| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep and getting out in any type soil for laying pipes etc, complete all as specified and directed by Engineer-in-Charge. |
| 2 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm, complete all as specified and directed by Engineer-in-Charge. |
| 3 | Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by Engineer-in-Charge. |
| 4 | Supply and spread river sand in trenches for cable cushioning, complete all as specified and directed by Engineer-in-Charge.Note : Punned thickness shall be measured for payment purpose. |
| 5 | Supply and lay un reinforced Pre-cast Concrete cable cover class LV, type I, flat, size 250 mm x 150 mm x 40 mm, complete all as specified and directed by Engineer-in-Charge. |
| 6 | Supply, Laying, Connecting and testing of LT XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 Core complete including taking down old existing LT cable, complete all as specified and directed by Engineer-in-Charge. |
| 7 | Supply, Laying, Connecting and testing of LT XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 Core complete including taking down old existing LT cable, complete all as specified and directed by Engineer-in-Charge. |
| 8 | Supply, Laying, Connecting and testing of LT XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 Core complete including taking down old existing LT cable, complete all as specified and directed by Engineer-in-Charge. |
| 9 | Material and labour for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth strip protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing including taking out old unserviceble GI earth plate & strip of any description, complete all as specified and directed by Engineer-in-Charge.Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II |
| 10 | Material and labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required with 32 X 6 MM GI strip complete including taking down of existing earth strip of any description, complete all as specified and directed by Engineer-in-Charge. |
| 11 | Material and labour for 80 mm dia, light grade galvanized iron (GI) pipes with necessary fittings, laid in trenches / fixed to walls and ceilings or laid in floors complete for passing of Earth strip complete complete including taking down of old existing pipe, complete all as specified and directed by Engineer-in-Charge. |
| 12 | Material and labour for 50 mm dia, light grade galvanized iron (GI) pipes with necessary fittings, laid in trenches / fixed to walls and ceilings or laid in floors complete for passing of Earth strip complete complete including taking down of old existing pipe, complete all as specified and directed by Engineer-in-Charge. |
| 13 | Material and labour for cutting of existing bitumen road / foor/CC road / PCC hard standing up to 45 cm depth and 45 cm width for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying/fixing of pipes, complete all as specified and directed by Engineer-in-Charge.Note:- The unit rate quoted shall be inclusive of excavation, earth work in any type of soil/hardstanding/flooring. |
| 14 | Design, fabricate, supply, installation, testing and commissioning of outdoor type cubicle panel board with inside panel suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 3 mm thick for outer shell and 2mm thick for inner shell with front openable door with two point locking arrangement i.e. Key locking system & pad-locking. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50 mm x 50 mm x 6 mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 900 mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C1 using 20mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Board(01 No) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring with suitable gauge of copper cables complete including taking down of old existing LT panel, complete all as specified and directed by Engineer-in-Charge :- Incoming :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole, 250 A, breaking capactiy 50kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 01 No (b) Digital Voltmeter with selector switch - 01 No(c) Digital Ammeter with selector switch - 01 No(d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 Outgoing :-(a) MCCB AC 3 Phase 415 V, 50Hz 4 pole,100 A, breaking capactiy 25kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 05 Nos |
| 15 | Design, fabricate, supply, installation, testing and commissioning of outdoor type cubicle panel board with inside panel suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 3 mm thick for outer shell and 2mm thick for inner shell with front openable door with two point locking arrangement i.e. Key locking system & pad-locking. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50 mm x 50 mm x 6 mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 900 mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C1 using 20mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Board(01 No) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring with suitable gauge of copper cables complete including taking down of old existing LT panel, complete all as specified and directed by Engineer-in-Charge :- Incoming :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole, 250 A, breaking capactiy 50kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 01 No (b) Digital Voltmeter with selector switch - 01 No(c) Digital Ammeter with selector switch - 01 No(d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 Outgoing :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole,100 A, breaking capactiy 25kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 06 Nos |
| 16 | Design, fabricate, supply, installation, testing and commissioning of outdoor type cubicle panel board with inside panel suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 3 mm thick for outer shell and 2mm thick for inner shell with front openable door with two point locking arrangement i.e. Key locking system & pad-locking. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50 mm x 50 mm x 6 mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 900 mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C1 using 20mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Board(01 No) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring with suitable gauge of copper cables complete including taking down of old existing LT panel, complete all as specified and directed by Engineer-in-Charge :- Incoming :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole, 250 A, breaking capactiy 50kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 01 No (b) Digital Voltmeter with selector switch - 01 No(c) Digital Ammeter with selector switch - 01 No(d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 Outgoing :-(a) MCCB AC 3 Phase 415 V, 50Hz 4 pole,100 A, breaking capactiy 25kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 04 Nos |
| 17 | Design, fabricate, supply, installation, testing and commissioning of indoor type cubicle panel board with inside panel suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick front openable door with two point locking arrangement i.e. Key locking system & pad-locking. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-43 degree of protection and including provision of 50 mm x 50 mm x 6 mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 900 mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C1 using 20mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Board(01 No) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring with suitable gauge of copper cables complete including taking down of old existing LT panel, complete all as specified and directed by Engineer-in-Charge :- Incoming :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole, 100 A, breaking capactiy 36kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 01 No (b) Digital Voltmeter with selector switch - 01 No(c) Digital Ammeter with selector switch - 01 No(d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 Outgoing :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole,63 A, breaking capactiy 25kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 04 Nos Please Enable Macros to View BoQ information |
| 18 | Design, fabricate, supply, installation, testing and commissioning of indoor type cubicle panel board with inside panel suitable for 3 phase 4 wire, 415 Volts, 50 Hz, AC supply system, factory fabricated in an approved factory having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick front openable door with two point locking arrangement i.e. Key locking system & pad-locking. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-43 degree of protection and including provision of 50 mm x 50 mm x 6 mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 900 mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C1 using 20mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Board(01 No) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring with suitable gauge of copper cables complete including taking down of old existing LT panel, complete all as specified and directed by Engineer-in-Charge :- Incoming :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole, 100 A, breaking capactiy 36kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 01 No (b) Digital Voltmeter with selector switch - 01 No(c) Digital Ammeter with selector switch - 01 No(d) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03 Outgoing :- (a) MCCB AC 3 Phase 415 V, 50Hz 4 pole,63 A, breaking capactiy 25kA, Ics=100% Icu with adjustable type thermal and magnetic setting relays - 04 Nos Please Enable Macros to View BoQ information |