| 1 | Point wiring with multi-stranded copper conductor, single core, FRLSH PVC insulated and unsheathed cable, including FRLSH PVC insulated unsheathed stranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes, ISI MARKED, with 3 mm thick plastic/bakelight laminated sheet cover having necessary cutting for fixing switches/ sockets comprising the following: - |
| 2 | One light/fan/exaust fan point controlled by one switch (one way) of 6 Amp or one fan point controlled by one switch(one way) of 6 Amp & fan regulator etc. or for bell/buzzer with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit, complete all as specified and directed. |
| 3 | One Socket outlet of 3-pin/ 5-pin, 6 Amp, on the same board, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, complete all as specified and directed. |
| 4 | One Socket outlet of 3-pin/ 5-pin, 6 Amp, independent, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit,complete all as specified and directed. |
| 5 | Point wiring with multi-stranded copper conductor, single core, FRLSH PVC insulated and unsheathed cable, including FRLSH PVC insulated unsheathed stranded copper conductor cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes, ISI MARKED, with 3 mm thick plastic/Bakelight laminated sheet cover for One socket outlet three pin, 15/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable single core & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit, complete all as specified and directed. |
| 6 | NOTES: (a) Switch(es) & socket(s) shall be measured & paid for separately under respective item of Schedule 'A'. (b) GI boxes shall be fixed flush to walls in position with cement mortar (1:4) complete all as directed. |
| 7 | Point wiring with multi-stranded copper conductor, single core, FRLSH PVC insulated and unsheathed cable, including FRLSH PVC insulated unsheathed stranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes, ISI MARKED, with 3 mm thick plastic/bakelight laminated sheet cover having necessary cutting for fixing switches/ sockets comprising the following: - |
| 8 | One light/fan/exaust fan point controlled by one switch (one way) of 6 Amp or one fan point controlled by one switch(one way) of 6 Amp & fan regulator etc. or for bell/buzzer with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC casing & caping, complete all as specified and directed. |
| 9 | One Socket outlet of 3-pin/ 5-pin, 6 Amp, on the same board, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, complete all as specified and directed. |
| 10 | One Socket outlet of 3-pin/ 5-pin, 6 Amp, independent, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty casing & caping ,complete all as specified and directed. |
| 11 | Point wiring with multi-stranded copper conductor, single core, FRLSH PVC insulated and unsheathed cable, including FRLSH PVC insulated unsheathed stranded copper conductor cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes, ISI MARKED, with 3 mm thick plastic/Bakelight laminated sheet cover for One socket outlet three pin, 15/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable single core & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty casing & caping, complete all as specified and directed. |
| 12 | NOTES: (a) Switch(es) & socket(s) shall be measured & paid for separately under respective item of Schedule 'A'. (b) GI boxes shall be fixed flush to walls in position with cement mortar (1:4) complete all as directed. |
| 13 | Switch piano flush button single pole one way, 6 Amp, complete all as specified and directed. |
| 14 | Switch piano flush button single pole one way, 15/16 Amp, complete all as specified and directed. |
| 15 | Switch piano flush button single pole two way, 6 Amp, complete all as specified and directed. |
| 16 | Socket outlet multipurpose having provision for 2&3 pin, 6 Amp, flush type, complete all as specified and directed. |
| 17 | Socket outlet multipurpose having provision for two-in-one 3 pin 6 Amp & 3 pin 16 Amp, flush type, complete all as specified and directed. |
| 18 | Switch Socket combo of capacity 5/6 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 19 | Switch Socket combo of capacity 15/16 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 20 | Bell push single pole flush type, 6 Amp, complete all as specified and directed. |
| 21 | Ceiling rose, surface bakelite, 65 x 50mm, three terminals, complete all as specified and directed. |
| 22 | Lamp (angle) holder, insulated body, cord grip pattern, complete, all as specified. |
| 23 | Electric buzzer AC 230 volt, single pole, bell push button type complete, all as specified |
| 24 | Electric buzzer AC 230 volt, single pole, Ding Dong type complete, all as specified |
| 25 | Fan regulator (electronic) suitable for 48”/56” sweep fan, step type, single phase, complete all as specified. |
| 26 | Modular Switch flush type 6 Amps Single pole, one way, IN REPLACMENT, complete all as specified. |
| 27 | Modular Socket outlet, multi purpose, 2/3 Pin combined 6 Amps flush type, IN REPLACMENT, complete all as specified. |
| 28 | Modular Bell push flush type,6 Amp, IN REPLACMENT, complete all as specified. |
| 29 | Modular Socket outlet, multi purpose, 2/3 pin combined 16 Amps universal socket , IN REPLACMENT, complete all as specified. |
| 30 | Modular Switch 16 Amps SIngle pole, one way, IN REPLACMENT, complete all as specified. |
| 31 | Modular fan regulator step type, 2 module type, IN REPLACMENT, complete all as specified. |
| 32 | Sunction boxes U PVC body concealed in wall suitable for housing modular accessories, IN REPLACEMENT, of following sizes :- |
| 33 | Sunction boxes of Size (7 inch x 4 inch) |
| 34 | Sunction boxes of SIze (8 inch x 10 inch) |
| 35 | Hylem bakelite sheet and providing suitable hole on hylem sheet for fixing of swiches ,sockets and modular plates as per site requirement wall suitable for housing modular accessories including taking down the existing of following sizes:- |
| 36 | Hylem bakelite sheet of Size ( 5 inch x 5 inch) |
| 37 | Hylem bakelite sheet of Size ( 7 inch x 4 inch) |
| 38 | Hylem bakelite sheet of Size ( 8 inch x 5 inch) |
| 39 | Hylem bakelite sheet of Size ( 8 inch x 10 inch) |
| 40 | Hylem bakelite sheet of Size ( 9 inch x 11 inch) |
| 41 | Sub main wiring (with approved colour coding as per IS) with single core FRLSH PVC insulated flexible stranded copper conductor 1.1 KV grade (main cable: number of runs as indicated below along with single core FRLSH PVC insulated flexible stranded copper conductor 1.1 KV grade for earthing in conduits, with and including rigid non metallic PVC medium duty concealed conduit not less than 25mm dia complete all as specified for the following: - |
| 42 | 2 runs of single core of 1.5 Sq. mm main cable + 1 run of 1.5 Sq. mm earth cable complete all as specified and directed. |
| 43 | 2 runs of single core of 2 Sq. mm main cable + 1 run of 2 Sq. mm earth cable complete all as specified and directed. |
| 44 | 2 runs of single core of 4 Sq. mm main cable + 1 run of 4 Sq. mm earth cable. complete all as specified and directed. |
| 45 | 2 runs of single core of 6 Sq. mm main cable + 1 run of 6 Sq. mm earth cable complete all as specified and directed. |
| 46 | NOTES: (i) For payment purposes, total runs of main cable (each run of one running metre) as mentioned above and one run (one running metre) of earth cable shall be considered together as \\"1 RUNNING METRE\\" |
| 47 | Rigid non metallic, PVC concealed conduit, not less than 25 mm bore, medium grade, ISI marked, inclusive of all fitings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing acessories such as couplers, lock nuts, saddles, pipe hook etc. for sub main wiring and the like, IN REPLACEMENT, complete all as specified. |
| 48 | Rigid non metallic, PVC casing caping, not less than 25 mm bore, medium grade, ISI marked, inclusive of all fitings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing acessories such as couplers, lock nuts, saddles, pipe hook etc. for sub main wiring and the like, IN REPLACEMENT, complete all as specified. |
| 49 | Sheet metal enclosure for DB for fixing MCB’s, isolators with bus bar, neutral link, earth bar and din etc., having IP-43 protection, suitable for surface and flush mounting, complete all as specified comprising the following: - |
| 50 | SPN, 4 way with 100 Amp rated bus bar, 240 V,double door type |
| 51 | SPN, 8 way with 100 Amp rated bus bar, 240 V,double door type |
| 52 | TPN, 4 way with 100 Amp rated bus bar, 415 V,double door type |
| 53 | VTPN, 12 way with 250 Amp rated bus bar, 415 V,double door type |
| 54 | MCCB suitable for 415 volts AC supply, 50 Hz, 4 pole 200 Amp with over load and short circuit protection, adjustable thermal & adjustable magnetic release type, complete all as specified |
| 55 | MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 6 to 32 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 56 | MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 6 to 32 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 57 | MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 40 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 58 | MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 63 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 59 | MCB suitable for 240 volt AC supply, TPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 40 to 63 Amp, IN REPLACEMENT, complete all as specified and directed. |
| 60 | Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 16-32 Amp, 240 volt, breaking capacity not less than 10 kA, IN REPLACEMENT, complete all as specified and directed. |
| 61 | Blanking plate to cover unused space in DB's complete all as specified.. |
| 62 | Integrated LED tube light fitting 1x18/20 Watt, 6000K complete fitting with all accessories duly connection with three core flexible copper cable duly fixed on two nos of PVC square boxes IN REPLACEMENT, complete all as specified. |
| 63 | Integrated LED tube light fitting 1x9/10 Watt, 6500K complete fitting with all accessories duly connection with three core flexible copper cable duly fixed on two nos of PVC square box, IN REPLACEMENT, complete all as specified. |
| 64 | Retrofit LED tube light T-8 type, 1x20 Watt, 6500K in Polycarbonate body with extruded Al heat SInk for efficient heat dissipation IN REPLACEMENT, complete all as specified. |
| 65 | Batten for retrofit type LED tube T-8 Type upto 1x22 Watt, pre-wired for LED tube complete with all accessories duly connection with three core flexible copper cable and duly fixed on and including two Nos PVC square boxes IN REPLACEMENT, complete all as specified. |
| 66 | LED round light fitting 15W recess mounting type,6000k complete with driver duly connection with copper cable etc, IN REPLACEMENT, complete all as specified. |
| 67 | Wall light fittings suitable for LED bulb 9 watt with & including LED bulb of 9 watt, including connection with all necessary fixing accessories complete all as specified and directed |
| 68 | LED 36 watt recessed 600mm x 600mm, 6000K luminaire warm white which provides soft-light and glare free symmetrical illumination suitable for Armstrong/Grid Ceiling including LED driver and connection with 3 core copper wire incl all accessories, IN REPLACEMENT, complete all as specified. |
| 69 | Flame proof Twin T8 tube of LED light fitting 2 x 16 watt with & including LED tube 16W each, CMRI certified recommended suitable for gas/vapur of IIA & IIB and Zone 1& 2 having IP-65 protection with die cast aluminium housing with heat resistant toughened glass with driver, holder, connector etc complete suitable for fixation on wall/roof including connecting up with three core suitable size twisted flexible copper conductor, IN REPLACEMENT, complete all as specified and directed. |
| 70 | Taking down carefully ceiling fans, exhaust fans, wall mounted fans, cabin/table fans, flame proof ceiling fans for repair, transporting to workshop, opening and reassembling after including necessary cleaning greasing oiling etc, testing and depositing back to EM store yard of GE (AF) Darbhanga including necessary loading unloading and transporting etc. complete.NOTE: Supply only spares & rewinding of fan(s) shall be measured & paid for separately under respective items of BoQ. |
| 71 | Supply only the following items/ spares parts for item No.44 above, complete all as specified and directed. |
| 72 | Fan Clamp made of SS |
| 73 | Fan capacitor of 2.5 MFD |
| 74 | Fan capacitor of 3.15 MFD |
| 75 | Fan ball bearing of existing make |
| 76 | Gun metal bushes of existing make |
| 77 | Rewinding fan of any description with super enamelled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, oiling, greasing including replacement of bush/bearing, condenser, 'U' clamp with reel to the entire satisfaction of Engineer-in-Charge including taking out burnt winding wire after opening the ceiling fan and other unserviceable parts, of size: - |
| 78 | Ceiling fan 1200 / 1400 mm sweep |
| 79 | Exhaust fan 300 mm sweep |
| 80 | Exhaust fan 450 mm sweep |
| 81 | Ceiling fan complete with blades, down rods, stepped type electronic regulator and accessories, 230 volt, 1200mm sweep with service value 6.00 BEE five star rated with brushless direct current motor (BLDC) including PVC insulated and overall sheathed flexible 3 core 0.5 Sq.mm copper conductor cable complete all as specified. |
| 82 | Exhaust fan steel body of size 300mm sweep with louvers, 900 RPM 230 volts single phase AC supply complete with bolt, nuts and washer and including PVC insulated and overall sheathed flexible 3 core 0.5 Sq.mm copper conductor cable from ceiling rose to exhaust fan for giving connection complete all as specified. |
| 83 | Exhaust fan steel body of size 450mm sweep with louvers, 1200 RPM 230 volts single phase AC supply complete with bolt, nuts and washer and including PVC insulated and overall sheathed flexible 3 core 0.5 Sq.mm copper conductor cable from ceiling rose to exhaust fan for giving connection complete all as specified. |
| 84 | Exhaust fan sturdy engineering plastic body of size 250mm sweep with louvers, 1200 RPM 230 volts single phase AC supply complete with bolt, nuts and washer and including PVC insulated and overall sheathed flexible 3 core 0.5 Sq.mm copper conductor cable from ceiling rose to exhaust fan for giving connection complete all as specified. |
| 85 | Anti suicidal rod of 12 inch white / brown and making necessary connection and testing fan for smooth functioning & anti suicidal fan rod shall be manufactured with inbuilt spring so as to break and hang on spring when load on fan exceed 20 kg, Fan rod shall be tested and approved by Govt of india MSME lab complete including taking down existing fan rod any length as directed.MAKE:- Goldlife, manufactured by safe solution Mumbai or equivalent approved make. |
| 86 | Shifting of existing Air Conditioners any capacity from one palce to another place, any height/any floor as per requirnment of users any make and new re-installation and commissioning the unit including testing ofter gas charging complete |
| 87 | Maintenance, servicing cleaning of at site, cleaning of equipment with blower for removing dust checking the wiring, running capacitor, staring relay, overload relay, thermostat switches condenser motor, blower/condensor fan rectification of fault, connecting and testing on load complete for following:- |
| 88 | Window type room air conditioner 1.5 / 2 Ton capacity |
| 89 | Split type room air conditioner 1.5 / 2 Ton capacity |
| 90 | NOTE:- Replacement of spares or gas shall be measured and paid separately under respective item of BoQ |
| 91 | Window type air 1.5/2 Ton capacity conditioner compressor, IN REPLACEMENT, including soldering, welding, brazing as required including charging of refrigerant gas and oil in the exchanged compressor, making electric & mechanical connections of air conditioner etc with testing etc complete. |
| 92 | Split type air 1.5/2 Ton capacity conditioner compressor, IN REPLACEMENT, including soldering, welding, brazing as required including charging of refrigerant gas and oil in the exchanged compressor, making electric & mechanical connections of air conditioner, etc with testing etc complete |
| 93 | Re-winding of blower motor of Split type AC any make with supper enamelled copper winding wire of adequate size and gauge, varnishing, drying, baking & insulation paper including, IN REPLACEMENT, GM bushes/bearing, fixing and testing on load etc complete of following capacity:- |
| 94 | 1.5 Ton |
| 95 | 2 Ton |
| 96 | Blower motor 230 Volts, AC 50 Hz single phase complete with blower fan for split type room air conditioner 1.5 / 2Ton capacity of existing make and size, IN REPLACEMENT, complete for following:- |
| 97 | Out door unit split type AC |
| 98 | Indoor unit split type AC |
| 99 | Running capacitor 36-50 mfd 400 volt IN REPLACEMENT complete. |
| 100 | Starting relay for air conditioner any capacity, IN REPLACEMENT, complete |
| 101 | Thermostatic switches for any capacity for window/split type AC, IN REPLACEMENT, etc complete. |
| 102 | Charging gas of air conditioner for following:- |
| 103 | R-134a |
| 104 | Cooling coil complete made of copper for Split type room air conditioner 1.5 / 2 Ton capacity, IN REPLACEMENT, complete. |
| 105 | Condensing coil complete made of copper for Split type room air conditioner 1.5 / 2 Ton capacity, IN REPLACEMENT, complete. |
| 106 | Blower assembly for indoor unit, IN REPLACEMENT, for following capacity:- |
| 107 | Split type AC 1.5 Ton |
| 108 | Split type AC 2 Ton |
| 109 | Remote kit (PCB plate) split type AC 1.5/2 Ton capacity, IN REPLACEMENT, complete |
| 110 | Repair of remote kit (PCB plate) for window type/split type Ac of any capacity complete. |
| 111 | Copper Pipe including welding brazing of copper pipe, IN REPLACEMENT, complete. For following size:- |
| 112 | 5/8\\"( with sleeves) |
| 113 | 1/4\\"( with sleeves) |
| 114 | 1/2\\"( with sleeves) |
| 115 | 3/8\\"( with sleeves) |
| 116 | Swing motor for air conditioner indoor / outdoor1.5 / 2 Ton capacity complete. |
| 117 | REFRIGERATOR :- Unserviceable sealed unit compressor of Refrigerator any make & model and supply and fixing company New compressor of same make for Refrigerator soldering, welding, brazing as required including gas charging in the compressor, making electric & mechanical connections at site and testing on load etc complete entire satisfation of Engineer-in-charge for following size:- |
| 118 | Upto 175 litre capacity |
| 119 | Above 175 litre capacity |
| 120 | NOTE FOR SERIAL ITEM NO 69.01 TO 69.02:-(i) Unserviceable sealed compressor may be given with more than one cut. (ii) Unit rate include transportation to site of work & back as applicable. (iii) Cost of refrigeration gas & oil deemed to be included in the unit rates quoted by the contractor. (iv) Make of new items to be replaced shall be approved by GE. |
| 121 | Thermostatic switches for any capacity for Refrigerator IN REPLACEMENT, complete |
| 122 | Starting relay for Refrigerator, IN REPLACEMENT, complete |
| 123 | Maintenance, servicing & repair of refrigerator 165/175 litres capacity any make model cleaning the various components and replacement i. e Chill tray, Shelves, Freezer door, Door Gasket, Door Lock, Blub Holder & bulb and Food tray complete for following size :- |
| 124 | 165/175 litres capacity |
| 125 | 230/310 ltrs capacity |
| 126 | Spare part of domestic refrigerator IN REPLACEMENT all as sample complete for following :- |
| 127 | Defrost timer |
| 128 | Bimetal relay |
| 129 | Defrost heater |
| 130 | Fan motor assy along with fan blade |
| 131 | over load protection for refrigerator |
| 132 | PTC relay |
| 133 | Condenser line filter for Refrigerator, IN REPLACEMENT, complete |
| 134 | Refrigeration gas (Mefron/Refron) in returnable cylinder for following :- |
| 135 | F-22/R-22 |
| 136 | R-134 (a) /R-404 |
| 137 | DESERT COOLER :- Re-winding of blower motor of desert cooler any capacity any make with supper enamelled copper winding wire of adequate size and gauge, varnishing, drying, baking & insulation paper including replacement GM bushes/bearing, fixing and testing on load etc complete. |
| 138 | Running capacitor 4 mfd IN REPLACEMENT complete. |
| 139 | 15 mm dia PVC (heavy duty) pipe for desert cooler, IN REPLACEMENT complete. |
| 140 | Blower motor 230 Volts, AC 50 Hz single phase complete with blower fan for Desert Cooler of existing make and size, IN REPLACEMENT complete. |
| 141 | Blower fan blade complete for desert cooler, IN REPLACEMENT complete. |
| 142 | PVC insulated & sheathed stranded FRLS copper conductor three core cable 1100 Volts of size 1 sq. mm ( nominal area), IN REPLACEMENT complete all as specified. |
| 143 | Pump motor 1/26 HP (Tullu pump) 230 volts, single phase, 1440 RPM for desert cooler IN REPLACEMENT, complete. |
| 144 | Wood wool pad set suitable for desert cooler heavy duty IN REPLACEMENT, complete. |
| 145 | Starting capacitor 4 mfd for Desert Cooler IN REPLACEMENT, complete. |
| 146 | Selector switch combination of 4 switches(for low,med,high & pump on/off) for desert Cooler as per sample, IN REPLACEMENT complete. |
| 147 | Top Plug 3 pin 220 Volt 5 Amp, IN REPLACEMENT complete. |
| 148 | Maintenance, servicing & repair of water coolar upto 150 litres capacity any make model cleaning the various components and finding out the faults and replacement of required spares complete all as specified and directed |
| 149 | Supply only the following items/ spares parts for item No.87 above, complete all as specified and directed. |
| 150 | Fan Motor of rated capacity, SIngle phase, 230 Volts |
| 151 | Thermostat. |
| 152 | Push type chromium plated bib cock 15 mm SIze. |
| 153 | 451 mm long PVC connection with PTMT connectors. |
| 154 | PVC float valve 15 mm SIze. |
| 155 | 0.71 mm thick stainless steel tray alongwith PVC waste pipe, pipe clamp complete. |
| 156 | Starting capacitor 60 to 80 MFD capacity. MAKE- Epcos, Havells, Usha. |
| 157 | Running capacitor 10 MFD capacity. MAKE- Epcos, Havells, Usha. |
| 158 | Over load relay. |
| 159 | Removing the burnt/defective sealed compressor unit of any make from water cooler cap 40 ltr/hr or 80 ltr/hr by cutting of suction and discharge lines and un-screwing the foundation nuts supply and fixing of new sealed compressor unit etc by tightening foundation nuts with new fittings and connecting suction and discharge line with gas welding work etc complete. |
| 160 | Servicing of RO system of any type and capacity including replacement of required housing elbow and any other minor spares other than mentioned below complete all as specified and directed. Note- spare parts shall be measured and paid separetely. |
| 161 | Supply only the following items/ spares parts for item No.90 above, complete all as specified and directed. |
| 162 | Aqua TFC 100 Gpd membrane |
| 163 | Membrane houSIng |
| 164 | Yarn PP 20\\" complete all as specified and directed. |
| 165 | Willfread PP complete all as specified and directed. |
| 166 | Geyser:- Attending the complaints of non functional and preventive maintenance of storage type electric water heater (Geyser) of capacity 25/50 ltrs compriSIng of the following tasks at different locations of any make, incl Taking down storage geyser of any capacity after disconnecting electrical connection from existing socket, removing the bolts and nuts from wall and disconnected inlet and outlet water connection for repair/ replacing the unsv items and assemble the same after making serviceable, cleaning dust including connecting flexible 3 core cable as required, painting the geyser complete, with white colour synthetic enamel paint by spraying and filling cavaties with pillar, one coat after cleaning all dust, with proper filling of glass wool as heat reSIstance material, suitable quantity etc and refixing the geyser at it's original location complete all as directed spcified by Engineer-in-charge (Note- Spare parts of geyser shall be measured and paid separetaly as 'Supply Only' under relevant item) complete all as specified and as directed. |
| 167 | (a) Inspection of geyser after opening bottom cover plate.(b) Examine water tightness of storage tank.(c) Carry out operation of all stop cocks, pressure reducing valves, etc. to ensure free movement of the working parts.(d) Replace washers and glands of defective taps to ensure water tightness smooth functioning.(e) Inspect vent pipes and remove blockage obstruction if any.(f) Check and correct earth continuity of electrical items.(g) Check and correct temperature setting of thermostats and test its functioning.(h) Checking and adjustments of pressure reducing valves.(i) Checking of dead weight type high pressure release valve (PRV) by removing dead weight protection cleaning the seat and ensuring that the waste hole is not blocked / chocked.(j) Testing of Geysers after repairs/maintenance in all respect for proper functioning. |
| 168 | Supply only the following items/ spares parts for item No.93 above, complete all as specified and directed. |
| 169 | Heating element push type 1.5 KW (ISI Marked), |
| 170 | Heating element push type 2.00 KW (ISI Marked), |
| 171 | Heating element triangle type 1.5 KW (ISI Marked) |
| 172 | Heating element triangle type 2 KW (ISI Marked) . |
| 173 | Indicators of Geysers of any capacity/type |
| 174 | Glass wool for insulation of geyser of any type and capacity, IN REPLACEMENT, complete all as directed. |
| 175 | Thermostat ISI marked suitable for the Geysers 25 ltrs/ 50 ltrs capacity, 20 Amps, 240 Volts AC, adjustable type, 210 mm long or nearest Size as per sample, IN REPLACEMENT, complete all as directed. |
| 176 | Thermostat ISI marked suitable for the Geysers 25 ltrs. to 50 ltrs capacity,20 Amps, 240 Volts AC, fixed type,300 mm long or nearest Size, Set at 90+/-6 degreeC as per sample, IN REPLACEMENT, complete all as directed. |
| 177 | PVC connections pipe with brass hexagonal adapters both SIde suitable for 15mm dia pipe 60cm long for cold water as per requirement, IN REPLACEMENT, complete all as directed. |
| 178 | PVC connections pipe (braided coated) with brass hexagonal adapters both SIde suitable for 15mm dia pipe 45 cm long for hot water as per requirement, IN REPLACEMENT, complete all as directed. |
| 179 | PVC connections pipe (braided coated) with brass hexagonal adapters both SIde suitable for 15mm dia pipe 60cm long for hot water as per requirement, IN REPLACEMENT, complete all as directed. |
| 180 | Non-return valve 15mm / 20mm dia of brass ISI marked as per requirement, IN REPLACEMENT, complete all as directed. |
| 181 | PVC Sheathed multi stranded unarmoured copper conductor cable 1100 volt grade Conforming to IS 7098, 2.5 Sqmm 3 Core (Nominal Area), complete |
| 182 | Inner tank 25 litre capacity, made of stainless steel for water heater of exiting type, model, of following capacity, IN REPLACEMENT, complete all as specifed and as directed. |
| 183 | Apparatus plate along with Rubber Gasket suitable for water heater of 25 / 35 / 50 ltrs capacity having six/seven/eight/nine hole assembly of approved make including clips, nuts, bolts, and washers etc., IN REPLACEMENT, complete. |
| 184 | Safety valve for water heater IN REPLACEMENT, of capacity 25 / 35 /50 ltrs, complete. |
| 185 | VOLTAGE STABLIZER :- Automatic voltage stabilizer single phase 50 Hz complete with time delay relay and auto cut off in the event of low/high voltage and all as per the following parameters fixed IN REPLACEMENT:- (i) Incoming voltage 140 V to 200 V (ii) Stabilized voltage 230 +- 5% complete for following size:- |
| 186 | 3 KVA capacity |
| 187 | 5 KVA capacity |
| 188 | Re-winding of main transformer of voltage stabilizer with super enamelled copper winding wire of suitable gauge including making connection by soldering and testing etc complete of following size:- |
| 189 | 3 KVA capacity |
| 190 | 5 KVA capacity |
| 191 | Relay for voltage stabilizer 240 volts all as per sample and required at site IN REPLACEMENT, complete. |
| 192 | Volt meter 0-300 volts, fixed, IN REPLACEMENT, complete. |
| 193 | Amps meter 0-30 Amp, fixed ,IN REPLACEMENT, complete. |
| 194 | Timer circuit for voltage stabilizer IN REPLACEMENT all as per sample and required at site complete. |
| 195 | Connector porcelain type for voltage stabilizer, IN REPLACEMENT, complete. |
| 196 | Drain hose pipe of length 05 metre for Air Conditioners/Water Coolers, IN REPLACEMENT complete. |
| 197 | Metal clad socket with two Pin and earth & plug top with one MCB SP 240 volt 20 Amp, IN REPLACEMENT complete. |
| 198 | Attending day-to-day internal electrification complaints of power failure and carrying out repair works to restore the supply includes tracing and rectification of faults in lighting, fan and power circuits, short circuits, open circuits, earth faults, no light/no power complaints, loose connections, tripping of MCBs, dressing of Distribution Boards (DBs), tightening of terminals and electrical connections, checking continuity and insulation resistance, carrying out minor repairs to wiring and accessories, testing and restoration of electrical supply. The work shall also include attending complaints related to air-conditioning (AC) systems, such as no power supply to AC units including voltage stablizer, tripping of AC circuits, loose electrical connections, checking and restoration of electrical supply to AC units, water leakage from indoor units complete in all respects and as directed by the Engineer-in-Charge. |
| 199 | Notes: The Contractor shall arrange and provide all tools, plants, equipment and minor spares required for the execution of the work at its own cost. Contractor shall be responsible for providing an electrician and helper immediately on all working days including during night hours, to attend to and rectify the emergency complaints like short circuits and power failures etc. |
| 200 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete with batten, casing caping of MS or and PVC conduit on surface or concealed, including switches, ceiling roses, pendants, regulators, sockets, mild steel terminal boxes etc., removing materials and making good disturbed surfaces due to taking down etc. to the entire satisfaction of Engineer-In-Charge, complete all as specified and directed. |
| 201 | Taking down carefully copper/aluminium sub main wiring complete, including existing batten/conduit consealed/surface etc., removing materials and making good disturbed surfaces due to taking down etc. to the entire satisfaction of Engineer-In-Charge,complete all as specified and directed. |
| 202 | Dismantling of unservisible existing DBs of any description with all accessories and MCBs, isolators etc. and making good surface as per existing, complete all as specified. |
| 203 | Notes: Amount of credit for retrieved materials is mentioned in tender documents in pdf form which will be deducted while acceptance of tender offline. Please Enable Macros to View BoQ information |