| 1 | Supply of the following materials |
| 2 | Bimettallic Lugs 95mm2-10 |
| 3 | Bimettallic Lugs 185mm2-10 |
| 4 | Bimettallic Lugs 240mm2-10 |
| 5 | LT Grade Armoured cable , 4Cx185 Sq.mm |
| 6 | Erection of the following |
| 7 | Erection of cable trenches of depth upto 1.2m in soft soil including getting out the excavated soil dressing of sides and ramming of bottoms with and disposal of surplus excavated soil as directed within a lead of 50 mtr. Trench size:-Width-350mm, Height:-1200mm. |
| 8 | Filling available excavated earth(excluding rock) in trenches, sides of foundations etc in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering , lead upto 50 m Trench size width-350mm, height-1200m |
| 9 | Erection of 9 mtr length of PCC Pole at any kind of soil direct in earth including excavation, refilling and ramming etc. as required complete (1 /6 th of the length of the pole to be embedded in earth) . |
| 10 | Erection of Stay Set complete direct in earth with 16 mm. dia. 1.8 mtr. long painted stay rod, anchor plate of size 300 X 300 X 8 mm. thick, turn buckle of length 356 mm. with 300 mm. long threaded adjustable 16 mm. dia. MS rod , thimble, guy insulator as per IS specification, hot dip (heavy duty) galvanized stay stranded wire of size 7/2.5 mm. fastened with stay clamps as required. |
| 11 | Erection of MS Angle Cross arm,1.0 to 2.5 mtr. Long 65x65x6 mm(excluding the cost of Back clamp, Nuts & bolts) |
| 12 | Erection of MS Channel Cross arm,0.3 to 1.2 mtr. Long 75x40x40x6 mm(excluding the cost of Back clamp, Nuts & bolts) |
| 13 | Erection of MS Channel Cross arm,1.3 to 2.8 mtr. Long 75x40x40x6 mm(excluding the cost of Back clamp, Nuts & bolts) |
| 14 | Erection of MS Channel Cross arm,0.6 to 2.8 mtr. Long 100x50x50x6 mm (excluding the cost of Back clamp, Nuts & bolts) |
| 15 | Erection of 11 KV Pin insulator along with Pin |
| 16 | Erection of 11 KV Single Disc insulator set along with necessary fittings |
| 17 | Earthing with GI Pipe 2.5 mtr. Long and 40mm dia including excavation, refilling with alternate layer of Salt & Charcoals as per drawing |
| 18 | Erection of Danger Plate on OH Lines(11KV/415Volts) |
| 19 | erection of Protective guarding /Cross lacing for 415/240 Volts line by BY GI wire 98/10SWG as per technical specification , across road/river/telecom line etc. in horizontal/vertical formation complete with Spoot/Reel insulator. |
| 20 | Supply of 60kg salt & 55 kg charcoal[ for 1 pit] |
| 21 | Fabrication of Cross Arms by MS Channel/MS Angle as per specification |
| 22 | Laying and Stringing of 1KM (single conductor) ACSR 6/1/2.59 mm dia weasel including, hoisting and binding etc complete as required |
| 23 | Erection of 9KV,5KA single pole metal oxide gapless LA including necessary connection complete as per technical specification |
| 24 | Erection of 11KV DOF Unit set of three nos including necessary connection complete as per technical Specification (Excluding the cost of back clamp , nuts & bolts) |
| 25 | Erection of 11KV,200A GOS Unit set of three nos including necessary connection complete as per technical Specification (Excluding the cost of back clamp , nuts & bolts) |
| 26 | Installation/ positioning of 11/0.430 KV,3-phase 200 KVA to 250 KVA of Distribution Transformer on pole with necessary connection & fitting & fixing of all allied accessories components as required for complete in all respect for for energizing |
| 27 | Providing three phase service connection with laying PVC Cable from nearby Electrical Pole to premises upto 35mtr in length supported by G.I wire, Reel Insulator in/c fitting fixing of Energy Meter as required |
| 28 | Carriage of 9mtr long PCC pole by mechanical transport from site to workshop vis-a-vis, including loading,unloading and stacking as required upto lead range of 25KM [for maximum 4 pole |
| 29 | Carriage of 11/0.430,3-phase 200/250KVA DTR by mechanical transport from/site /store/workshop to worksite vis-a-vis including loading,unloading and placing on base as required a. Upto lead range 80KM |
| 30 | Laying of one number PVC insulated & Sheathed /XLPE Power Cable of 1.1 KV garade of following size direct in ground including excavation, sand cushioning, Protective covering and refilling the trench etc as required .Trench Size width -350mm,height-750mm/sand(coushioning): Height-250mm, width 350mm/ Protection: Double layer Bricks above 95Sq.mm upto 185 sq.mm |
| 31 | Laying of one number additional PVC insulated & Sheathed /XLPE Power Cable of 1.1 KV garade of following size direct in ground including excavation, sand cushioning, Protective covering and refilling the trench etc as required .Trench Size width -350mm,height-750mm/sand(coushioning): Height-250mm, width 350mm/ Protection: Double layer Bricks above 95Sq.mm upto 185 sq.mm |
| 32 | Fixing of Cut Out including all necessary accessories etc as required. |
| 33 | Supply of double door LT metering KIOSK Box of size 1250mmx1040mmx450mm made of 2mm MS Sheet on 5x50x6mm MS angle structure bus bar made of copper strip size 500mmx50mmx6mm with locking system and painting for LT metering purpose i/c fitting fixing of Cut Outs cable and other related work. |
| 34 | Maintaining adequate clearance from overhead live conductors by Trimming of tree branches for way leaves |
| 35 | Supply of Erection of S/S Fencing as per specification |
| 36 | Civil work for construction of Transformer base and fencing of Hard drawn steel wire fabric as per requirement and direction of Engg.-in-Charge |
| 37 | Supply of fabricated clamps of assorted size of MS flat[50x6mm] with double coated of red oxide primer coating |
| 38 | Supply of MS nuts nuts & Bolts i/c washer of assorted size of ISI marked machine made |
| 39 | Carrying of Store materials loading, unloading materials |
| 40 | supply of 2.5 mtr long 40mm dia G.I Pipe Make:-TATA/JINDAL Please Enable Macros to View BoQ information |