Tender For Restoration Of Rain Damages Of Lwss Harchakian Lapiana In Tehsil Harchakian, Distt. Kangra, (Hp) (Sh:- Construction Of Main Reinforced Cement Concrete Up Gradation Reservoir 50000 Ltr Cap. (Under Pdna). Estimated Cost- 600000/- Earnest Mon, Shahpur-Himachal Pradesh
TDR : 56011598
Tender Notice
BOQ
8 Days Left
Shahpur
Himachal Pradesh
Tender For Restoration Of Rain Damages Of Lwss Harchakian Lapiana In Tehsil Harchakian, Distt. Kangra, (Hp) (Sh:- Construction Of Main Reinforced Cement Concrete Up Gradation Reservoir 50000 Ltr Cap. (Under Pdna). Estimated Cost- 600000/- Earnest Mon
Name of Work:- Restoration of rain damages of LWSS Harchakian Lapiana in Tehsil Harchakian, Distt. Kangra, (HP) (SH:- Construction of main RCC U/G reservoir 50000 ltr cap. (Under PDNA). Estimated Cost- 600000/- Earnest Money- 12000/- Time Limit- Six Months
Sl. No.
Item Description
1
Design and Construction of RCC Under ground Reservior. of various capacity each, including cost of excavation, site development cost of construction material , necessary arrangement of inlet,outlet, over flow & scour pipe alongwith sluice valves , & other fixtures & fitting, and carriage of meterial within all leads and lifts. ( The design and Drawing shall be got approved from competent authority before execution )
2
RCC Under ground Reservior. of 50,000 Ltrs. Capacity.
3
Inlet pipe shall be provided by the department, however the Contractor / Firm shall have to make arrangements for connection the same with the tank with in all leads and lifts.
4
Providing and fixing of atleast 1 number manhole with CI cover 500 milimeter internal dia meter total weight of cover and frame to be not less than 110 Kg. ( medium duty ) the weight of cover and frame to be 56 Kg. each.
5
Cast iron ventilating pipe 150 milimeter dia with cowl and mosquito proof cover of sufficient length and lightening conductor as per site shall be provided by the contractor/ firm.
6
All other required accessories such as bell mouth control valves of cast iron class PN-1 one for each out let and occur system shall be supplied and fixed by the firm.
7
All the fitting shall be embeded in the structure while the work is in progress. All connections shall be left out side the structure with sluice valves of appropriate class and specification in position ready for connection with incomming and outgoing pipes . direction of the scour shall be made towards natural drainage as per direction of Engineer-in-charge.
8
The safe bearing capacity of the soil shall be got tested by the contractor, however for design purpose. The safe bearing capacity shall not be more than 10 tonne per square meter. The design and drawing for the structure shall be supplied by the contractor/firm and shall be got approved by the competent authority before execution of the work.
9
The work shall be executed as per techinical specification attached in the NIT and direction of Engineer-in-charge . All the surrounding shall be levelled and make good and brought in proper shape as per direction of Engineer-in-charge.
10
All the pipe fitting , valves and other specials shall be ISI marked and confirm to relevant BIS codes and also shall be subject to the approval of Engineer-in-charge. Please Enable Macros to View BoQ information