| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER BAREILLY Name of Work: PROVISION OF 11 KV UNDERGROUND CABLE FROM MAIN POWER HOUSE TO EQUINE FEED PELLETING PLANT AT RTS & DEPOT HEMPUR UNDER GE (EAST) BAREILLY Contract No : CWE / BLY / GE(E) /32 OF 2026-27 Bidder Name : SCHEDULE A(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supply, install, testing and commissioning of step down transformer voltage rating HT11/0.433 KV,out door type of capacity 200 KVA, LEVEL 2, 3 Phase,4 Wire,50 Hz, 5 star rating, oil cooled, core type, floor mounted, Delta/star connected maximum losses as defined in vector group DYN 11, Double copper wound ONAN manual type off load tap changing facility on HT side to vary secondary voltage from minus 7.5 % to plus 7.5 % in steps of 2.5 % continuous rating of capacity 200 KVA incl cable box on both HT & LT side .The transformer shall be completed with all standard fittings and accessories, guages,first fill transformer oil as as per indication level etc and confirming to IS :1180 and fittings and accessories of transformers shall confirm to IS 3639-1996 as amended and duly mounted on rollers as per load bearing capacity of transformer and the transformer shall have the following fittings/accessories fitted complete all as specified and directed. |
| 3 | (a) Rating plate and terminal marking plate of HT/LT sides(b) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing(c) Lifting Lugs(d) Dehydrating silicagel breather(e) Oil level indicator with minium and maximum marking(f) Cooling Radiator(g) Thermometer pocket(h) Drain valve with plug or cover plate(i) Conservator tank(j) Oil filling hole with cover including funnel(k) Air release device(l) Thermometer 100 mm dia/stem type with metal guard having maximum temperature indication with resetting devices for transformer (m) Winding temperature indicator(n) Air release device for transformerNote 1:- Information plate /Technical data plate as laid down in para 15.2 and 15.3 as per IS. |
| 4 | Supply, laying & testing 11 KV (Earthed) grade cable XLPE insulated, screened, PVC bedded,galvanized steel strip or wire armoured, electric power cables (heavy duty ) with stranded aluminium conductor,11000 volts earth grade, of cross sectional area 3 core 95 sq mm complete all as specified and directed. |
| 5 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed. |
| 6 | Material and labour for steel tubular swaged poles complete with cast iron base plate,finial taper plug, bolts ,nuts screws as specified type 410 SP-55, 11 metres long for fabricating of 4 pole structure on 11 meter with two coats of red oxide two coats of silver paint for all iron channel/ angles and necessary bracings supports and includng complete all as specified and directed. |
| 7 | Material and labour for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending colt or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of red oxide primer coat and two coat of aluminuim paint all as specified and directed. |
| 8 | Supply and fix and in repair 11 KV out door type Air Break gang operated device of rating 400 Amps, triple pole, vertical type,mechanically operated, mounted on HT insulators and steel channel frame with operating machanism worked from ground level with GI tubing 25 mm dia medium grade with operating handle and locking arrangement including seven lever navtal lock and providing ACSR conductor jumpers duly crimped with lugs, connecting to existing 11 KV supply cad testing complete all as specified and directed. |
| 9 | M&L for Loop type insulator, Large size, with overall dimensions 90mm x 140mm, clearance of hole 25.5 mm with working pressure 11000 volts complete all as specified and directed |
| 10 | Supply and fix drop out fuse unit expulsion type for air break gange operated switch single pole mounted on and including insulators for 11KV working pressure fixed to and including MS channel with nut,bolts and washers etc, synthetic bounded fuse carrying tube complete with line taps and suitable for current carrying capacity upto 50Amps and testing complete all as specified and directed. |
| 11 | Material and labour for PCC 1:4:8 type D2 using (40 mm graded stone aggregate) for making good cutting portion, mass concrete, filling of foundations etc including necessary use and waste of form work complete all as specified and directed |
| 12 | Material and labour for PCC 1:3:6 type C2 using (40 mm graded stone aggregate) for making good cutting portion mass concrete, filling of foundations etc including necessary use and waste of form work complete all as specified and directed |
| 13 | Material and labour for XLPE insulated, LT armoured electric cable with aluminium stranded conductor 1100 volts grade ,cross-sectional area 300 sqmm;3.5 core laid in trenches/pipes/ducts/walls with necessary cable lugs and glands, nuts, bolts and washers etc and testing complete all as specified and directed. |
| 14 | Material and labour for Earthing complete with galvanised steel earth plate electrode 600mmX 600mmX 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 32 X 6 mm from earth electrode to test point/equipment or up to 7.5 metres whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate No 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade,GI funnel with wire mesh,including charcoal, salt packed all around the earth electrode plate in layers,PCC earth pit chamber 1:3:6 type C1,RCC cover 1:2:4 type B1,including excavation/ earth work in any strata and returning filling, removal of surplus soil and testing for required value complete all as specified and directed. |
| 15 | Supplying and laying reinforce precast concrete cable cover class HT, Type 1,flat, size 300mm x180 mm x 40 mm for protection under ground HT cable complete all as specified and directed |
| 16 | M&L for brick sub class 'B' old size brick and laid in trenches as in protection of UG cable complete all as specified and directed. |
| 17 | Supply and filling in and spreading unwashed river sand for cushioning and covering the under ground cables in trenches and punning to provide required cover complete all as specified in SSR Part-I and as directed. |
| 18 | Supply, installation, Testing and commissioning of three phase four wire 415 Volts outdoor type factory fabricated free floor standing type, including PCC foundation as per requirement of size (minimum), dust rain and vermin proof cubical type, LT panel board fabricated from angle iron frame of size 50x50x6 mm with 3.15 mm thick CRCA sheet with anti corrosive coating and finally expoxy polyester powder coating of flint grey shade (RAL-7032) fully compartmentalized design with 04 Nos of bus bars each made of high conductivity 99.9% pure copper of ETP cable/ insulated copper strip (including suitable Aluminium earth strips conforming to IS and all as specified with supply and fixing the following :- |
| 19 | Incommer:- (i) MCCB four pole, 400 Amps, 36 KA = 415 Volts adjustable thermal magnetic release type-01 no (incoming)(ii) Change over switch 4 poles, three phase 415 volts, 400 Amp complete.(iii) Digital Ammeter 0-400 Amp 96x96 mm with inbult slector -01 Nos(iv) Three indication lamps for three phases.(v) Bus bar chamber having insulated copper bus bar (color coded) each suitable for 630 Amps for three phases and neutral.Outgoing:- (i) MCCB four pole 400 Amps 36 KA 415 Volts 01. |
| 20 | Excavation in trenches not exceeding 1.5 mtr wide and not exc 1.5 mtr depth for laying of cables, pipe lines, protection pipes and foundations etc and getting out in soft/ loose soil complete all as specified and directed. |
| 21 | Returning filling in soil including spreading leveling watering and well rammimg in layer n exc 25 cm complete all as specified and directed |
| 22 | Removing excavated soil not exc 50 mtr ant depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 23 | Material & labour for GI pipe 100 mm \\"light grade\\" laid in trenches floors/on , pole/road for cable protection with all fittings complete all as specified and directed . |
| 24 | Boaring holes horizontally under road without damaging the surface of road (minimum 1.0 Mtr bellow the road surface) with the help of GI tubing of any dia not exc 80mm dia for passing of UG cable all as specified and as directed. |
| 25 | Surface dressing n.exc 15 cm deep soft/loose soil complete all as specified and directed. |
| 26 | M&L for plain cement concrete type D2 1:4:8 (using 40 mm stone aggregate) in foundations, filing & mass concrete complete all as specified and directed. |
| 27 | M&L for galvanised steel standerd stay wire of size 2.24 mm grade for stay of poles including necessary clamps of 50x6 mm of flat iron complete all as specified in electric 300x300x6 mm MS stay plate including thumble, GI stay wire 7/2.24 mm SWG of required with all as accessories complete all as specified and directed. |
| 28 | M&L for construction of transformer plateform as per manufacturer drawing/ instructions must have with mininimum size 2 mtr x 2 mtr x 1.5 mtr height. Top with interlocking tiles including packing, Brick work, filling hard core and PCC and also covered shead and fencing all around area with gate & locking arrangement with connected path complete all as specified and directed. Note : Working space must be available all arround the transformer plateform. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |