| 1 | Heading |
| 2 | Supplying and laying of folowing sizes XLPE insulated PVC sheathed aluminium conductor armoured cable with necessary connection etc as reqd.working voltage 650 V / 1100 V Grade as per IS 1554 (part-I)/1988. (a) 2 Core 6 sqmm |
| 3 | (a) 2 Core 10 sqmm |
| 4 | Drawing of armoured/un-armoured cable with proper saddling etc. as reqd |
| 5 | Laying of 10 sqmm armoured cable in trench of 60cm depth and 30cm width i/c refilling the trench by protection of 2nd class of bricks, sands etc as reqd incl. necessary connection etc as reqd. |
| 6 | Supplying and stringing of 1.5 sqmm 3 core PVC sheathed and insulated copper conductor cable |
| 7 | Supplying of 30Watt LED Post Top lantern of make Surya/ Havells product RUBYNXTPT25WLED730PSYMTOPC HSNCode 9405clear cover offers illumination for different application. Llights will be selected as per choice of E.I.C. |
| 8 | Supplying of 35Watt LED Post Top lantern of make Surya / Havells product SPRINGNXTPT35W730SYMWHTTGGRY HSNCode 9405 clear cover offers illumination for different application. Llights will be selected as per choice of E.I.C. |
| 9 | Supplying and fixing of thermoplastic cable junction box with connector suitable for following sizes cable. a) 1.5 sq.mm -6 sq.mm cable |
| 10 | Heading. |
| 11 | Supplying & fixing of connector |
| 12 | Supplying & fixing of 8- way enclosure |
| 13 | Supplying & fixing of 63 Amps DP Isolator |
| 14 | Supplying and fixing of 5-32 Amps DP MCB |
| 15 | Supplying and fixing of 19/20mm dia PVC conduit (medium gauge ) with all accessories on slab/recessed on wall etc. as reqd. |
| 16 | Supplying and fixing of 40 mm dia PVC conduit (medium gauge ) with all accessories on slab/recessed on wall etc. as reqd. |
| 17 | supplying ,installation ,testing ,commissining of tottaly enclosed ,weather proof pedestal mounting cubical type,feederdistribution pillar box (of size H=1m,W=0.8m,B=0.6) fabricated out of 2mm thick M.S sheet with vertical & horizontal members of 35 mmx 35mm x 6mm angle iron work.Hinged detachable but locakable front door, to be mounted on block masonary /cement concrete pedestal foundation ,including mounting the control gears on MS flat with procelin base support ,making connection / inter connection with single core sheeved solid / strip conductor of suitable cross section ,painting letterings earthing etc & fixing in the wall by MS frame (suitable size) with i.e including 01 No 32 A TPN MCB incomer,single dial time switch,22 A TP contactor for the automatic switching of luminaries complete as reqd as per direction of site Engineer -in -charge |
| 18 | Earthing with G.I. earth pipe 4.5 mtr.long & 40 mm dia with necessary salt,charcoal & enclosure on top etc.as reqd. |
| 19 | Fitting and fixing charge of post-top fittings |
| 20 | Supplying & fixing of 50 mm dia 6\\" long GI pipe (MG) with base plate , nuts & bolts etc as reqd . Please Enable Macros to View BoQ information |