| 1 | Feeder Pillar Box : Design, Manufacture, testing, supply and commissioning of Double door outdoor type Distribution Feeder Pillar box (H x W x B) (1000mmx860 mm x 600mm approx ) conforming to Indian Standard IS : 5039- 1969 with latest amendments,suitable for use on 3 phase 4 wire, 400/440 Volts 50 Cycles A.C. Supply and shall be suitable to be fabricated as per design & drawing to be approved by EIC. The Enclosure shall provide Degree of protection IP -66 respective Indian standard (IS). [Manufacturer/Fabricator having Test Certificates from CPRI]The body will be fabricated with 3mm thick MS plate, MS angle ( 40X40X5) & MS Flat ( 50X6 ). The top of the box will be fitted with a sloping canopy made out of 5 mm thick sheet steel. It will have double hinged door at the front and back with suitable locking arrangement (Godrej Type ) and provision for manual locking arrangement also. |
| 2 | Provision for Fixing WBSEDCL Meter : i) Hylam/Bakelite Sheet; size: 600mm x 600mm x 12mm (H x W x Thickness) ---- 1set.ii) 415v; 63A porcelain Kit Kat Fuse unit --- 3nos.iii) 415V; 63A nuutral link --- 1 no. inter connection should be done by suitable Cu wire (mini. size 4 core, 16 sq. mm.). |
| 3 | Incomer : i) 415V, 63A, FP MCCB of Breaking capacity 25kA/35kA with adjustable thermal and fixed magnetic setting (Make – LK (L&T) / Havells / SIEMENS / ABB) -- 01 No.ii) Bus-Bar : Cu 4 bars 415V, 63A.iii) LED indicator Lamp (R/Y/B) - 03 nos.iv) Danger Board |
| 4 | Out Going:i) 415V, 16A FP Power Contactor (Make: LK (L&T) / Havells / Legrand / SIEMENS /ABB) -- 02 nos.ii) 415V, 16A FP MCB (Make: LK (L&T) / Havells / Legrand / SIEMENS / ABB) -- 02 nos.iii) Digital Astronomical Time Switch (Make –LK (L&T) / Havells / ABB / Siemens) -- 02 nos.iv) Auto Manual Selector Switch -- 02 nos.v) ON/OFF Push Button -- 04 nos.vi) ON/OFF LED Indication Lamp -- 04 nos. |
| 5 | Interconnection :-All interconnection between incoming main to Busbar are to be made with suitable size flexible pvc insulated multistranded single core Cu cable and the same between busbar to each outgoing MCBs with proper socketing of the end of each wire leads. |
| 6 | Earthing Arrangement :-A separate continuous aluminum earth busbar of appropriate size is to be painted at the inside bottom of the panel and run across the full load of the Feeder Pillar Box. All electrical equipment are to be properly earthed with suitable size G.I. strip. |
| 7 | The complete Feeder Pillar Box is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating. |
| 8 | Installation :-The complete feeder pillar box board is to be installed on suitable brick padestal as directed by the E.I.C. |
| 9 | Dismentling charge of damaged 9mtr. Swan neck type MS tubular pole & installation the same after minor repair with co's own tools and tackles |
| 10 | Erection of Single Steel tubular pole of length as given belowwith/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly |
| 11 | Providing CC (6:3:1) muffing 600x600x760 mm in size or equivalent size of cylindrical muffing above ground level around the pole base complete with 3 mm thick neatly finished cement plaster all round after dismantling the unserviceable muffing if necessary |
| 12 | Supplying & Fixing GI waterproof type looping cable box size200x150x100 mm deep having 4 mm thick comprising of 1 nos. 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint. |
| 13 | Supplying, installation, Testing & Commissioning of Street light LEDfixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range 0o to 50o C and working RH 10% - 90%,internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driverfor 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with type II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect and LED Chips of SMD mid tohigh-power (2.5 to 4 watt for 200 watt and above, as per required (LM- 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except LM80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. System lumen efficacy shall be as below:i)System lumen efficacy ≥135 lm/Watt 150 Watt Mandatory sample testing must be carried out as per terms and Conditions at the end of BOQ. (Make - Havells / Signify (Philips) / Wipro / Crompton / LT (Lighting Technologies) / Surya ) |
| 14 | Supplying and Drawing 1.1 kV 3 (three) core stranded 'FR' PVC insulated & sheathed 1.5 sqmm copper cable (Make - Polycab / Havells / RR Kabel / Gloster / KEI) |
| 15 | Supplying and delivery of following size Armoured cables XLPE/PVC insulated are designed for 1.1 kV Stranded Aluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and XLPE / FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.)[Make : Gloster/Havells/Polycab/RR Kabel/ KEI] |
| 16 | 4C X 50 sq. mm |
| 17 | 4C X 25 sq. mm |
| 18 | 4C X 16 sq. mm |
| 19 | 4C X 10 sq. mm |
| 20 | Laying of cable as below, on existing Cable Tray/ MS angle structure and binding with suitable size GI wire.Up to 50 sqmm |
| 21 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 22 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed |
| 23 | Laying only Cable upto 50 sqmm through existing RCC/Hume/ GI Pipe/open masonary trench for single, 2, 3, 3½ & 4 core |
| 24 | Cutting of RCC road of size 3\\"x6\\" depth by co's own tools & tackles for cable laying and mending good the damages to original finish. |
| 25 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/ PVC armoured cables as below as to GS. |
| 26 | 4C×50 mm² |
| 27 | 4C×25 mm² |
| 28 | 4C×16 mm² |
| 29 | 4C×10 mm² |
| 30 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. S&F solderless socket etc as per GS. |
| 31 | 4C×50 mm² |
| 32 | 4C×25 mm² |
| 33 | 4C×16 mm² |
| 34 | 4C×10 mm² |
| 35 | Supplying & fixing medium gauge GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as required. |
| 36 | 32 mm dia |
| 37 | 40 mm dia |
| 38 | S & fixing pole clamp (191mm dia) made from 40 mm x 4 mm thick MS flat to hold 2 nos. 32 mm dia. GI pipe on 9mtr pole with necy. Nut-bolts etc as per requirement. As per GS |
| 39 | S & Fixing MS column clamp made from 50mmx50mmx5mm equal angle and 50 mm x 5 mm thick MS flat having arrangement to fix 2 nos. PVC cable on the extended part of the clamp so that the cable can not be displaced from the original positions. The clamp is to be fixed around the 10\\" size cubical form concrete beam with necy. nuts-botls. As per GS |
| 40 | Making hole of 13 mm dia on the body of the pole for passing the wires from loop box to light fittings. |
| 41 | Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil |
| 42 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground levelBy ISI-Medium GI pipe. |
| 43 | Connecting the equipments body to earth busbar including S&F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. |
| 44 | Connecting the equipments body to earth busbar including S&F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. |
| 45 | Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 5 (Five) year (DLP) from the date of completion. 2) Total is rounded off to the nearest rupees. |
| 46 | Terms and Conditions:- 1) The warranty for the LED street light fittings of BOQ Item Sl. No. 6.00 has to be provided for 5 years by the manufacturer/OEM. 2) One light fitting against Item Sl. No. 6.00 as per direction of EIC, randomly selected from the supplied lot consisting of total material, will be tested as follows from NABL accredited Government Laboratory at the cost to be borne completely by the bidder. The test process should consist of following tests:-(i) Visual Examination (for physical dimensions confirmation as per GA Drawing, model no., wattage etc. (ii) Insulation resistance and electric strength. (iii) Resistance to dust and moisture (iv) Photometric test, (v) Endurance test, (vi) Humidity test, (vii) Drop test, (viii) Vibration test. (ix) Electrical parameters test (namely input power, input current, PF, THD, output power, output current and output voltage, (x) Surge test, xi) High voltage and Low voltage test, xii)Scratch test. If the test result is not fully complied with the specifiction, the entire lot of supplied LED street light fixtures will be rejected. Fresh supply from the same manufacturer shall not be accepted and test should be repeated for fresh supply from a different manufacturer within the mentioned make list. 3) The Agency must procure the materials from the Manufacturer / OEM or from their authorized Sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.(4) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted before execution of work. The Serial. Nos of theFittings must be mentioned in the Delivery challan on site along with the warranty certificate provided by the Manufacturer/OEM specifying the fittings with Serial number and date. 5) If any refurbished material is supplied and installed, penal action will be taken as per existing rules. Please Enable Macros to View BoQ information |