| 1 | Taking down unserviceable fitting of any type or any wattage i.e. 100/90/80/72/60/45/30/25 Watt energy efficient street light fitting, identifying the fault, repair / replacement of old unserviceable accessories with new accessories, reassembling and make the street light fitting functional and refixing in existing location including three core copper PVC insulated conductor of 1 sqmm size (nominal area) of suitable length to connect the lumaniries to overhead conductor / existing lines complete all as specified and directed . Note : Spares part/material required for repair to street light fitting shall be measued and paid separtely under relevent items as supply only. |
| 2 | M&L for 1100 volts grade heavy duty cable PVC insulated and FR PVC rounded sheathed, copper conductor (flexible) industrial cable, conforming IS: 694 of size 1.5 sqmm 3 core laid along pole from junction box to light fitting complete all as specified and directed. Make : Polycab/Havells/KEI |
| 3 | S&F in replacement of street light driver of 25 watt to 50 watt, 230V,50Hz suitable for operation over voltage range of 140V to 270V by emoving from existing position complete all as specified and direcred by Engr-in-Charge.Make : Surya/Crompton/Havells/Philips/Wipro |
| 4 | S&F in replacement of street light driver of 55 watt to 100 watt, 230V,50Hz suitable for operation over voltage range of 140V to 270V by emoving from existing position complete all as specified and direcred by Engr-in-Charge.Make : Surya/Crompton/Havells/Philips/Wipro |
| 5 | M & L in for DK Thermoplastic cable junction boxes IP 65 with of size 300x200x105 of metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 2/4 core and fixed to the PSC/Steel Poles by means of suitable size of clamps with nut and bolts and incl provn for fixing 01 No. of single pole MCBs 6-32 amps,10KA and MCB TP 6-32 amps, 10 KA, ‘C’ series 01 No inside the box incl taking down old u/s junction box complete all as specified and directed. Make : Sintex/Hensal or equivalent approved by GE. |
| 6 | S&F Busbar Chambers 4 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts including necessary connection including taking down of old u/s bus bar completed all as specified and as directed. Make Havells cat part No IHBC010004 or equivalent make of SMC/Hensel |
| 7 | S&F in repairs Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. Make : Crompton,/Havells/Bajaj/Philips |
| 8 | Supply and Laying in replacement XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area16 sq. mm 4 core complete all as specified and directed. Make : MESCAB/HAVELLS/POLYCAB/GLOSTER/KEI |
| 9 | Excavation in trenches/ foundation in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed by Engineer-in- Charge. |
| 10 | Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed. |
| 11 | Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed. |
| 12 | M&L for sand cushioning to U/G cable in layers in trenches complete all as specified and directed. Note :- Only Puned layers shall be measured for payment |
| 13 | M&L for well burnt bricks, sub class 'B' bricks of size 250mmx125mmx75mm, best quality locally available laid flat dry in trenches for cable protection complete all as specified and as directed. |
| 14 | M&L for painting of steel tubular pole of any size , vertical complete with cross arms with one coat of aluminium paint after cleaning and preparation of surfaces of poles, cross arms, painting 30 cm wide Yellow and black strip on poles up to 1.5 mtr high above coping level and numbering of size 70mmx40mm by using stencil to the pole with black synthetic enemal paint (1st grade ) complete all as directed. |
| 15 | S&F in repair GI Pipes 25mm bore light grade in any position for protection of cable fixed at pole/laid under road , nallah, crossing walls under floors etc complete all as specified and directed.Make : TATA/BANSAL/JINDAL or equivalent |
| 16 | S&F in repairs automatic street/security light switch of rating 8 KW in three phase using nature switch for automatic switching of street lights based on lux level on nature light. The sensor (Nature Switch) along with suitable power contactor, MCB and supprot terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade special moulding compound (Polycarbonate) conforming to IP 54 complete all as specified and as directed. along with each contactor 25-32 Amps , Incoming-Outgoing MCBs (03 Nos each) rating : 32 Amps, circuit wiring min 10 sqmm. Model - SWADEEP - 02EC8KW3P. MAKE- 1.Nature-Nature Switch : Kakatiya Energy systems Pvt. Ltd / HEALER / BAJAJ / Havells 2.Contactor : BCH / L& T / Schneider 3.MCB : Hager / Schneider /L&T/C&S 4. Circuit wiring : Finolex / Polycab or equivalent. |
| 17 | Dismantling/taking up or down roof conductor/down conductor of aluminium strip any size/condition with insulators from the Bldg for replacement of insulator/conductor etc and segregating serviceable conductor for re-use at site and removal of unserviceable conductor and insulators from site of work all as specified and as directed. |
| 18 | Fixing only serviceable roof conductor/down conductor any type/size ron roof wall on porcelain or epoxy spacer insulator (insulator measured and paid separately under relevant item) all as specified and as directed. Note :- Rates quoted by the contractor are deemed to be included for cutting ,jointing pieces ofstrip with nut bolts etc., and Only good condition items retrieved under item No.17 will be supplied for fixing to the contractor) |
| 19 | S&F aluminum strip 25 x 3.15 mm complete with saddles and fixing screws for roof / down conductor on porcelain/epoxy spacer insulatoror fixed on GI Pipe all as specified and as directed (Spacer insulator measured and paid separately under relevant items) . Note :- Rates quoted by the contractor are deemed to be included for cutting ,jointing pieces ofstrip with nut bold etc. |
| 20 | S&F porcelain/epoxy white / brown / green spacer insulator with one GI stud bolt with nut and washer with necessary drilling for bolt hole for holding / fixing roof conductor / down conductor of lightning conductor complete all as specified and as directed. |
| 21 | Fixing only porcelain/epoxy white / brown / green spacer insulator with one GI stud bolt with nut and washer for holding / fixing roof conductor / down conductor of lightning conductor complete all as specified and as directed. (Note : Only good condition items retrieved under item No.17 will be supplied for fixing to the contractor) |
| 22 | S&F single pointed air termination aluminium rod 12-mm dia 300 mm long with fixing arrangement including dismantling of old unserviceable/ deshaped conductor and removed from site of work complete all as specified and as directed. |
| 23 | Fixing only single pointed air termination aluminium rod 12-mm dia 300 mm long with fixing arrangement complete all as specified and as directed. (Note : Only good condition items retrieved under item No.22 will be supplied for fixing to the contractor) |
| 24 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed by Engr-in-Charge. |
| 25 | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion all as specified. |
| 26 | S&F LED type 24 watt all in one Solar LED street light in aluminium Die cast housing with IP 68 protection lumen output> 3000 lumens with 30 LED chips of 1 watt each system efficiency should not less than 175 lumens /watt CRI -70(+/-%%) CCT -5700 K (+/-5%) UV stabilized polycarbonate cover for better should be used with battery capacity >170wh integrated MPPT charger with driver luminaire should have built in PIR sensor foxture tilt angle should be 0-15 degree adjustable input voltage -12V DC to 14V DC LED burnung hours should be >50000 Hrs @ L70 luminaire should have charging & discharging LED indicator with 110watt poly, solar PV module as per MNRE standard with RFID (25 years performance warranty) .Incl pole with light arm bracket. Note - Light should be with 5 Years warranty Make : Philips/Havells/RS Solar/Crompton |
| 27 | Supply and fixing Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Crompton Make : LPTO-40-CDL/M or equivalent in Havells/Philips or equivalent |
| 28 | Supply and fixing LED Bollard with robust design and efficient light distribution 10W 230 watt volts AC outdoor type with decorative with IP 65 protection with impact and corrosion resistant complete all as per Crompton Make : LBLSR-10-CDL or quivalent in Havells/Philips or equivalent |
| 29 | M & L for Plain Cement Concrete (1:3:6) mix type C2 (using 40 mm graded stone aggregate) in foundation, filling and mass-concrete etc for pole, stay etc all as specified and directed by Engr-in-charge. |
| 30 | M & L for Plain Cement Concrete (1:2:4) type B1 (using 20 mm graded stone aggregae) as in copping including necessary formwork, weathering, slightly rounded or chamfered angles, finishing of exposed surfaces of concrete to even and smooth without using extra cement all as specified and directed by Engr-incharge. Please Enable Macros to View BoQ information |
| 31 | M & L for Plain Cement Concrete (1:2:4) type B1 (using 20 mm graded stone aggregae) as in copping including necessary formwork, weathering, slightly rounded or chamfered angles, finishing of exposed surfaces of concrete to even and smooth without using extra cement all as specified and directed by Engr-incharge. Please Enable Macros to View BoQ information |