| 1 | (i) Installation of a new 5MVA PTR (refer Annexure-1)Itemwise price should be filled in strictly as per the detailed Bill of Quantities at respective referred Annexure. |
| 2 | (ii) Construction of a 33 KV line from the 33/11 KV Dolopani Substation to the tapping point of the 33 KV Chapakhowa-AP Feeder to facilitate the LILO system (refer Annexure-2)Itemwise price should be filled in strictly as per the detailed Bill of Quantities at respective referred Annexure. |
| 3 | 33/11 KV 5 MVA Transformer with oltc &RTCC Panel |
| 4 | 33 KV C&R Panel for Transformer with differeential relay(numerical type & with Static TVM ) |
| 5 | 33 KV C & R Panel for feeder (with numerical relay & stetic TVM) |
| 6 | 33 KV VCB 1250A with GI mounting structure |
| 7 | 33 KV 0.5 Class 1ph Outdoor CT with GI mounting structure & marshaling Box (Set comprising of three units) 200-100/5-5-5A, 25kA for 3 sec |
| 8 | 33 KV 0.5 Class 1ph Outdoor CT with GI mounting structure & marshaling Box(Set comprising of three units) 400-200/5-5A, 25kA for 3 sec |
| 9 | 33kV/110V, 1ph Outdoor PT with GI mounting structure & marshaling Box (Set comprising of three units) |
| 10 | 11 KV XLPE Cable 1 Core 300 Sqmm ( Aluminium ) |
| 11 | 11 KV Cable Kit for XLPE 1 Core 300 sqmm (Indoor) |
| 12 | 11 KV Cable Kit for XLPE 1 Core 300 sqmm (Outdoor) |
| 13 | T' Clamp for 33kV Bay Connections (Wolf) |
| 14 | 33KV Isolator with earth blade GI Mounting Structure 800A |
| 15 | 33KV Isolator without earth blade GI Mounting Structure |
| 16 | 33kv 10KA Lighting Arrestor with Surge monitor(polymer) with GI Mounting structure |
| 17 | 33kv 10KA Lighting Arrestor with line type |
| 18 | Control cable copper 2 corex2.5sqmm |
| 19 | Control cable copper 4 corex2.5sqmm |
| 20 | Control cable copper 7 bcorex2.5sqmm |
| 21 | Control cable copper 10 corex2.5sqmm |
| 22 | 33/0.433KV 100 KVA Transformer - Aluminium Wound |
| 23 | DTR Cubical for 100KVA DTRS(comprising of requisite one Micrprossessor based MCCB for incomming, three TM release MCCB for outgoing, Static TVM, CT, Vmeter,Ammeter etc.) |
| 24 | GI Channel Cross Arm (100x50x6x2800mm) |
| 25 | 33KV GOAB switch 400Amp |
| 26 | 33 KV DO Fuse Set 150A Assembly |
| 27 | PSC Pole 9.75m |
| 28 | HT Stay Set |
| 29 | GI Stay wire 7/14 SWG |
| 30 | 33 kV Guy insulator Porcelin |
| 31 | Bimettalic Lug 70 Sqmm |
| 32 | LT XLPE Cable 1 core 70sqmm (Armoured) |
| 33 | GI Nuts & bolts |
| 34 | Disc Insulator (Polymeric) 90kN (B&S Type) |
| 35 | Polymeric Pin Insulator (FRP 34mm) |
| 36 | H/W fitting for Disc Insulator B&S 90kN tension type |
| 37 | ACSR \\" RACCON\\" Conductor |
| 38 | Pole Clamp, GI flat 50 x 6mm |
| 39 | PG Clamp for ACSR Wolf |
| 40 | PG Clamp for ACSR Raccon |
| 41 | Transformer pad for 5MVA complete as per specification |
| 42 | Grouting & mufflering of PSC of 9.75 Mtr using PCC |
| 43 | Stay Grouting with PCC & Boulder |
| 44 | Transformer Pad |
| 45 | DTR fanching as per REC standard specefication complete with materials and labour |
| 46 | RCC foundation for PT, CT |
| 47 | RCC foundation for VCB |
| 48 | RCC foundation for 33KV Isolator as per standard drawing and technical specifications |
| 49 | RCC foundation for 33KV LA as per standard drawing and technical specifications(per No.) |
| 50 | Switch yard graveling of 0.15 mtr thickness by 40 mm size crushed stone |
| 51 | Construction of RCC switchyard Cable Trenches Size (750x775)mm including trays of MS/GI for cable including supply of all materials and installation of 75 mm RCC slab for cover as per specification and drawing |
| 52 | Construction of RCC switchyard Cable Trenches Size (1250x775)mm including trays of MS/GI for cable including supply of all materials and installation of 75 mm RCC slab for cover as per specification and drawing |
| 53 | Installation of earthing system with MS flats 50x10mm (for earthing mat) with GI flat riser 25x6mm (for earthing conductor) and GI pipe 50mm dia of length 3000mm for earth electrodes) including excavation of earth welding etc. as necessary |
| 54 | Earth filling with river sand including watering, leveling, compacting, grading etc. icluding payment of land compensation,forest royalty and other duties as per site condition and technical specification |
| 55 | Switch yard lighting (complete with 6 nos. of 40W LED bulb with structure and accessories) |
| 56 | GI Steel Tubular Pole SP-76 (14.50) |
| 57 | GI 33KV \\"V\\" Cross Arm with channel size 100x50x6mm |
| 58 | GI Channel Cross Arm (100x50x6x3200mm) |
| 59 | Polymeric Pin Insulator (FRP 34mm) |
| 60 | GI Top Cleat (100x50x6x350)mm for 33KV |
| 61 | Disc Insulator (Polymeric) 90kN (B&S Type) |
| 62 | Tension clamp for ACSR Wolf |
| 63 | H/W fitting for Disc Insulator B&S 90kN tension type |
| 64 | ACSR \\" WOLF\\" Conductor |
| 65 | Pole Clamp, GI flat 50 x 6mm |
| 66 | HT Stay Set |
| 67 | Guy Insulator (Porcelain) |
| 68 | Hot Dip GI Wire Stay Wire 7/10 SWG (For HT) |
| 69 | Jointing sleeve for Wolf |
| 70 | PG Clamp for ACSR Wolf |
| 71 | Hot Dip GI Wire 6 SWG |
| 72 | GI Nuts & Bolts with Washer(Assorted) |
| 73 | 33KV Danger Plate |
| 74 | GI Barbed wire Type A |
| 75 | GI Angle (50x50x6)mm |
| 76 | CI Earth Pipe 1.8m Inner dia 100mm, outer dia 110mm with perforated holes of 15mm dia at 30 cm interval along length of the pipe |
| 77 | 33kV 3-Ph 4-W Combined CT-PT Accuracy Class: 0.5, 600/5A, STC: 18.1 kA for 1 Sec, 600/5A |
| 78 | 3P4W ICS DLMS compliant HT Trivector energy meter (Category-C), √110/v3v -/5A Class 0.5s for consumer metering |
| 79 | Copper Control Cable, 10-C x 2.5sqmm |
| 80 | Grouting & mufflering of steel tubular pole of type SP-66 and SP-76 as per specification and drawing with minimum planting depth of 2.15 m (using PCC) |
| 81 | Grouting of Stay Set with PCC and Boulder Please Enable Macros to View BoQ information |