| 1 | Excavation in trenches in soft/loose/hard/dense soil n.exc 1.5 mtr wide and n.exc 1.5 mtr deep & getting out soil for taking out/laying of cables etc.complete all as specified & directed by Engr-in-Charge. |
| 2 | Returning, filling in, including spreading, levelling watering and well ramming in layers not exc 25 cm.complete all as specified & directed by Engr-in-Charge. |
| 3 | Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above starting point all as specified and directed by Engineer-in-Charge. . |
| 4 | Supply and laying dry river sand laid in trenches 8cm below the cable and 15cm above the cable and punned to 18cm as cable cushioning and covering complete all as specified and directed by Engineer-in-Charge. (Note:- Punned thickness of sand cushioning will only be measured & paid in this item.) |
| 5 | Supply and laying of brick well burnt locally available sub class 'B' laid over sand cushioning for cable protection in trenches width of brick perpendicular to the length of cable, complete all as specified and directed by Engr-in-Charge. |
| 6 | M & L for road cutting of size (30x45) cm, width-30 cm and depth-45 cm depth for laying of cables incl making good the excavated road with necessary returning filling and bituminious pavement portion with concret and bituminious mix and cemented portion with PCC in 1:2:4 , 15 cm thick from top and matching the surfaces with existing all as directed. |
| 7 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm, 4.0 core as per IS 7098 incl. lugs/clamps to mount on walls/ ceiling/floors/other accessories necessary for installation incl. disconnecting and taking out old unsv cable, complete all as specified and directed by Engr-in-Charge. |
| 8 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sqmm, 3.5 core as per IS 7098 incl. lugs/clamps to mount on walls/ ceiling/floors/other accessories necessary for installation incl. disconnecting and taking out old unsv cable, complete all as specified and directed by Engr-in-Charge. |
| 9 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm, 3.5 core as per IS 7098 incl. lugs/clamps to mount on walls/ ceiling/floors/other accessories necessary for installation incl. disconnecting and taking out old unsv cable, complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm, 3.5 core as per IS 7098 incl. lugs/clamps to mount on walls/ ceiling/floors/other accessories necessary for installation incl. disconnecting and taking out old unsv cable, complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sqmm, 3.5 core as per IS 7098 incl. lugs/clamps to mount on walls/ ceiling/floors/other accessories necessary for installation incl. disconnecting and taking out old unsv cable, complete all as specified and directed by Engr-in-Charge. |
| 12 | M & L for galvanised light grade steel conduit of size 32 mm for cable protection, laying cables in road crossings/drain crossings, incoming and outgoing cable in junction boxes incl. all bends, elbows and fixing accessories such as couplers, lock nuts, saddles, holderbats, clamps, etc, complete all as specified & directed by Engr-in-charge. Make - Jindal/Tata or equivalent make as specified. |
| 13 | M & L for galvanised light grade steel conduit of size 40 mm for cable protection, laying cables in road crossings/drain crossings, incoming and outgoing cable in junction boxes incl. all bends, elbows and fixing accessories such as couplers, lock nuts, saddles, holderbats, clamps, etc, complete all as specified & directed by Engr-in-charge. Make - Jindal/Tata or equivalent make as specified. |
| 14 | M & L for galvanised light grade steel conduit of size 50 mm for cable protection, laying cables in road crossings/drain crossings, incoming and outgoing cable in junction boxes incl. all bends, elbows and fixing accessories such as couplers, lock nuts, saddles, holderbats, clamps, etc, complete all as specified & directed by Engr-in-charge. Make - Jindal/Tata or equivalent make as specified. |
| 15 | M & L for galvanised light grade steel conduit of size 80 mm for cable protection, laying cables in road crossings/drain crossings, incoming and outgoing cable in junction boxes incl. all bends, elbows and fixing accessories such as couplers, lock nuts, saddles, holderbats, clamps, etc, complete all as specified & directed by Engr-in-charge. Make - Jindal/Tata., complete all as specified & directed by Engr-in-charge. Make - Jindal/Tata or equivalent make as specified. |
| 16 | Supply, Installation, Testing & Commissioning of outdoor type LT Distribution Panel 415 V, 3-ph, 50 Hz of size not less than 0.6 (H) x 0.6 (W) x 0.4 (D) made out of CRCA sheet 3.15 mm thick outdoor totally enclosed with front & rear opening, hinged doors alongwith suitable locking arrangements, weather and waterproof having copper busbars of capacity 250 A for R,Y,B and Neutral with heat proof colour code and mounted on insulators, stickering of switchgears, danger notice plate, including connecting incoming and outgoing cables with 40 x 40 x 6 mm angle legs of length not less than 70 cm fixed to necessary PCC 1:3:6 foundation on ground comprising the following:-Incoming(a) MCCB 200A, 4P, 415 V, 50 Hz, Adjustable type with rupturing capacity of 36 KA -01 No. Make:L&T/ Havells/ Schneider/C&S electric(b) LED Indicating lamps (R,Y,B) - 01 set. Make: C&S/Neptune/L&T/Vaisnavo(c) Digital Three Phase VIF Meter with VLN, VLL, I1, I2, I3, F measurement -01 No. Make: L&T, Schneider, C&S electric(d) Socket outlet 2 in 1, 3 pin, 6 and 6A flush type-01 No.(e) MCB 6A, 'C' curve with breaking capacity 10kA-03 Nos.(f) CT 200/05, 5VA, cl-1.0-01 Set (03-ph)Outgoing(a) 04 Nos. threaded busbar (03 thread on each strip) of current carrying capacity 250A each with heatproof colour code for R, Y, B & N.(Note: Cost includes necessary power/control wiring connections, lugs/spreader links other accessories necessary for LT Panel construction) |
| 17 | Supply, Installation, Testing & Commissioning of outdoor type LT Distribution Panel 415 V, 3-ph, 50 Hz of size not less than 0.6 (H) x 0.6 (W) x 0.4 (D) made out of CRCA sheet 3.15 mm thick outdoor totally enclosed with front & rear opening, hinged doors alongwith suitable locking arrangements, weather and waterproof having copper busbars of capacity 200 A for R,Y,B and Neutral with heat proof colour code and mounted on insulators, stickering of switchgears, danger notice plate, including connecting incoming and outgoing cables with 40 x 40 x 6 mm angle legs of length not less than 70 cm fixed to necessary PCC 1:3:6 foundation on ground comprising the following:-Incoming(a) MCCB 160A, 4P, 415 V, 50 Hz, Adjustable type with rupturing capacity of 36 KA-01 No. Make:L&T/ Havells/ Schneider/C&S electric(b) LED Indicating lamps (R,Y,B) - 01 set. Make: C&S/Neptune/L&T/Vaisnavo(c) Digital Three Phase VIF Meter with VLN, VLL, I1, I2, I3, F measurement -01 No. Make: L&T, Schneider, C&S electric(d) Socket outlet 2 in 1, 3 pin, 6 and 6A flush type-01 No.(e) MCB 6A, 'C' curve with breaking capacity 10kA-03 Nos.(f) CT 200/05, 5VA, cl-1.0-01 Set (03-ph)Outgoing(a) 04 Nos. threaded busbar (03 thread on each strip) of current carrying capacity 200A each with heatproof colour code for R, Y, B & N.(Note: Cost includes necessary power/control wiring connections, lugs/spreader links other accessories necessary for LT Panel construction) |
| 18 | Supply, Installation, Testing & Commissioning of outdoor type LT Distribution Panel 415 V, 3-ph, 50 Hz of size not less than 0.6 (H) x 0.6 (W) x 0.4 (D) made out of CRCA sheet 3.15 mm thick outdoor totally enclosed with front & rear opening, hinged doors alongwith suitable locking arrangements, weather and waterproof having copper busbars of capacity 125 A for R,Y,B and Neutral with heat proof colour code and mounted on insulators, stickering of switchgears, danger notice plate, including connecting incoming and outgoing cables with 40 x 40 x 6 mm angle legs of length not less than 70 cm fixed to necessary PCC 1:3:6 foundation on ground comprising the following:-Incoming(a) MCCB 100A, 4P, 415 V, 50 Hz, Adjustable type with rupturing capacity of 16 KA-01 No. Make:L&T/ Havells/ Schneider/C&S electric(b) LED Indicating lamps (R,Y,B) - 01 set. Make: C&S/Neptune/L&T/Vaisnavo(c) Digital Three Phase VIF Meter with VLN, VLL, I1, I2, I3, F measurement -01 No. Make: L&T, Schneider, C&S electric(d) Socket outlet 2 in 1, 3 pin, 6 and 6A flush type-01 No.(e) MCB 6A, 'C' curve with breaking capacity 10kA-03 Nos.(f) CT 100/05, 5VA, cl-1.0-01 Set (03-ph)Outgoing(a) 04 Nos. threaded busbar (03 thread on each strip) of current carrying capacity 125A each with heatproof colour code for R, Y, B & N.(Note: Cost includes necessary power/control wiring connections, lugs/spreader links other accessories necessary for LT Panel construction) |
| 19 | Supply, Installation, Testing & Commissioning of outdoor type Busbar Panel 415 V, 3-ph, 50 Hz capacity made out of CRCA sheet 3.15 mm thick outdoor pedestal type of size not less than 1.2m(H) x 1.0m(W) x 0.5 m(D) totally enclosed with front & rear opening, hinged doors alongwith suitable locking arrangements, double sided retractable roof, weather and waterproof, verminproof and having copper busbars of capacity 400 A for phase R,Y,B with heat proof colour code and mounted on insulators, danger notice plate, including connecting incoming and outgoing cables, with 40 x 40 x 6 mm angle legs of length not less than 45 cm fixed to necessary PCC 1:3:6 foundation, for fixing XLPE, armoured 415V, 400sqmm, 3.5CxAl cable in panel, complete all as specified and directed by Engr-in-Charge. |
| 20 | Shifting of Existing outdoor distribution LT Panel after disconnection of all incoming and outgoing cable connections, unmounting and re-mounting to new position incl. dismantling of old deteriorated LT Panel followed by connecting new/old incoming and outgoing cables incl. necessary accessories for connection viz.. clamps, conduit etc. and necessary PCC foundation at footing, complete all as specified and directed by Engr-in-Charge. |
| 21 | Maintenance of existing LT Panels viz. replacing damaged/wornout Digital 3-ph VAF meters, LED indicator lamps, MCCBs, MCBs, etc and making necessary threads in busbars for connecting new cables and cutting holes in the panel plate for cable entry. Power cable/Control Cable incl. copper lugs/nut-bolts for connection of aforementioned items is deemed to be included in the quoted price.Note: Digital 3-ph VAF meters, LED indicator lamps, MCCBs, MCBs, etc will be measured separatedly under relevant serials. |
| 22 | S & F of Digital 3-ph VAF meter, VLN, VLL, I1, I2, I3, F, SMPS Auxiliary Supply (35-300 VAC/DC), programmable CT & PT Ratio, programmable 1A/5A site selectable, Accuracy class 0.5 & Voltage measurement range 50-520 V AC (p-p) for LT panels incl. necesary control cables with lugs complete, all as specified and directed by Engr-in Charge.Make: L&T/Risabh or equivalent make as specified. |
| 23 | S & F of resin cast CT set (set of 03), ratio 100/5A, burden 5VA, CL 1.0 after unbolting of busbars from LT panel and again fixing the busbars after mounting CT set and connecting the CT set to control cables complete, all specified and as directed. |
| 24 | S & F LED Indicator Lamp dia 22.5 mm, operating voltage-240 V AC in red, yellow or blue complete, all as specified and as directed. |
| 25 | S & F MCCB, 4P, 415V, overload adjustable 0.63 - 0.8-1 x in short circuit fixed 63 Amps breaking capacity 16KA complete all as specified and as directed. |
| 26 | S & F MCCB, 4P, 415V, overload adjustable 0.63 - 0.8-1 x in short circuit fixed 100 Amps breaking capacity 16KA complete all as specified and as directed. |
| 27 | S & F in repair MCB, SP, 240V, 6 to 32 Amps and ' C ' series breaking capacity 10 KA ISI marked complete, all as specified and as directed. |
| 28 | S & F in repair MCB TPN 415 V 16 to 32 A and 'C' curve series of breaking capacity 10 kA ISI marked, complete all as specified and as directed. |
| 29 | S & F in repair MCB TPN 415 V 40 to 100 A and 'C' curve series of breaking capacity 10 kA ISI marked, complete all as specified and as directed. |
| 30 | M & L for painting surfaces of existing LT panels with attached accessories with two coat of synthetic enamel paint after preparation of old painted surfaces including writing proper incoming and outgoing line details and painting the legs and channel/angle frames with existing colour complete, all as directed by Engr in Charge. |
| 31 | Supply & Fix of Aluminium Busbars (for R, Y, B & N phase-01 set) of size not less than 0.75 m for each phase, colour coded, bent to shapes for each phase suitable upto 11KV, 200A, 3- phase, 50 Hz conforming to IS:8084 incl mounting on existing porcelain/SMC/DMC insulators in existing LT panel incl. necessary nut bolts, threading, etc. complete all as specified & directed by Engr-in-Charge. |
| 32 | Supply and Fix double compression copper stainless steel gland for fixing armoured cable in panel of size 3.5 C x 16 Sqmm complete all as specified & directed by Engr-in-Charge. |
| 33 | Supply and Fix double compression copper stainless steel gland for fixing armoured cable in panel of size 3.5 C x 25 to 35 Sqmm complete all as specified & directed by Engr-in-Charge. |
| 34 | Supply and Fix double compression copper stainless steel gland for fixing armoured cable in panel of size 3.5 C x 50 to 70 Sqmm complete all as specified & directed by Engr-in-Charge. |
| 35 | Supply and Fix double compression copper stainless steel gland for fixing armoured cable in panel of size 3.5 C x 95 to 120 Sqmm complete all as specified & directed by Engr-in-Charge. |
| 36 | Supply and Fix double compression copper stainless steel gland for fixing armoured cable in panel of size 3.5 C x 150 Sqmm complete all as specified & directed by Engr-in-Charge. |
| 37 | Supply and Fix 16 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 38 | Supply and Fix 25 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 39 | Supply and Fix 50 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 40 | Supply and Fix 70 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 41 | Supply and Fix 95 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 42 | Supply and Fix 120 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 43 | Supply and Fix 150 Sqmm Al Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 44 | Supply and Fix 400 Sqmm Copper Cable Lugs complete all as specified & directed by Engr-in-Charge.Note: Not to be measured for ser 07 to 11. Will be measured when maintenance activity is carried out in existing cable separately. |
| 45 | S & F of Danger Sign Board sticker, not less than 10 cm x 10 cm size for LT Panels with following indicated on it:-\\"440 Volts Danger\\" in Red and Yellow/White complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 46 | S & F of Danger Sign Board sticker, not less than 10 cm x 10 cm size for LT Panels with following indicated on it:-\\"440 Volts Danger\\" in Red and Yellow/White complete all as specified and as directed. Please Enable Macros to View BoQ information |