345366/2025-2026:Dismantling of existing pump set including cutting of suction and delivery pipes and placing it at a location as directed by the departmental staff in charge |
| 5 | Supplying, Erection, Testing and Commissioning of Centrifugal Pumps |
| 6 | OD345373/2025-2026:Supply,erection,testcharging, trial run and commissioning of CF pump set with the following specification - 1. Pump - Supply, erection, testing and commissioning of KWA pre-qualified reputed make centrifugal pump sets with Bronze/SS impeller, SS shaft and CI pump casing with suitable types factory made base plate with pin and bush coupling, coupling guard, foundation bolts and nuts etc. complete including providing suitable concrete foundation including cost of material etc. complete. Discharge - 857 LPS, operating head - 19 m, with one standby.with an efficiency not less than 70%, Suction head ? positive suction, 2. Supply and delivery of empanelled make horizontal solid shaft foot mounted TEFC squirrel cage induction motor of the below specified motor rating with Class 'F' insulation with the temperature rise limit as applicable for Class B insulation, suitable for pump working at synchronous speed of 1000 rpm, 3 phase 50 Hz AC supply,duty condition -S1, working voltage 3.3kV . The motor shall conform to IE3 grade and IS 12615 (upto date revision and amendments). Motors shall be provided with PT 100 simplex type RTD's for winding temperature sensing (for indication, alarm and trip) and PT 100 Duplex type bearing RTDs for both bearings for trip, reading bearing temperature meter and space heaters with independent terminal box. Rates for the following motor ratings shall be provided. , including providing suitable concrete foundation, including cost of materials etc. complete. Flexible coupling shall be used for coupling of pumps and motors using pin & bush. 3. Flux compensated magnetic amplifier ( FCMA ) starter with neutral side type, , 14 SWG sheet clad IP 54 rated dust and vermin proof floor mounting, free standing cubicle type fully automatic motor control panel suitable for operation on 3 phase, 6.6/3.3kV Ac supply. The starting current shall be limited to 3 times of full load current of the motor. The starter is accompanied with following components, One number air cooled flux compensated magnetic amplifier unit, one number 3 pole 6.6/3.3 kV 630A LBS with HRC fuse , One set 6.6/3.3kV 400A 3P main vacuum contractor and 1 number 2P 400A bypass vacuum contactor, One number potential transformer with necessary primary and secondary fuse, One number control transformer for content control supply, One set current transformer for measuring current in each phase and neutral for metering, One set current transformer for protection circuit, One set timer for bypass and supervisory,. One Motor protection relay MM30/MPro 200 or equivalent, One set of RYB indication lamp, ON OFF, emergency push button with Trip indication , One set of Space heater with control switch and thermostat. One number Hour meter (Analog Type) for counting running time, Providing for power capacitor with HRC fuse for PF correction One set cable box with gland plate shall have sufficient space for termination incoming and outgoing cables.One number auxiliary relay trip on fault annunciation conforming to relevant IS, Bus bar should be made of aluminium conforming to relevant IS, with a minimum capacity of the current rating of the vacuum contactor One set of surge suppressor unit.NB: Feeder VCB cannot be used as a part of the starter The starter is comapatable with SCADA operation and remort loging the all parameters 4. Cabling - Supply, laying testing and commissioning of suitable size XLPE Aluminium cables for the above pump set from panel board to starter and from starter to motor considering energy conservation. 5. Earthing - Supply of all materials and providing suitable earthing by using suitable size pipe /plate earthing GI/copper strip buried in ground and giving double earthing to motor, starter, panel board etc. as per IE standards. 6. Capacitor - Supply, erection testing and commissioning of heavy duty APP capacitor for the motor to get a power above 0.99. Capacitor should be connected to external contactor, and the capacitor shall confirm to IS 28348. 7.Valves and Pressure gauges ? Supply, Erection and commissioning of suitable size best quality heavy duty ISI marked CI double flanged PN 1.6 Sluice Valve with electrical actuator (capable of operating in Fully, Semiautomatic modes and also in manual mode), PN 1.6 Non Return Valve and Pressure Gauges with suitable Pressure rating. Fitting of valves shall include proper RCC support. 8. Suction and delivery pipe connection - Supply and fitting of suitable size best quality MS pipe of shell thickness not less than 10 mm for a total of 10 m. suitable for the above pump set and connecting the suction pipe. |
| 7 | 14.72:Providing and fixing double scaffolding system (cup lock type) on the exterior side, upto seven story hight made with 40 mm dia. M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staricase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required location with essential safety features for the workmen etc. complete as per directions and approval of Engineer- in Charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment will be made once irrespective of duration of scaffolding. Note:- This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done . |
| 8 | 100.37.26.1:In situ fabrication of M.S. pipes of size 1000mm (I.D.) using 10mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete. |
| 9 | OD345374/2025-2026:Conveying, hoisting, fixing 1000mm MS Pipe including all labor charges and hiring of tools plants etc. |
| 10 | OD345377/2025-2026:Fabricating M.S. flanges of diameter 1000mm using 32mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete: For pipes fabricated with 10mm thick M.S. plates. |
| 11 | 100.37.26.3:Cutting 1000mm (I.D.) M.S. pipes for making bends and other specials by gas cutting including cost of gas, all labour and hire charges of tools etc., complete: For pipes fabricated with 10mm thick M.S. plates. |
| 12 | 100.37.26.4:Welding 1000mm (I.D.) M.S. pipes for making bends and other specials by gas/electric welding machine including cost of gas and welding rods, all labour and hire charges of tools etc., complete: For pipes fabricated with 10mm thick M.S. plates. |
| 13 | 100.37.26.5:Grinding cut and weld edges of 1000mm (I.D.) M.S. pipes during fabrication work including all labour and hire charges of tools etc., complete: For pipes fabricated with 10mm thick M.S. plates. |
| 14 | OD345376/2025-2026:Providing flanged joints to double flanged MS pipes and specials, including testing of joints: 1000 mm diameter pipe |
| 15 | 13.52.1:Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work |
| 16 | 5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 17 | 5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars |
| 18 | 5.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 19 | OD345375/2025-2026:Supply, Erection and commissioning of 600mm best quality heavy duty ISI marked DI double flanged PN 1.6 Sluice Valve with electrical actuator (capable of operating in Fully, Semiautomatic modes and also in manual mode) starter cables etc completed as per direction of departmental officers |
| 20 | OD5556/2026-2027:Providing and making circular holes of 300 mm diameter in RCC / PCC wall using heavy-duty core cutting / diamond drilling machine, including all labour, machinery, tools, and consumables required to complete the work as per site requirements. |
| 21 | Supply, Erection & Commissioning of Transformer |
| 22 | OD501/2026-2027:11/3.3 KV, 1000KVA Transformers (Outdoor type) - Supply, Erection, testing and commissioning of 1000 KVA, 11/3.3KV . 3phase, 50Hz. ONAN cooled, outdoor type copper wound power transformer, Energy Efficiency Level-1 outdoor transformer having vector group of YNd11 suitable for parallels operation, with HV and LV side cable entry box arrangements, on load tap changer with 17 tap positions having +5% to -15% variations in1.25% steps with RTCC panel with AVR control relay and local & remote indication of tap position, and including first filling of oil, earthing etc. complete with all fittings as per IS 1180 & IS 2026 and Kerala Electrical Inspectorate standards. Armored multi core 2.5 Sq.mm copper control cables shall be used for all external & internal interconnections. The cost of neutral grounding CT, emergency stop, control cables both internal and external shall be included in the cost of Transformer. |
| 23 | OD345363/2025-2026:11KV/433V, 160 KVA Transformers (Outdoor type) - Supply, Erection, testing and commissioning of160 KVA, 11KV/433 V. 3phase, 50Hz. ONAN cooled, outdoor type copper wound power transformer, suitable for parallels operation, with HV and LV side cable entry box arrangements, OFF load tap changer with 7 tap positions having +5% to -10% variations and including first filling of oil, earthing etc. complete with all fittings as per IS 1180 & IS 2026 and Kerala Electrical Inspectorate standards. Armored multi core 2.5 Sq.mm copper control cables shall be used for all external & internal interconnections. The cost of neutral grounding CT, emergency stop, control cables both internal and external shall be included in the cost of Transformer. |
| 24 | 2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil |
| 25 | 4.1.2:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources : 3graded stone aggregate 20 mm nominal size derived from natural sources) |
| 26 | 5.1.3:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 27 | 5.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 28 | 5.9.2:Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 29 | 7.1.1:Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 30 | 5.2.2:Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up tot floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 31 | 5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more |
| 32 | 50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 33 | 50.10.2:Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 34 | 26.19.1:Providing at all heights, levels and locations Aluminium profile industrialtroughed sheet of Alloy 31500/31000/40800, conforming to IS 1254, IS 737, IS2676. The sheet shall be fixed using self drilling/self tapping SS screws of size5.5x65 mm with EPDM seal complete upto required pitch in horizontal, verticalor curved surfaces i/c cutting to size and shape where required as perspecifications, detail drawings and direction of Engineer-in-Charge. The rateshall be inclusive of all screws, seal, ridge, labour, scaffolding, machinery forfixing and approved sealent where required etc. but excluding the cost ofpurlins, rafters and trusses.0.71 mm thick, the profile detail width 1044/920 mm, cover width 1000/875 mm. |
| 35 | 13.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 36 | 12.41.2:Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.110 mm diameter |
| 37 | 50.6.1.3:Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure above floor two level up to floor V level thickness 20cm and above in: CM 1:6 ( 1 cement :6 coarse sand) etc complete |
| 38 | 13.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) |
| 39 | 13.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer |
| 40 | 13.44.1:Finishing walls with water proofing cement paint of required shade:New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 41 | 16.3.2:Supplying and stacking at site.63 mm to 45 mm size stone aggregate |
| 42 | OD345362/2025-2026:Laying stone aggregates including screening, sorting and spreading to template and consolidation etc. complete. (excluding the cost of material). Stone aggregate 63 mm to 45 mm |
| 43 | OD3812/2026-2027:Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts , bolts and washers as required complete as per the direction of Engineer-in- charge.Made of G.I wire of minimum dia 3.5mm. PVC coated to achieve outer dia. not less than 5 mm in required colour and shade |
| 44 | 10.2:Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 45 | HT Panel Works |
| 46 | OD345368/2025-2026:11 KV Switch gear(Indoor) Extending exciting 11KV MSB Supply, erection, testing and commissioning of 11KV, 630A, 350MVA, totally enclosed, single bus bar, floor mounting in metal clad, indoor extensible type flush mounted horizontal isolation and draw out type vacuum circuit breaker single panel system (2 no. VCB ) suitable for installation in 3 phase , 3wire, 50Hz. AC,11kv, effectively earthed supply system, comprising of motorized and spring assisted, independent, trip free closing mechanism and all metering equipment, protective relays etc. complete as approved by Kerala Electrical Inspectorate and relevant standards. Armored multi core 2.5 Sq.mm copper control cables shall be used for all external & internal interconnections. The cost of control cables both internal and external shall be included in the cost of HT panel. |
| 47 | OD345370/2025-2026:Supply and extension of existing busbars (100*10 copper busbar) of 11 kV HT panel and providing proper connections to the newly installed VCB panel |
| 48 | OD345369/2025-2026:Supply and installation of new copper Flexibles for termination at transformer and HT panel side |
| 49 | OD345371/2025-2026:Supply and installation of 16 gauge adapter box for termination of aluminium bus duct at transformer HT side |
| 50 | Panel Board Fixing |
| 51 | OD614/2026-2027:3.3 KV MCB Switch gear Panel (Indoor) Supply, erection, testing and commissioning of 3.3KV, 630A, 350MVA, totally enclosed, single bus bar, floor mounting in metal clad, indoor extensible type flush mounted horizontal isolation and draw out type vacuum circuit breaker 1 No incomer and 1 no bus coupller and 3 No outgoing suitable for installation in 3 phase , 3wire, 50Hz. AC3.3kv, effectively earthed supply system, comprising of motorized and spring assisted, independent, trip free closing mechanism and all metering equipment, protective relays etc. complete as approved by Kerala Electrical Inspectorate and relevant standards. Armored multi core 2.5 Sq.mm copper control cables shall be used for all external & internal interconnections. The cost of control cables both internal and external shall be included in the cost of HT panel. |
| 52 | OD345343/2025-2026:Design, Fabrication, Supply, Erection, Testing and commissioning of - cubicle type, fully compartmentalized, free standing type switch boards, dust tight and vermin proof, fabricated out of 16 SWG CRCA sheet powder coated with approved colour. The switch boards should have a set of suitably rated TPN aluminium bus bars with specified current and fault level, insulated with heat shrinkable colour coded PVC sleeves and supported using DMC/SMC pillar or finger type bus bar supports. :- MSB INCOMER, 630A 50kA 4P microprocessor based MCCB with shunt trip and UV coil - 1nos, Meters & Indications, MFDM (EM6400) -2set, RYB Indication lamps - 1set, 400/5A, CL-.5, 15VA, C.T. - 3No, 400/5A, CL-PS, 15VA, C.T. - 3No, Relays - Under voltage relay 1 nos, Over voltage relay 1 nos, Restricted earth fault relay 1 nos, Ground Earth fault relay 1 nos, OUTGOING - 250A 3P 50 kA microprocessor based MCCB - 4nos, 160A 3P 36kA microprocessor type MCCB - 4 Nos, |
| 53 | OD345342/2025-2026:Design, Fabrication, Supply, Erection, Testing and commissioning of - Cubicle type, fully compartmentalized, free standing type switch boards, dust tight and vermin proof, Fabricated out of 16 SWG CRCA sheet powder coated with approved colour. The switch boards should have a set of suitably rated TPN aluminium bus bars with specified current and fault level, insulated with heat shrinkable colour coded PVC sleeves and supported using DMC/SMC pillar or finger type bus bar supports. :- SSB - INCOMER - 250A 4P 50 kA microprocessor based MCB - 1no, Meters & Indications, MFDM (EM 6400) -1set, RYB Indication lamps - 1set. OUTGOING -160A TP 36kA MCCB - 3Nos, 125A TP 25kA MCCB - 3No,100A 3P 36kA microprocessor type MCCB - 3 Nos |
| 54 | OD3242/2026-2027:MCB DISTRIBUTION BOARDS - Supply Installation, Testing & Commissioning of dust and vermin proof, MCB DB, IP-43, with metal door, including copper busbar, neutral link, DIN bar, necessary dummy plates, RCBO/RCCB/MCB/MCB Isolator as incomer and SPMCB/3PMCB (10KA) as outgoings etc. Fixed on wall using suitable anchor bolts or fixed in recess including cutting holes, rough plastering, etc. as required. 4 WAY, 3 PHASE, DOUBLE DOOR, ETPN DB, IP 43.Incomer: 32A, 4P, RCBO 30mA -1no.Outgoings: 6/10/16A/20A SPMCB -12nos |
| 55 | OD3243/2026-2027:MCB DISTRIBUTION BOARDS - Supply Installation, Testing & Commissioning of dust and vermin proof, MCB DB, IP-43, with metal door, including copper busbar, neutral link, DIN bar, necessary dummy plates, RCBO/RCCB/MCB/MCB Isolator as incomer and SPMCB/3PMCB (10KA) as outgoings etc. Fixed on wall using suitable anchor bolts or fixed in recess including cutting holes, rough plastering, etc. as required. 6 WAY, 3 PHASE, DOUBLE DOOR, VDB, IP 43.Incomer: 63A, 4P, MCB IsolatorOutgoings: 16A SPMCB -3nos, 32A, 3P, MCB-3nos |
| 56 | Armored UG Cables - AL |
| 57 | OD3258/2026-2027:H T CABLING - Supply and laying of 3C 300 sq.mm (A2XFY/A2XWY) XLPE insulated, PVC sheathed, Armoured cable with conductors of best conductivity Aluminium conforming to IS: 7098/II/85, 11KV grade approved by the Engineer in charge. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 3C X 300sq.mm AL |
| 58 | OD3257/2026-2027:H T CABLING - Supply and laying of 3C 185 sq.mm (A2XFY/A2XWY) XLPE insulated, PVC sheathed, Armoured cable with conductors of best conductivity Aluminium conforming to IS: 7098/II/85, 11KV grade approved by the Engineer in charge. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 3C X 185sq.mm AL |
| 59 | OD3397/2026-2027:H T CABLING - Supply and laying of 3C 185 sq.mm (A2XFY/A2XWY) XLPE insulated, PVC sheathed, Armoured cable with conductors of best conductivity Aluminium conforming to IS: 7098/II/85, 6.6KV grade approved by the Engineer in charge. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 3C X 185sq.mm AL |
| 60 | OD345339/2025-2026:Supply and Laying of XLPE insulated FR PVC outer sheathed, inner extruded PVC sheath, armored, stranded Al conductor cables of 1.1KV 'class cables per IS 7098 Part -1. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 3.5C X 240sq.mm AL |
| 61 | OD345338/2025-2026:Supply and Laying of XLPE insulated FR PVC outer sheathed, inner extruded PVC sheath, armored, stranded Al/Cu conductor cables of 1.1KV 'class cables per IS 7098 Part -1. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters. 3.5C X 70 sq.mm AL |
| 62 | OD3241/2026-2027: MV XLPE ARMOURED CABLE -) Supply and laying of 3.5x35sq.mm Armoured XLPE insulated and PVC sheathed power cable AL conductor of best conductivity 1.1KV grade strictly conforming to IS:7098 (Part-I) 1988 .The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 3.5C X 35sq.mm AL |
| 63 | OD3240/2026-2027: MV XLPE ARMOURED CABLE -) Supply and laying of 4Cx10sq.mm Armoured XLPE insulated and PVC sheathed power cable AL conductor of best conductivity 1.1KV grade strictly conforming to IS:7098 (Part-I) 1988 .The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 4C X 10sq.mm AL |
| 64 | OD3239/2026-2027: MV XLPE ARMOURED CABLE - Supply and laying of 4Cx6q.mm Armoured XLPE insulated and PVC sheathed power cable AL conductor of best conductivity 1.1KV grade strictly conforming to IS:7098 (Part-I) 1988 .The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 4C X 6sq.mm AL |
| 65 | OD3238/2026-2027:COPPER CONTROL CABLE - Supply and laying of 3Cx2.5sq.mm Armoured XLPE PVC insulated and PVC sheathed copper control cable of best conductivity 650V grade strictly conforming to IS:7098 (Part-I)1988.The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 3C X 2.5sq.mm Cu |
| 66 | OD3237/2026-2027:COPPER CONTROL CABLE - Supply and laying of 12Cx2.5sq.mm Armoured XLPE PVC insulated and PVC sheathed copper control cable of best conductivity 650V grade strictly conforming to IS:7098 (Part-I)1988.The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready -made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tag shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters.- 12C X 2.5sq.mm Cu |
| 67 | Armored / Flexible Cables - CU |
| 68 | OD345350/2025-2026:Supply and Laying of XLPE insulated FR PVC outer sheathed, inner extruded PVC sheath ,armored/flexible, stranded Cu conductor cables of 1.1KV 'class cables per IS 7098 Part -1. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready –made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tags shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters. 3C X 16 sq.mm Cu cable. |
| 69 | OD345348/2025-2026:Supply and Laying of XLPE insulated FR PVC outer sheathed, inner extruded PVC sheath ,armored/flexible, stranded Cu conductor cables of 1.1KV 'class cables per IS 7098 Part -1. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready – made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tags shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters - 6C X 1.5 sq.mm Cu Armed Cable |
| 70 | OD345349/2025-2026:Supply and Laying of XLPE insulated FR PVC outer sheathed, inner extruded PVC sheath ,armored /flexible, stranded Cu conductor cables of 1.1KV 'class cables per IS 7098 Part -1. The cable shall either be 'laid in trench 0.5M wide 0.75M deep / RCC 'Hume pipe of size 150mm / ready – made cable tray with proper clamping. Rate shall be inclusive of cable tags, clamps, etc. Cable tags shall be of aluminium engraved sheets (2mm) tied at regular intervals of not less than 10 meters. 1C * 150 sq.mm copper flexible cable |
| 71 | Cable Termination |
| 72 | OD345354/2025-2026:MV CABLE END TERMINATION - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminiumconductor cable of 1.1 KV grade as required. 3.5 C x 240 sqmm |
| 73 | OD345352/2025-2026:MV CABLE END TERMINATION - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5C X 70 sq.mm AL |
| 74 | OD3234/2026-2027:MV CABLE END TERMINATION - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminiumconductor cable of 1.1 KV grade as required. 3.5C x 35sq.mm |
| 75 | OD345353/2025-2026:MV CABLE END TERMINATION - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. . 4C X 16 sq.mm AL |
| 76 | OD3233/2026-2027:MV CABLE END TERMINATION - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminiumconductor cable of 1.1 KV grade as required. 34C x 10/6sq.mm |
| 77 | OD3235/2026-2027:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.12C x2.5sq.mm |
| 78 | OD3236/2026-2027:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3C x2.5sq.mm |
| 79 | OD345351/2025-2026:Supply and making end termination with brass single compression glands for indoor terminations and double compression cable glands for outdoor terminations, and solder less crimping type tinned Cu lugs/Al lugs for the following XLPE insulated PVC sheathed 1100 V grade, armored, stranded, Al /Cu conductor cable including cost of ferrules, cable sockets, insulation tape and other accessories, inclusive of dismantling of existing if necessary as required. 1C * 150 sq.mm copper flexible cable |
| 80 | OD345356/2025-2026:Supply and making end termination with brass single compression glands for indoor terminations and double compression cable glands for outdoor terminations, and solder less crimping type tinned Cu lugs/Al lugs for the following XLPE insulated PVC sheathed 1100 V grade, armored, stranded, Al /Cu conductor cable including cost of ferrules, cable sockets, insulation tape and other accessories, inclusive of dismantling of existing if necessary as required. 6C X1.5 sq.mm Cu Arm. |
| 81 | Earthing System |
| 82 | OD345359/2025-2026:Earthing with G.I. earth plate1200 mm X1200 mm X 12 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. The earthing station should confirm to IS 3043/87. (All civil works shall be done by the contractor |
| 83 | OD345361/2025-2026:Supply and laying earth strips 0.5M below ground/exposed including connections by proper nut-bolts/ welding 50 X 6mm GI strip (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 84 | OD345358/2025-2026:Supply and laying earth strips 0.5M below ground/exposed including connections by proper nut-bolts/ welding 32 X 6mm Cu strip (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 85 | OD345360/2025-2026:Supply and laying earth strips 0.5M below ground/exposed including connections by proper nut-bolts/ welding 25 X 3mm Cu strip (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 86 | Supply Erection commissioning of flow meter |
| 87 | OD345345/2025-2026:Supply erection commissioning 1422mm an electro magnetic flow meter confirming to protection level of IP68 for flow sensor and IP67 for transmitter and having on accuracy level of 0.5% with LED/LCD display unit. The flow meter should have the housing (floe sensor) to be made of SS 304/ carbon steel with anti corrosive protection and inside liner to be made up of hard rubber/ neoprene all confirming drinking water standards. The flow meter should be coupled with HART for data acquisition and transfer with for wireless transfer through GSM. The manufactures should have the calibration standards as per the ISO 17025 and flow meter certified by FCRI Palakkad .Work include cutting the pipe and placing the flow meter and jointing the pipe using standard DI/ MS pipe specials, testings joints , laying the electrical and communication cables including all materials and labour charges |
| 88 | OD345347/2025-2026:Supply erection commissioning 1200/1000mm an electro magnetic flow meter confirming to protection level of IP68 for flow sensor and IP67 for transmitter and having on accuracy level of 0.5% with LED/LCD display unit. The flow meter should have the housing (floe sensor) to be made of SS 304/ carbon steel with anti corrosive protection and inside liner to be made up of hard rubber/ neoprene all confirming drinking water standards. The flow meter should be coupled with HART for data acquisition and transfer with for wireless transfer through GSM. The manufactures should have the calibration standards as per the ISO 17025 and flow meter certified by FCRI Palakkad .Work include cutting the pipe and placing the flow meter and jointing the pipe using standard DI/ MS pipe specials, testings joints , laying the electrical and communication cables including all materials and labour charges |
| 89 | OD345346/2025-2026:Supply erection commissioning an 150mm electro magnetic flow meter confirming to protection level of IP68 for flow sensor and IP67 for transmitter and having on accuracy level of 0.5% with LED/LCD display unit. The flow meter should have the housing (floe sensor) to be made of SS 304/ carbon steel with anti corrosive protection and inside liner to be made up of hard rubber/ neoprene all confirming drinking water standards. The flow meter should be coupled with HART for data acquisition and transfer with for wireless transfer through GSM. The manufactures should have the calibration standards as per the ISO 17025 and flow meter certified by FCRI Palakkad .Work include cutting the pipe and placing the flow meter and jointing the pipe using standard DI/ MS pipe specials, testings joints , laying the electrical and communication cables including all materials and labour charges. |
| 90 | Construction of Valve Chamber |
| 91 | 100.1.1:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in all kinds of soil. |
| 92 | 100.1.2:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth exceeding 1.5m but not exceeding 3m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in all kinds of soil. |
| 93 | 4.1.2:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources : 3graded stone aggregate 20 mm nominal size derived from natural sources) |
| 94 | 5.1.2A:1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) incuding manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 20% : 3 graded stone aggregate 20 mm nominal size of Recycled Concrete Aggregate (RCA) upto 20%. |
| 95 | 5.22.B.1:Steel reinforcement for R.C.C. work ready to use \\"cut and bend\\" rebars of approved make from factory/workshop to construction site including placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more |
| 96 | 4.3.1:Centering and shuttering including strutting, propping etc. and removal of form work for:Foundations, footings, bases for columns |
| 97 | Replacing the RTC unit of 2MVA 11/3.3Kv transformers |
| 98 | OD4536/2026-2027:Supply erection commissioning of RTC panel for 2MVA 11/3.3Kv transformer including control wiring and all related accessorizes as per direction of departmental officers. RTC panel must be comparable for exiting 2MVA transformer. |
| 99 | OD4537/2026-2027:Dismantling the old and damaged RTC panel and disconnecting control wiring , power connection etc as per direction of departmental officers |
| 100 | Preparation of drawing and Scheme approval charges |
| 101 | OD4585/2026-2027:\\"Statutory Approval - Obtaining statutory approval from Elecrical Inspectorate including preparation ofdrawings, obtaining approval for the drawings arranging inspection of the installations and obtainingsafety certificate etc.after completion of the work and avail supply from KSEB. The necessary statutory fees if any payable to the Electrical Inspectorate/ KSEB will be paid by KWA (Note: Scheme approval from theElectrical Inspectorate has to be obtained before supplying the equipment. Payment for the supply of materials (Electrical side ) will be released only on production of scheme Approval.) |
| 102 | Safety Items |
| 103 | OD4756/2026-2027:SAFETY ITEMS - Supply of HT Hand Gloves 2 pair and 32mm Telscopic High Voltage Discharge Earth Rod 3 stage 18F fiber glass finishing with 6Sq.mm copper wire 6M with crocodile clip |
| 104 | OD4757/2026-2027:SAFETY ITEMS - Supply & fixing of high voltage danger notice board 250mmx200mm size vitrous enamelled high voltage danger notice board 250mmx200mm size |
| 105 | OD4758/2026-2027:SAFETY ITEMS - Supply fixing of MV voltage danger notice board 200mmx150mm MV voltage danger notice board 200mmx150mm |
| 106 | OD4759/2026-2027:SAFETY ITEMS - "Supply and fixing of First-Aid Box with essential medicines along with First Aid Chart duly framed and placed in a conspicuous location for clear vision |
| 107 | OD4760/2026-2027:SAFETY ITEMS -Supply and fixing of 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint mounted on MS angle frame work/ wall bracket filled with finesand, painting the bracket/ floor stand, etc. as required |
| 108 | Supply and erection Vacuum pump |
| 109 | OD5090/2026-2027:Supply and erection commissioning of vacuum pump with the following specification Supply and erection of reputed make have I S I mark approved by the K W A 10 HP 415V 50 Hz. 1500 rpm coupled type vacuum pump with motor, air flow rate upto 162M3/Hr (at mean sea level), IP55, Suction and delivery pipe size not less than 40mm pipe 25M length, 6 nos GM valve inter connection etc and all accessories having panel board with MCCB,volt meter with selector switch and fully automatic star delta starter 6 sq mm 3.5 core copper PVC insulated cable , earthing work (double earthing) of the motor starter ,switch cable etc , and M20 concert foundation with MS rails etc complete |
| 110 | BPT Painting |
| 111 | 13.91:Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete. |
| 112 | 13.52.1:Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work |
| 113 | OD5512/2026-2027:Wall painting on exterior walls with Acryllic exterior emulsion paint of approved brand (two coats over old surfaces) to give an even shade after scrapping and cleaning the surfaces. |
| 114 | Construction of ladder for 74MLD BPT |
| 115 | 14.72:Providing and fixing double scaffolding system (cup lock type) on the exterior side, upto seven story hight made with 40 mm dia. M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staricase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required location with essential safety features for the workmen etc. complete as per directions and approval of Engineer- in Charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment will be made once irrespective of duration of scaffolding. Note:- This item to be used for maintenance work judicially, necessary deduction for scaffolding in the existing item to be done . |
| 116 | 10.2:Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 117 | 15.2.1:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) |
| 118 | 4.1.2:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources : 3graded stone aggregate 20 mm nominal size derived from natural sources) |
| 119 | 5.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 120 | 5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |