| 1 | SCHEDULE 'A' PART-I: E/M WORKS |
| 2 | Supply, installation, testing and commissioning hi wall split units comprising of indoor and outdoor units including outdoor stands complete with cordless remote control unit and with in built air filter for better indoor air quality with minimum BE 5 star rating of capacity as shown complete all as specified and directed. |
| 3 | Supply and install Voltage Stabilizer for automatic operation,single phase naturally air controlled indoor type & designed for input variation between 170A to 250 V with output voltage stabilized at 240V with accuracy of +/- 2.5% and of capacity 4 KVA |
| 4 | M&L for sub main wiring with two run of 4.0 Sq. mm PVC un-sheathed, copper conductor cable, 1100 Volt, and one run of copper earth wire 4.0 Sq mm drawn through PVC concealed/surface conduict of 25 mm dia, complete all as specified. Note: Copper conductor 2 run and one run of copper earth wire along with PVC concealed conduict shall be measured as one length & Cutting of chases/walls and making good the disturbed surface are included in the rate. |
| 5 | Supply and Fixing copper tubing 24 guage of size 1/2\\" along with tubular insulation suitable for split AC complete all as specified and directed. |
| 6 | Supply and Fixing copper tubing 24 guage of size 1/4\\" along with tubular insulation suitable for split AC complete all as specified and directed. |
| 7 | S & F moduler sheet metal enclosure with single pole and neutral enclosure with a two pin and earth plug and socket complete with one MCB, SP, 20 Amps, 240 volts, 10 KA complete suitable for AC all as specified and directed. |
| 8 | Supply and fixing of Factory made sheet metal enclosure for DBs (Fixed flush to the wall), SPN, 240 volt, 8 Way, IP-42 protection with suitable Amp rated bus bar and 1.5 Sq. mm copper PVC sheathed cable for earth continuity and suitable for having MCB’s , complete all as specified. |
| 9 | Supply and fixing of MCB 6 to 32Amp, 240 Volt, SPN, breaking capacity 10 KA 'C' series, , complete all as specified |
| 10 | Supply and fixing of MCB 6 to 32Amp, 240 Volt, SP, breaking capacity 10 KA 'C' series, complete all as specified |
| 11 | Supply lay and testing of cable in trenches/walls XLPE insulated, armoured electric cable (heavy duty 1100volt grade with stranded aluminium conductor of size 10sqmm 2.0 core complete all as specified and directed by Engr-in-charge. |
| 12 | M&L Earthing complete with GI plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected with GI earth wire of 4 mm dia by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No 3, connected to earthing with DBs all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber,CI frame with CI 10mm thick cover, 20mm dia GI medium grade pipe for watering , and water funnel with wirw mesh, 20mm dia light grade GI pipe for protection of strip complete all as specified and testing on completion. |
| 13 | Supply anf fix non metalic rigid conduit 25 mm dia on wall/ceiling Including tee, bends and clamp complete all as specified and directed. Please Enable Macros to View BoQ information |
| 14 | Supply anf fix non metalic rigid conduit 25 mm dia on wall/ceiling Including tee, bends and clamp complete all as specified and directed. Please Enable Macros to View BoQ information |