Defence Statutory Bodies & Commissions/Committees Closing in 1 days TDR #56017671

Tender For Repair / Replacement Of Star/Delta Starter, Lt Panel, Aviation Light, Dozing Plant And Associated E/M Works At Af Stn Udh Ur

Issued by Statutory Bodies & Commissions/Committees · GE (AF) STATION UDHAMPUR, Jammu and Kashmir
Tender Value
Ref. Documents
Estimated cost
Bid Submission
07 Jul 2026
1 days left
EMD
50000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
GE (AF) STATION UDHAMPUR → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Repair / Replacement Of Star/Delta Starter, Lt Panel, Aviation Light, Dozing Plant And Associated E/M Works At Af Stn Udh Ur

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 24-Jun-2026 CERTAIN CHANGES IN TENDER DCOUCS BOQ 07-Jul-2026

BOQ

Name of Work:- REPAIR / REPLACEMENT OF STAR/DELTA STARTER, LT PANEL, AVIATION LIGHT, DOZING PLANT AND ASSOCIATED E/M WORKS AT AF STN UDH UR
Sl. No. Item Description
1Supply, Installation and Fixing Floor Mounting MCC PANEL shall be OEM made out of GRP, Glass-fiber reinforced as per EN 14598-1-UP FR2 material with Protection class IP 66 in accordance with IEC 60529 and Color code RAL 7032 completely dyed in mass and box shall be made out of insulating, slow-burning and self-extinguishing composite (polyester + glass fiber) characterized with resistance to atmospheric agents (UV). Protection class II (EN 61140) when correctly installed on the base and Panel internal size should be not less than 800x600x300mm. GRP material shall be Anti-corrosive suitable for saline atmosphere and have ambient temperatures of -50°C up to +120°C, Flammability HB 40 a, b (EN 60695-11-10),V-1. Glow wire tested at 960°C/ 3 mm as per EN 60695-2-12. The dimensional stability under heat is more than 200 °C as per ISO 75 – 2 method A . The enclosure is Halogen-free, resistant to termites. GRP cabinet should withstand minimum Di-Electric strength of 130KV/Cm as per IEC 60243-1. FRP Not accepted. The Panel box shall have shall be equipped with GRP handle lock with THREE point locking mechanism and the provision to insert various type of locking cylinders provided to avoid unauthorized access. RoHS Directive (EU) 2015/863 (extension to directive 2011/65/EU),REACH Regulation (EC) no. 1907/2006. The Panel mounted on suitable MS Angle Stand Ground Clearance 450mm height and Copper Bus-bar with Heat Shrinkable Sleeves of capacity 100 Amp, wiring of Panel with suitable size of Copper Conductor Cable, Cable Glands , Thimbles, etc. having size of the Panel suitable for fixing the Items/Materials mentioned at here-in-below, complete all as specified and as directed . Make-Hensel/ABB/Siemens/Schneider. ( NOTE : GRP Panel shall be build from OEM Only)
2All as per item No 1.00 hereinbefore but (Location - SMC Bore Pump House, Air Force MT Pump House)
3INCOMER:
463 Amp, 4 pole MCCB, 25 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No,
5Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent)
6Set of LED type indicating lamps - 01 No
7OUTGOINGS:
850 Amp, MCCB TP 16 KA 415 V,with Spreader Links - 02 Nos. (LK Cat No. CM98944OOFO or equivalent. )
9Digital Soft Starter suitable for 20 HP motor, current Rating 28 to 32 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 01 Nos. ( Submersible Pump 20HP )
10MCB 40A TPN C-Curve Type - 2 Nos
11One Spear Compartment to be provided for Standby starter. (As per Soft Starter Size)
12All as per item No 1.00 hereinbefore but (Location - Near 153 Hanger Pump House, )
13INCOMER:
1463 Amp, 4 pole MCCB, 25 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No,
15Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent)
16Set of LED type indicating lamps - 01 No
17OUTGOINGS:
1850 Amp, MCCB TP 16 KA 415 V,with Spreader Links - 02 Nos. (LK Cat No. CM98944OOFO or equivalent. )
19Digital Soft Starter suitable for 20 HP motor, current Rating 28 to 32 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 01 Nos. ( Submersible Pump 20HP )
20MCB 40A TPN C-Curve Type - 2 Nos
21One Spear Compartment to be provided for Standby starter. (As per Soft Starter Size)
22Supply, Installation and Fixing Floor Mounting MCC PANEL shall be OEM made out of GRP, Glass-fiber reinforced as per EN 14598-1-UP FR2 material with Protection class IP 66 in accordance with IEC 60529 and Color code RAL 7032 completely dyed in mass and box shall be made out of insulating, slow-burning and self-extinguishing composite (polyester + glass fiber) characterized with resistance to atmospheric agents (UV). Protection class II (EN 61140) when correctly installed on the base and Panel internal size should be not less than 800x600x300mm. GRP material shall be Anti-corrosive suitable for saline atmosphere and have ambient temperatures of -50°C up to +120°C, Flammability HB 40 a, b (EN 60695-11-10),V-1. Glow wire tested at 960°C/ 3 mm as per EN 60695-2-12. The dimensional stability under heat is more than 200 °C as per ISO 75 – 2 method A . The enclosure is Halogen-free, resistant to termites. GRP cabinet should withstand minimum Di-Electric strength of 130KV/Cm as per IEC 60243-1. FRP Not accepted. The Panel box shall have shall be equipped with GRP handle lock with THREE point locking mechanism and the provision to insert various type of locking cylinders provided to avoid unauthorized access. RoHS Directive (EU) 2015/863 (extension to directive 2011/65/EU),REACH Regulation (EC) no. 1907/2006. The Panel mounted on suitable MS Angle Stand Ground Clearance 450mm height and Copper Bus-bar with Heat Shrinkable Sleeves of capacity 160 Amp, wiring of Panel with suitable size of Copper Conductor Cable, Cable Glands , Thimbles, etc. having size of the Panel suitable for fixing the Items/Materials mentioned at here-in-below, complete all as specified and as directed . Make-Hensel/ABB/Siemens/Schneider. ( NOTE : GRP Panel shall be build from OEM Only)
23( Phase - I , Main Pump House)
24INCOMER:
25125 Amp, 4 pole MCCB, 25 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No,
26Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent)
27Set of LED type indicating lamps - 01 No
28OUTGOINGS:
2950 Amp, Motor Protected MCCB TP 50KA 415 V,with Spreader Links - 04 Nos. ( LK Cat No. CM98944OOFO or equivalent.)
30Digital Soft Starter suitable for 20 HP motor, current Rating 28 to 32 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 03 Nos. ( Mono Block Pump 20HP, Cetrifugal Pump/submerical Pump ).
31MCB 10A TP C-Curve Type - 2 Nos for Dosing Pump.
322HP DOL Starter Contactor MNX-12, Relay MN2 (2-3.3Amp), Indicator Red & Green, Push Button Start Stop Complate Wiring with marking. - 2 Nos
33Supply, Installation and Fixing Floor Mounting MCC PANEL shall be OEM made out of GRP, Glass-fiber reinforced as per EN 14598-1-UP FR2 material with Protection class IP 65 in accordance with IEC 60529 and Color code RAL 7032 completely dyed in mass and box shall be made out of insulating, slow-burning and self-extinguishing composite (polyester + glass fiber) characterized with resistance to atmospheric agents (UV). Protection class II (EN 61140) when correctly installed on the base and Panel internal size should be not less than 1000x800x300mm. GRP material shall be Anti-corrosive suitable for saline atmosphere and have ambient temperatures of -50°C up to +120°C, Flammability HB 40 a, b (EN 60695-11-10),V-1. Glow wire tested at 960°C/ 3 mm as per EN 60695-2-12. The dimensional stability under heat is more than 200 °C as per ISO 75 – 2 method A . The enclosure is Halogen-free, resistant to termites. GRP cabinet should withstand minimum Di-Electric strength of 130KV/Cm as per IEC 60243-1. FRP Not accepted. The Panel box shall have shall be equipped with GRP handle lock with THREE point locking mechanism and the provision to insert various type of locking cylinders provided to avoid unauthorized access. RoHS Directive (EU) 2015/863 (extension to directive 2011/65/EU),REACH Regulation (EC) no. 1907/2006. The Panel mounted on suitable MS Angle Stand Ground Clearance 450mm height and Copper Bus-bar with Heat Shrinkable Sleeves of capacity 320 Amp, wiring of Panel with suitable size of Copper Conductor, Cable Glands , Thimbles, etc. having size of the Panel suitable for fixing the Items/Materials mentioned at here-in-below, complete all as specified and as directed . Make-Hensel/ABB/Siemens/Schneider. ( NOTE : GRP Panel shall be build from OEM Only)
34( Phase - II , Pump House )
35INCOMER:
36320 Amp, 4 pole MCCB, 36 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No,
37Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent)
38Set of LED type indicating lamps - 01 No
39OUTGOINGS:
40MCCB 40 to 100 Amp capacity current rating, as per required current rating capacity of Motor Protected MCCB TP, 50KA, 415 V,with Spreader Links - 05 Nos. (100 A -01, 80 A- 03 No, 50A- 01 Nos )
41Digital Soft Starter suitable for 40 HP motor, current Rating 52 to 60 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 01 Nos. ( Centrifugal Pump 40HP )
42Digital Soft Starter suitable for 30 HP motor, current Rating 40 to 45 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 03 Nos. ( Centrifugal Pump 30HP )
43Digital Soft Starter suitable for 20 HP motor, current Rating 28 to 32 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 01 Nos. ( Centrifugal Pump 20HP )
44Supply, Installation and Fixing Floor Mounting MCC PANEL shall be OEM made out of GRP, Glass-fiber reinforced as per EN 14598-1-UP FR2 material with Protection class IP 66 in accordance with IEC 60529 and Color code RAL 7032 completely dyed in mass and box shall be made out of insulating, slow-burning and self-extinguishing composite (polyester + glass fiber) characterized with resistance to atmospheric agents (UV). Protection class II (EN 61140) when correctly installed on the base and Panel internal size should be not less than 800x600x300mm. GRP material shall be Anti-corrosive suitable for saline atmosphere and have ambient temperatures of -50°C up to +120°C, Flammability HB 40 a, b (EN 60695-11-10),V-1. Glow wire tested at 960°C/ 3 mm as per EN 60695-2-12. The dimensional stability under heat is more than 200 °C as per ISO 75 – 2 method A . The enclosure is Halogen-free, resistant to termites. GRP cabinet should withstand minimum Di-Electric strength of 130KV/Cm as per IEC 60243-1. FRP Not accepted. The Panel box shall have shall be equipped with GRP handle lock with THREE point locking mechanism and the provision to insert various type of locking cylinders provided to avoid unauthorized access. RoHS Directive (EU) 2015/863 (extension to directive 2011/65/EU),REACH Regulation (EC) no. 1907/2006. The Panel mounted on suitable MS Angle Stand Ground Clearance 450mm height and Copper Bus-bar with Heat Shrinkable Sleeves of capacity 125 Amp, wiring of Panel with suitable size of Copper Conductor, Cable Glands , Thimbles, etc. having size of the Panel suitable for fixing the Items/Materials mentioned at here-in-below, complete all as specified and as directed . Make-Hensel/ABB/Siemens/Schneider. ( NOTE : GRP Panel shall be build from OEM Only)
45( Upper Camp - Pump House)
46INCOMER:
47125 Amp, 4 pole MCCB, 25 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No,
48Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent)
49Set of LED type indicating lamps - 01 No
50OUTGOINGS:
51MCCB TP 50 Amp, Motor Protected 16 KA 415 V,with Spreader Links - 02 Nos. ( LK Cat No. CM98944OOFO or equivalent.)
52Digital Soft Starter suitable for 15 HP motor, current rating 22 to 32 amp, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 02 Nos. ( Mono Block Pump 15HP )
53MCB 10A TP C-Curve Type - 2 Nos for Dosing Pump.
542HP DOL Starter Contactor MNX-12, Relay MN2 (2-3.3Amp), Indicator Red & Green, Push Button Start Stop Complate Wiring with marking. - 2 Nos
55MCB 32A TPN C-Curve Type - 2 Nos. Lighting Load & One Standby.
56Supply and fixing HDPE Pipe 100mm dia used to cabe protection all as specified and directed by Engr-in-Charge.
57Supply and fixing HDPE Pipe 50mm dia used to cabe protection all as specified and directed by Engr-in-Charge complete all as specified and directed by Engr-in-Charge.
58Supply, laying Jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core Confirming to IS7098 amended upto date complete all as specified and directed by Engr-in-Charge.
59Supply, laying Jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core Confirming to IS7098 amended upto date complete all as specified and directed by Engr-in-Charge.
60Supply, laying Jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4core Confirming to IS7098 amended upto date complete all as specified and directed by Engr-in-Charge.
61M & L for cutting of Road and Concrete surfaces upto 300 mm depth and 300 mm wide for laying of cable / pipe in any type of soil, returning and filling in and spreading, leveling, watering and well ramming in layers not exceeding 25cm thick removal of surplus soil and provision of 150 mm thick PCC type B-1, 1:2:4 with 20mm graded crushed stone aggregate on top layer all as specified and as directed by Engr in charge.
62M & L for PCC 1:3:6 type C2 with using 40 mm graded aggregate as fixing of LT panel including necessary work complete as specified and directed by Engr in charge.
63M&L for type PCC 1:2:4 type B-1 using 20 mm graded stone aggregate in coping for HT pole including necessary form work complete as specified and directed by Engr in charge. Please Enable Macros to View BoQ information
64M&L for type PCC 1:2:4 type B-1 using 20 mm graded stone aggregate in coping for HT pole including necessary form work complete as specified and directed by Engr in charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56017671
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 07-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Replacement Of Star/Delta Starter, Lt Panel, Aviation Light, Dozing Plant And Associated E/M Works At Af Stn Udh Ur
Basic Detail
Tender No GEAFU-44/2026-27
Bidding Type Tender
Location
City GE (AF) STATION UDHAMPUR
State Jammu and Kashmir
Key Dates
Publish Date 24 Jun 2026
Submission Date 07 Jul 2026
Open Date 01 Jan 0001
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 50000
Exemption Not Available
Document List
BOQ_864962.xls
d7b86ff6-3294-4eed-8fd6-1a8b3ea1ee90.html
TENDER44.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jun 24, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 07, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 1 day
Jul 07, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day

Tender Documents

Download All (ZIP) ↓
xls

BOQ_864962.xls

html

d7b86ff6-3294-4eed-8fd6-1a8b3ea1ee90.html

pdf

TENDER44.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders