| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified and as directed. |
| 2 | Returning filling in excavated soil upto a depth of 30 cm after riddling of excavated soil (in lieu of sand) for cushioning of cable and refilling of trenches with left over normal excavated soil including spreading, levelling, watering and well ramming in layers complete all as specified and as directed. |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. |
| 4 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size 250mm x 150mm x 40mm complete all as specified and as directed. |
| 5 | M&L for Plain Cement Concrete 1:4:8 type D2 (using 40mm graded stone aggregate) in foundation complete all as specified and as directed. |
| 6 | M&L for Plain Cement Concrete 1:3:6 type C1 (using 20mm graded stone aggregate) for stay and coping for poles including necessary form work to exposed surface finished smooth and even complete all as specified and as directed. |
| 7 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc.for protection of UG cable complete all as specified and as directed. |
| 8 | M&L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine including GI pipe of 50/80/100mm dia suitable for 0.4mpa working pressure complete all as specified and as directed. |
| 9 | Boring of holes under road, pavement, hardstandinig by trenchless technology using ultrasound technique and necessary maching including HDPE pipe of 63mm dia suitable for 0.4 mpa working pressure. |
| 10 | S&F AC Distribution box with socket three phase, 63A , 5P, 415V including plug and socket, TPN 63 AMP complete all as specified and directed. Make : C&S/ Havells/ABB/ Indoasian/ its equivalent approved by GE. |
| 11 | M&L for point wiring in PVC concealed conduit as required at site of size confirming to IS 2079-1973 medium grade on surface with PVC insulated unsheathed multistranded copper conductor cable (FRLS) 1.5 sqmm nominal cross sectional area 1100 volts grade with all fittings such as elbows, bends, junction boxes, saddles including PVC board (ISI Mark) and screws and rawal plugs including 1.5 sqmm PVC insulated & unsheathed copper conductor cable as earth wire and connected to light/fan & common earth dolly with necessary copper thimbels all as specified and directed for One light/bell/ fan point controlled by one ,one way switch complete all as specified and directed. |
| 12 | All as per item No 11 above but one socket outlet 5 pin 5/6 Amps on independent board controlled by one, one way switch. |
| 13 | All as per item No 11 above but one socket outlet 5 pin 5/6 Amps on same board with other one, one way switch. |
| 14 | All as per item No 11 above but for socket out let, 15/16 Amps on independent board with 4 Sqmm size cable and 2.5 Sqmm for continuity earth wire connected to common earth dolly all as specified and directed. |
| 15 | M&L for point wiring using approved colour coding as per IS with stranded copper conductor 1.5 Sqmm (Nominal area), single core, ZHFR/HFFR, PVC insulated and unsheathed stranded cable, 1100 volt grade, ISI -694 marked and FIA approved in and including heavy duty, steel concealed conduit, ISI marked and its fittings for One light point controlled by one switch/one fan point/one bell or buzzer controlled by one switch & fan regulator complete all as specified and as directed. |
| 16 | M&L for point wiring using approved colour coding as per IS with stranded copper conductor 1.5 Sqmm (Nominal area), single core, ZHFR/HFFR, PVC insulated and unsheathed stranded cable, 1100 volt grade, ISI -694 marked and FIA approved in and including heavy duty, steel concealed conduit, ISI marked and its fittings for One socket outlet 5/6 Amps on independent board controlled by one switch complete all as specified and as directed. |
| 17 | S&F switch flame proof rotary type with termination box in LM6, 16A single pole 250V complete all as specified and directed. |
| 18 | S&F flame proof switch socket and plug combined in LM6 cable termination box in LM6 16A , 250 V, 2P+ earth rotary type with termination box in LM6A single pole 250V complete all as specified and directed. |
| 19 | M&L for point wiring in PVC casing & caping all as required at site of size confirming to IS 2079-1973 medium grade on surface with PVC insulated unsheathed multistranded copper conductor cable (FRLS) 1.5 sqmm nominal cross sectional area 1100 volts grade with all fittings such as elbows, bends, junction boxes, saddles including PVC board (ISI Marked) and screws and rawal plug including 1.5 sqmm PVC insulated & unsheathed copper conductor cable as earth wire and connected to light/fan & common earth dolly with necessary copper thimbels for One light/bell / Fan point controlled by one, one way switch complete all as specified and directed. |
| 20 | All as per item No 19 above but one socket outlet 5 pin 5/6 Amps on independent board controlled by one, one way switch. |
| 21 | All as per item No 19 above but one socket outlet 5 pin 5/6 Amps on same board with other one, one way switch. |
| 22 | All as per item No 19 above but for socket out let, 15/16 Amps on independent board with 4 Sqmm size cable and 2.5 Sqmm for continuity earth wire connected to common earth dolly complete all as specified and directed. |
| 23 | S&F Modular metal flush/PVC terminal boxes with lumina plate and frame suitable for 3 module complete all as specified and directed. |
| 24 | S&F Modular metal flush/PVC terminal boxes with lumina plate and frame suitable for 4 module complete all as specified and directed. |
| 25 | S&F Modular metal flush/PVC terminal boxes with lumina plate and frame suitable for 6 module complete all as specified and directed. |
| 26 | S&F Modular metal flush/PVC terminal boxes with lumina plate and frame suitable for 8 module complete all as specified and directed. |
| 27 | S&F Switch modular type single pole one module, 6 Amps complete all as specified and directed. |
| 28 | S&F Switch modular type single pole one module, 16 Amps complete all as specified and directed. |
| 29 | S&F Socket outlet modular type, multipurpose, 2/3 pin, single pole two module, 6 Amps complete all as specified and directed. |
| 30 | S&F Socket outlet modular type, multipurpose, 2/3 pin, single pole two module, 6/16 Amps complete all as specified and directed. |
| 31 | S&F Modular bell push single pole one module, 6 Amps complete all as specified and directed. |
| 32 | S&F Modular blank plate one module complete all as specified and directed. |
| 33 | S&F Modular type stepped type electronic fan regulator 2 Module 230 Volts complete all as specified and directed. |
| 34 | S&F call bell Ding Dong 230V, AC, single phase ISI marked complete all as specified and directed. |
| 35 | S&F in ceiling rose 2/3 terminals 65x25 mm dia poly carbonate isolated complete all as specified and directed. |
| 36 | S&F DB, SPN 8 way double door for MCB, 240 volt with 200 amps rated bus bar all as specified and directed. |
| 37 | S&F DB, TPN 4 way vertical type with single/three phase outgoing with provision for MCCB as incomer 415 volt with 200 amps rated bus bar complete all as specified and directed. |
| 38 | S&F MCB 6-32 amps, 10 KA, SP 240 Volt, 'C' series complete all as specified and directed. |
| 39 | S&F MCB 32-40 amps, 10 KA, DB 240 Volt, 'C' series complete all as specified and directed. |
| 40 | S&F MCB DP 63 Amps, 10 KA, DB 240 Volt, 'C' series complete all as specified and directed. |
| 41 | S&F MCB TPN 63 Amps, 10 KA, DB 240 Volt, 'C' series complete all as specified and directed. |
| 42 | S&F single pole and neutral sheet metal enclosure with a two pin and earth plug socket complete including one single pole MCB of 20 Amp, C Curve, 10 KA rupturing capacity complete all as specified and directed. |
| 43 | M&L for sub main wiring in PVC casing and capping of required size 2x6 sqmm PVC insulated multistrand copper conductor with 01x6 sqmm PVC insulated multistrand copper conductor FRLS as earth continuity wire all as specified and directed. Note:- For the purpose of payment two runs of 6 sqmm conductors and one run of 6sqmm conductor with casing caping will be measured as one length. |
| 44 | M&L for sub main wiring in PVC conduit of required size 2x6 sqmm PVC insulated multistranded copper conductor with 01x6 Sqmm PVC insulated multistrand copper conductor as earth continuity wire all as specified and directed. Note:- For the purpose of payment two runs of 6 sqmm conductors and one run of 6 Sqmm conductor with conduit will be measured as one length. |
| 45 | S&F Switch Socket Combination 2 in 1,3 pin 16 Amp including PVC gang box fixing screw ISI marked complete all as specified and directed. Make : Anchor/Legrand/HPL/Cona/its equivalent approved by GE |
| 46 | S&F Switch Socket Combination 2 in 1,3 pin 6 Amp including PVC gang box fixing screw ISI marked complete all as specified and directed. Make : Anchor/Legrand/HPL/Cona/its equivalent approved by GE |
| 47 | S&F LED street light fitting 70/72 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed. |
| 48 | S&F LED slim ROUND panel light fitting for surface ceiling light, 12 watt, colour white/warm white, pressure die cast aluminium luminaire in powder coated white finish, independent electronic driver and including connected with 3 core 23/0.0076 insulated copper wire from ceiling rose to fitting connector complete all as specified and directed. |
| 49 | S&F LED slim square panel light fitting, 36 Watt, 2x2 feet edge-lit luminaire suitable for arm strong/grid ceiling for low ceiling and including connected with 3 core 23/0.0076 insulated copper wire from ceiling rose to fitting connector complete all as specified and directed. |
| 50 | S&F LED light fitting four feet 20 watt, slim design, 230volts, Cool white/ warm white, indoor recess mounting with reflector and connector block complete all as specified and directed. |
| 51 | S&F LED flood light 210 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all specified and directed. |
| 52 | S&F LED light fittings 2x16W flame proof, CMRI certified recommended for gas/vapour group of IIA & IIIB, Zone 1&2 and IP 65 Protection with die cast aluminium housing with heat resistant toughened glass with LED tube light fixtures drivers, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed. |
| 53 | M&L for core cutting on stone wall/concrete wall for inserting of copper tube and flexible copper cable for fixing of outdoor unit and making good to the disturbed surfaces also matching with the existing surfaces complete all as specified and directed. |
| 54 | Supply, fixing, jointing and testing copper tubing with nominal diameter of 0.25 inch of suitable thickness for liquid line to connecting out door condensing unit and fan coil unit complete all as specified and directed. (for 1.5/2.0 TR split AC). |
| 55 | Supply, fixing jointing and testing copper tubing with nominal dia meter of 0.5 inch and 0.8 inch thickness including expanded polyethylene foam insulation tubing for external insulation of suction line for connecting outdoor condensing unit and fan coil unit complete all as specified and directed (For 1.5/2.0 TR split AC). |
| 56 | Supply and Charging of Freon gas R-22/R-410 for Ac's complete all as specified and as directed. |
| 57 | M&L for taking down split type air conditioner of capacity 1.5/2 TR from the existing location complete indoor/ outdoor unit, pumping down the refrigerant by disconnecting nut bolts of copper tubing. Removal of stand and refixing the same on the other location after carrying out servicing and repairs by replacement of minor spares ie replacement of Running / starting capacity, repair to PCB Plate, replacement of connecting cables, washing of indoor/ out door unit with pressure washer, gas charging and insulation of copper tubing complete all as specified and directed. Note : Replacement of following items will be measured and paid separately (i) Copper tubing (ii) gas charging (iii) Core cutting |
| 58 | S&F exhaust fan, steel body AC Single phase, 230V of size 300mm sweep with blades and frame and louvers complete all as specified and directed. |
| 59 | S&F exhaust fan made of sturdy engineering plastic complete with louvers shutters, voltage winding of sweep 250mm including making hole in wall of suitable size and making good disturbed surface complete all as specified and directed. |
| 60 | S&F wall mounted fan single phase, PVC body 300mm sweep voltage 230Volt, 50 Hz, 1200 RPM copper winding complete all as specified and directed. Make: Bajaj/ Crompton/ Havells/equivalent make approved by GE |
| 61 | S&F flame proof exhaust fan, single phase, metal body, 230 Volts, 50 hz, 1200 rpm copper winding including louver shutter complete all as specified and directed. |
| 62 | S&F Special standing seam fixture Clamp for Air terminal on Metal Structure -Site specific all as specified and directed. |
| 63 | S&F Vertical Air Termination Solid aluminium with Base-10 mm dia and 1000 mm long Air Termination Base tested for conditioning, Ageing Test & Lightning impulse current withstand test: 100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol, 3 mtr mast all as specified and directed. |
| 64 | S&F 8mm dia solid Aluminium Conductor for Down Conductor and tested as per IEC 62561- 2 conducted in the Govt. aggregated thirty party laboratory to meet the requirement of IS/ IEC 62305 all as specified and directed |
| 65 | S&F Aluminium conductor holding clamp suitable for fixing 8 mm Down Conductor, Conductor holder @ 1 meter distance should be tested as per IEC-62561-2 conditioning & Ageing test, conducted in the Govt. accredited thirty party laboratory to meet the requirement of IS/ IEC 62305 all as specified and directed. |
| 66 | S&F Standing Seam clamp:To hold 8 mm Al conductor at every 1m distance on the top roof without any drilling on roof, Installation can be made through simple fastening system, mainly used for seaming sheet roof application tested as per IEC-62561-2 for conditioning & Ageing test & conducted in the Govt. accredited Third party laboratory to meet the requirements of IS/IEC 62305 complete all as specified and directed. |
| 67 | S&F Cross splicer, should be tested for conditioning, Ageing Test & Lightning impulse current withstand test: 100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol all as specified and directed. |
| 68 | S&F Aluminium Straight Splicers for 8mm and 10 mm Conductor to meet the requirement of IS IEC 62305 tested for conditioning, Ageing Test & Lightning impulse current withstand test: 100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol all as specified and directed. |
| 69 | S&F Expansion Piece without connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations to be provided on conductors length over 20 meters to connect Solid Round Al. Conductor at both ends to meet the requirements of IS/IEC 62305 all as specified and directed. |
| 70 | S&F test link in order to disconnect the earth termination system for enabling measurements. SS Test Link To connect Round to Flat conductor all as specified and directed. |
| 71 | S&F Earth Electrode Cu Bonded Steel Rod 14.2mm dia x 3000mm-(250Microns); Eco Friendly rust proof heavy duty weather proof Polyethylene Earth Pit Chamber with following dimensions :254 mm dia (top), 330 mm dia (bottom) & 260 mm (height).;14.2 / OD SS Clamp Both Side; Carbon based backfill compound - 25 Kg - 02 bags all as specified and directed. Note for Item NO.62 to 71 (i) Earthing value should be constant for 15 years from the date of installation. Certification for the same to be obtained by the contractor from OEM and submitted to Engr In Charge before completion of work. (ii) In case the value are not found within limit ie less than 1 Ohm of Equipments, less than 5 for LA and power supply the same to be rectified by the contractor free of cost for 15 years .(iii) The following test certificate shall be submitted to Engineer In charge prior to supply of material : (a) Certificate for copper bonded electrode alongwith control number duly certified by CPRI (b) Short circuit withstanding capacity of the copper bonded rod from an independent laboratory (NABL accredited Laboratory) (c) Resistivity test certificate for the backfill compound from an independent laboratory (NABL accredited laboratory) (d) Contractor has to install the earthing in ring system in order to obtain desired value as mentioned in Ser No II of Note.(e) Rate quoted by the contractor for earthing deemed to inclusive of cost of Exothermic joints and cost for ring formation etc. nothing extra will be paid to the contractor. Make: JEF / Tirumala or approved make by E-in-C Branch/CE Southern Command. |
| 72 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 95 Sqmm 3.5 core complete all as specified and directed. |
| 73 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 70 Sqmm 3.5 core complete all as specified and directed. |
| 74 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and directed. |
| 75 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 35 Sqmm 3.5 core complete all as specified and directed. |
| 76 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 25 Sqmm 3.5 core complete all as specified and directed. |
| 77 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 16 Sqmm 4 core complete all as specified and directed. |
| 78 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 10 Sqmm 4 core complete all as specified and directed. |
| 79 | Supply and Lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty) 1100V grade with stranded aluminium conductor of size 10 Sqmm 3 core complete all as specified and directed. |
| 80 | M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick burried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip of size 32x6 mm up to a length of 7.5 mtr long by means of nuts, bolts, checknuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed. Note :(a) Earthing value should be less than 5 ohms.(b) If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision. |
| 81 | Supply, installation and commissioning LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coars of synthetic enamel paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 125 Amps 4 pole ,415 Amps, 50 Hz of breaking capacity 25 KA as incomer and 63 Amps MCCB 4 pole 16 KA-02 Nos as outgoing and 32 SPN outgoing -01 nos , RYP B Indicator , VAF Meter complete all as specified and directed. |
| 82 | Supply, installation and commissioning LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 125 Amps 4 pole ,415 Amps, 50 Hz of breaking capacity 25 KA as incomer and 63 Amps MCCB 4 pole 16 KA as outgoing , RYP B Indicator , VAF Meter complete all as specified and directed. |
| 83 | Supply, installation and commissioning LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 63 Amps 4 pole ,415 Amps, 50 Hz of breaking capacity 16 KA as incomer and 40 Amps MCCB 4 pole 16 KA-01 nos , 32 Amps SPN-02 Nos as outgoing , RYP B Indicator , VAF Meter complete all as specified and directed. |
| 84 | Supply, installation and commissioning LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 40 Amps 4 pole, 415 Amps, 50 Hz of breaking capacity 16 KA as incomer and 32 Amps SPN-02 Nos as outgoing, RYP B Indicator, VAF Meter complete all as specified and directed. |
| 85 | Fabricate, supply, install, testing and commissioning of LT panel Outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire suitable for accommodating the following accessories totally enclosed self supporting structure fully compartmentalized suitable for outdoor use with bottom cable entry with suitable cable glands made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1, foundation block with suitable monitoring arrangement for aluminium bus bars 300 Amps capacity, hinged door at front with suitable locking arrangement, provision of louvers at sides, CPRI approved, dust and vermin proof, powder coated and with following accessories suitable for incoming/outgoing arrangements complete all as specifed and directed:- (a) 4 Pole MCCB 125 Amp, 50 Hz, 415 V with rupturing capacity 25 KA-01Nos (b) Digital Ammeter-01 No(c) Digital voltmeter (0-500V)-01 Nos (d) CT's200/5- set of 3 No(e) LED type Indication lamps (RYB)-one setNote: (i) Contractor has to get the approval of drawings of LT panel from the Engr In Charge /GE before commencement of work. (ii) Switch gear and connected items should be of approved make. (iii) Bottom portion of panel should be 30cm above from the ground level. |
| 86 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 160 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following. INCOMING:- MCCB 4 pole 125 Amps 35 kA - 01 Nos OUTGOING:- MCCB 4 pole 40 Amps 16 kA - 01 Nos MCCB 4 pole 63 Amps 16 kA - 01 Nos MCB DP 32 Amps 10 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set for incoming MS work incl angle iron frame and PCC work Internal wiring including copper lugs. |
| 87 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 160 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following: INCOMING:-MCCB 4 pole 160 Amps 25 kA - 01 Nos OUTGOING:-MCCB 4 pole 125 Amps 16 kA - 01 Nos MCCB 4 pole 63 Amps 16 kA - 01 Nos MCB DP 32 Amps 10 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set for incoming MS work incl angle iron frame and PCC work Internal wiring including copper lugs |
| 88 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 160 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following:INCOMING:- MCCB 4 pole 125 Amps 35 kA - 01 Nos OUTGOING:- MCCB 4 pole 40 Amps 16 kA - 03 Nos MCCB 4 pole 63 Amps 16 kA - 01 Nos MCB DP 32 Amps 10 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set for incoming MS work incl angle iron frame and PCC work Internal wiring including copper lugs Please Enable Macros to View BoQ information |