| 1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and directed. |
| 2 | M & L for Point wiring for one light/fan point/call bell controlled by one way switch with two runs of single core 1.5 Sq.mm. (Nominal area) PVC insulated unsheathed multistranded copper conductor cable FRLS (ISI marked) drawn through and including non metallic PVC casing capping (ISI marked) (aprox size 20/25/40mm width) surface type with all fittings/fixtures such as Tee, Bend, elbow, socketr, shaddle etc including 1.5mm thick MS sunken/terminal box including 3mm thick backelite sheet cover for fixing flush type switches, sockets, regulators etc. including provision of multistranded 1.5 Sq.mm copper conductor cable FRLS [ISI marked] as earth wire connected to common earth dolly and earth in distribution board complete all as specified and as directed.(Note.: (i) The rate quoted is deemed to include making good the disturbed sufaces and to match the adjoining surface.) |
| 3 | All as per item No. 02 mentioned here-in-above but for One 3/5 pin socket outlet 6 amps on independent board complete ditto |
| 4 | All as per item No. 02 mentioned here-in-above but for One 3/5 pin socket outlet 6 amps point on same board complete ditto |
| 5 | All as per item No. 02 mentioned here-in-above but for one 15 Amps power point on the independent board with two runs of PVC insulated and unsheathed copper conductor cable of size 2.5 sqmm multistranded FRLS (ISI marked) and 2.5 sqmm PVC insulated unsheathed solid copper conductor cable FRLS (ISI marked) as earth lead complete ditto |
| 6 | S & F switch piano Flush type, single pole one way 6 Amp 240 volts, complete all as specified and as directed. |
| 7 | S & F in repairs switch piano Flush type, single pole one way 6 Amp 240 volts, complete all as specified and as directed. |
| 8 | S & F Switch socket combination 2 in 1, 6 Amp, flush type complete all as specified and as directed. |
| 9 | S & F in repairs Switch socket combination 2 in 1, 6 Amp, flush type complete all as specified and as directed |
| 10 | S & F Socket outlet 2 in 1, 3 pin, 6 Amps, flush type complete all as specified and as directed. |
| 11 | S & F in repair Socket outlet 2 in 1, 3 pin, 5 Amps, flush type complete all as specified and as directed. |
| 12 | S & F Bell electric, Ding Dong AC 230 Volts, single pole complete all as specified and as directed. |
| 13 | S & F in repairs Bell electric, Ding Dong AC 230 Volts, single pole complete all as specified and as directed. |
| 14 | S & F bell push flush type, 6 amp 240 volts, complete all as specified and as directed. |
| 15 | S & F in repairs bell push flush type, 6 amp 240 volts, complete all as specified and as directed. |
| 16 | S & F Switch socket combination 3 pin 16A, flush type complete all as specified and as directed. |
| 17 | S & F in repair switch socket combination 3 pin 16A, flush type complete all as specified and as directed. |
| 18 | S & F ceiling rose, 65 X 50mm two to three terminals, PVC/polycarbonate, insolated body complete all as specified and directed. |
| 19 | S & F in repairs ceiling rose, 65 X 50mm two to three terminals, PVC/polycarbonate, insolated body complete all as specified and directed. |
| 20 | S & F Lamp Holder, PVC/ Polycarbonate type with backplate suitable for batten fitting complete all as specified and as directed. |
| 21 | S & F in repair Lamp Holder, PVC/ Polycarbonate type with backplate suitable for batten fitting complete all as specified and as directed. |
| 22 | S & F LED bulb 12Watts 240V 50Hz 6500K b22 base in bulb holder complete all as specified and directed by Engineer-in-Charge. |
| 23 | S & F in repair LED bulb 12Watts 240V 50Hz 6500K b22 base in bulb holder complete all as specified and directed by Engineer-in-Charge. |
| 24 | S & F Stepped type electonic fan regulator 230 V flush type on the existing phenolic laminated sheet complete all as specified and as directed. |
| 25 | S & F in repairs Stepped type electonic fan regulator flush type on the existing phenolic laminated sheet complete all as specified and as directed. |
| 26 | S & F in repairs switch modular, 1 Way, 10 amp, 240 volts,1 Module complete all as specified and as directed. |
| 27 | S & F in repairs switch modular, 1 way, 16 amp 240 volts,1 Module complete all as specified and as directed. |
| 28 | S & F in repairs switch modular, Two way, 10 Amp, 240 volts,1 module complete all as specified and as directed. |
| 29 | S & F in repairs Modular socket outlet 6A, 2/3 pin combined, 2 module, AC 230V, 50HZ complete all as specified and as directed. |
| 30 | S & F in repairs Modular socket outlet 6A/16A, 2/3 pin combined, 2 module, AC 230V, 50HZ complete all as specified and as directed. |
| 31 | S & F in repairs stepped type modular fan regulator ,100/120 W, 1/ 2 module complete all as specified and as directed. |
| 32 | S & F in repairs modular bell push 6 amp 240 volts1 module,complete all as specified and as directed. |
| 33 | S & F in repair madular Switch socket Combination 16A, 6 pin, 3 module complete all as specified and directed |
| 34 | M & L in repair Sub main wiring with two runs of 2.5 sqmm (Nominal area) single core cable FRLS PVC insulated, multistranded, unsheathed, copper conductor cables 1100 Volts grade drawn through including PVC Casing capping of suitable size with all accesories and fittings, fixed to wall/ceiling etc including 2.5 sqmm (nominal area) single core, FRLS PVC insulated, multistranded, unsheathed, copper conductor as earth wire and duly connected to common earth point complete all as specified and as directed by Engineer-in-charge. (Note : Two run cables and one run of earth wire and one run of casing capping will be measured as one length.) |
| 35 | M & L in repair Sub main wiring with 2 runs of Single core 4 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FRLS (ISI marked) copper cable drawn through and including surface PVC casing capping of suitable size with all accesories and fittings along with 1 run of single core 4 sqmm PVC insulated multi stranded FRLS (ISI marked) copper cable as earth continuity conductor complete all as specified and as directed.(Note :- Two runs of 4 sqmm and one runs of 4 sqmm cable as earth wire and one run of casin capping shall be measured as one length) |
| 36 | M & L in repair Sub main wiring with 2 runs of Single core 6 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FRLS (ISI marked) copper cable drawn through and including surface PVC casing capping of suitable size with all accesories and fittings along with 1 run of single core 6 sqmm PVC insulated multi stranded FRLS (ISI marked) copper cable as earth continuity conductor complete all as specified and as directed.(Note :- Two runs of 6 sqmm and one runs of 6 sqmm cable as earth wire and one run of casin capping shall be measured as one length) |
| 37 | S & F in repair Rigid non-metalic PVC casing capping of size 25mm inclusive of all fittings and fixing accessories complete all as specified and directed. |
| 38 | S&F in replacement of PVC conduit 20 mm dia medium duty in existng wiring with complete all as directed. |
| 39 | S&F in replacement of PVC conduit 25 mm dia medium duty in existng wiring with complete all as directed. |
| 40 | S & F in repairs PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 100 mm x 100 mm and 50 mm deep complete all as specified and directed. |
| 41 | S & F in repairs PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 175 mm x 100 mm and 50 mm deep complete all as specified and directed. |
| 42 | S & F in repairs PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 200 mm x 150 mm and 50 mm deep complete all as specified and directed. |
| 43 | S & F LED Bulk Head, 10 Watt, IP 65 rated, compact design, PC Co extruded with high energy saving with all accessories and connecting up including lamp complete all as specified and directed. |
| 44 | S & F in repair LED Bulk Head, 10 Watt, IP 65 rated, compact design, PC Co extruded with high energy saving with all accessories and connecting up including lamp complete all as specified and directed. |
| 45 | S & F LED tube light fittings, surface mounting, general purpose, in extruded aluminium housing, 20 Watt and 2000 Lumens, 6500K with all accessories, internally prewired and connecting up including tube lamp complete all as specified and directed. |
| 46 | S & F in repair LED tube light fittings, surface mounting, general purpose, in extruded aluminium housing, 20 Watt and 2000 Lumens, 6500K with all accessories, internally prewired and connecting up including tube lamp complete all as specified and directed. |
| 47 | S & F wall mounted, mirror light LED light 10 watt, 230 Volts, complete with all accessories, connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting and testing complete all as specified and directed. |
| 48 | S & F in repair wall mounted, mirror light LED light 10 watt, 230 Volts, complete with all accessories, connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting and testing complete all as specified and directed. |
| 49 | S & F LED recessed round shape suitable for false ceiling 12 watts, 220 volts AC with high efficiency PMMA diffuser soft glare free light complete drivers, holders, LED lamp including connecting up with three core flexible copper conductor cable of suitable, including LED bulb, complete all as specified and as directed. |
| 50 | S & F in repair LED recessed round shape suitable for false ceiling 12 watts, 220 volts AC with high efficiency PMMA diffuser soft glare free light complete drivers, holders, LED lamp including connecting up with three core flexible copper conductor cable of suitable, including LED bulb, complete all as specified and as directed. |
| 51 | S & F 36 Watt (100lm/w), 2ftx2ft, LED recessed full lit luminaire with glare free uniform illumination with loger life and less maintenance with all accessories, internally prewired and connecting up including tube lamp complete all as specified and directed. |
| 52 | S & F in repair 36 Watt (100lm/w), 2ftx2ft, LED recessed full lit luminaire with glare free uniform illumination with loger life and less maintenance with all accessories, internally prewired and connecting up including tube lamp complete all as specified and directed. |
| 53 | S & F in repair LED STREEK TRACKLIGHT Surface Spotlight with aluminum structure, available with adjustable light engine to achieve the desired illumination angle, 20 watts, 4000K, body colour white or black connected with with all accessories and three core flexible copper conductor cable complete all as specified and as directed. |
| 54 | S & F in repair 6W LED Picture Light wallmounted, 3-in-1 colour changing connected with with all accessories and three core flexible copper conductor cable complete all as specified and as directed. |
| 55 | S & F in repairs MCB SP 6 to 32 Amps, 240 Volts, 10KA, C Curve, complete all as specified and as directed |
| 56 | S & F in repair MCB SPN 6-32A Amps, 240 Volts, 10KA, C Curve complete all as specified and as directed |
| 57 | S & F in repairs MCB SPN 40-63 Amps, 240 Volts, 10KA, C curve complete all as specified and as directed |
| 58 | S & F in repair MCB, TPN 40-63 Amps, 415 Volts, 10KA, C Curve complete all as specified and as directed |
| 59 | S&F in repair MCB SPN DB made up with sheet metal double door, phosphorised, power coated, neutral link, earth bar and din rail, 2 way with 200 amps rated bus bar, 240 volts complete all as specified and as directed. |
| 60 | S&F in repair MCB SPN DB made up with sheet metal double door, phosphorised, power coated, neutral link, earth bar and din rail, 4 way with 200 amps rated bus bar, 240 volts complete all as specified and as directed. |
| 61 | S&F MCB SPN DB made up with sheet metal double door, phosphorised, power coated, neutral link, earth bar and din rail, 8 way with 200 amps rated bus bar, 240 volts complete all as specified and as directed. |
| 62 | S&F in repair MCB TPN DB made up with sheet metal, phosphorised, power coated, neutral link, earth bar and din rail, 4 way TPN with 200 amps rated bus bar, 415 volts complete all as specified and as directed. |
| 63 | S&F Galvanised iron strip of size 32 x 6 mm with saddles and fixing screws etc buried in ground incl taking down old unserviceable one complete all as specified and as directed. |
| 64 | M&L for 32 x 6mm aluminium strip burried in ground/fixed on wall ,roofwith saddles and fixing screws etc., for roof conductors and down conductors above ground after taking down old one complete all as specified and as directed |
| 65 | S&F Air termination aluminium single pointed rod 12 mm dia, 300 mm long incl taking down old unserviceable one complete all as specified and as directed. |
| 66 | Supply and fix in repair test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25 mm drilled and screwed including 3 nos 8mm dia 25mm long hex head screw complete all as specified and as directed. |
| 67 | Supply and Laying 40mm bore of GI pipe Steel Water Tubing , Galvanised, ‘Light Grade’ with all Fittings, laid in trenches or any other Situation, for earth strip in road crossing complete as all specified and as directed. |
| 68 | S & F 1100 volts grade, heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, cross sectional area 6 Sqmm 2 core solid conductor including taking down existing one complete all as specified and directed. |
| 69 | S & F 1100 volts grade, heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, cross ectional area 10 Sqmm 2 core solid conductor including taking down existing one complete all as specified and directed. |
| 70 | S & F 1100 volts grade, heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, 16 Sqmm 2 core solid conductor including taking down existing one complete all as specified and directed. |
| 71 | M & L for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized steel earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (light grade), wire mesh, aluminium lugs, complete in all respect, GI earth wire protected by 15 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge. |
| 72 | M & L Earthing complete with GI earth plate electrode 600 mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with galvanised earth strip of size 32x6mm by means of bolts, nuts, check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 40 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab of size 350x350x50mm (reinforced with 10 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge. Please Enable Macros to View BoQ information |
| 73 | M & L Earthing complete with GI earth plate electrode 600 mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with galvanised earth strip of size 32x6mm by means of bolts, nuts, check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 40 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab of size 350x350x50mm (reinforced with 10 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge. Please Enable Macros to View BoQ information |