| 1 | M&L for earthing complete with galvanised steel plate electrode 600x600x6mm thick buried directly in ground (top edge of the plate should not be less than 1.50Mtrs below ground level) connected to GI strip 25×4mm by means of bolts, nuts check nuts and washers of galvanised iron or steel connected to earthing test point all as specified incl 20 mm GI tubing medium grade and necessary fitting for protection of GI strip incl laying of charcoal dust and common salt in alternate layers of 150mm th, PCC chamber using PCC(1:3:6) type C-1 using 20mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally up to 150mm below ground level, GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on Electrical plate No.3 of SSR Part-I (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results (in white) on a black painted M.S. Plate (size 300x300x3mm th) duly welded with angle iron of size 40X40x5mm, 60cm long, fixed with the earth pit chamber by grouting complete all as specified and directed.Note :- (i) GI strip and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing.(ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for PCC chamber and PCC cover as per SSR part-1. |
| 2 | M&L in repair water level indicator gage of over head tank,replacement of copper float of size 200mm dia with 2mm thik flexible steel wire rope and replacement of level Scale painting of numbering, and replacement of gauge move pully complete accessory all as directed. |
| 3 | Supply fixing testing and commisioning of Automatic Star delta starter suitable for 15 HP, 3 Phase, 415 Volts motor including taking down old one complete all as specified and as directed by the Engineer-In-Charge. |
| 4 | S&F in repair contactor 3 pole,32 Amps 415 Volts suitable for 12.5 HP Auto Star Delta Starter ,complete all as specified and as directed by the Engineer-In-Charge. |
| 5 | S&F in repair Overload Relay of range 16 to 22 amps suitable for 3 Phase 15 HP Auto Star Delta Starter ,complete all as specified and as directed by the Engineer-In-Charge. |
| 6 | S&F in repair Single phase preventor complete all as specified and as directed by the Engineer-In-Charge. |
| 7 | S&F in repair timer switch for 3 Phase 15 HP Auto Star Delta Starter ,complete all as specified and as directed by the Engineer-In-Charge. |
| 8 | Disconnecting and taking out /lifiting out existing non-functional 2/3 HP capacity submersible/Mono-block centrifugal/Chiloronem plant motor, set of any description and in any position, dismantling and strip opening of pumps for servicing /overhauling, cleaning, oiling / greasing, fixing of serviceable parts in position, removing & replacement of defective / unserviceable parts with new parts and re-assembling the pump, fixing/lowering, in position, connecting to existing system and testing at site on full load to the entire satisfaction of the Engineer-in-Charge complete all as specified and directed. Note: - (i) The replacement of defective / non-functional parts shall be measured & paid for separately as “Supply only” under appropriate item of Sch ‘A’ and fixing rate for new items are deemed to include under these item.(ii) The rates for above items are deemed to include for transportation of pumps/ motors to and from workshop as approved by Engineer-in-charge for necessary repairs, alignment and testing of pump and motors at workshop replacement of necessary unserviceable screws/nuts /bots/washers/ packing etc.(iii) Burnt out windings of motor shall be replaced, measured and paid for separately under appropriate item of Sch ‘A’ for re- winding.(iv) Turning/ polishing of the rotor shaft shall be measured and paid seperately |
| 9 | All as per item no. 8 above but, for capacity 0.25/1.5 HP, single phase, of any make & any discription complete all as specified and as directed. |
| 10 | Taking out and removing old burnt out windings of the 2/3 HP, three phase, 415 Volts, 50 Hz, AC supply Induction motor of mono block booster pump/single phase submersible pumpsets and rewinding of motor with existing size PVC insulated copper conductor as approved by the Engineer-in-charge including cleaning the slots with carbon- tetra-chloride solution before rewinding ,transportation to site, fixing in position & testing on full load complete all as specified and directed. |
| 11 | All as per item No. 10 here in before but of capacity 0.25 / 1.5 HP, Single phase, of any make & any description complete all as specified and as directed. |
| 12 | Supply only CI impeller for multistage booster pump |
| 13 | Supply only CI impeller for centrifugal pump |
| 14 | Supply only CI gland bush with pump for booster pump/centrifugal pump |
| 15 | Supply only Cast iron gland plate for booster pump / centrifugal pump |
| 16 | Supply only Stainless steel main shaft |
| 17 | Supply only PVC Fan along with fan cover |
| 18 | Supply only Ball Bearing No 6202 for Induction motor & booster pump of any description, any capacity compete all as specified and directed. |
| 19 | Supply only Ball Bearing No 6205 for Induction motor & booster pump of any description, any capacity compete all as specified and directed. |
| 20 | Supply only Ball Bearing No 6206 for Induction motor & booster pump of any description, any capacity compete all as specified and directed. |
| 21 | Supply & fixing 100/150 mm dia Pressure gauge range 150kg/cm compete all as specified and directed. |
| 22 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep, in any type of soil including forming sides and bottom surfaces to required level / slope / gradients etc for taking down/laying of the pipe lines complete all as specified and directed at site.Note: The disturbed surfaces of roads/paths/plinth etc shall be made good by the contractor to match with the existing surfaces without any extra cost). |
| 23 | Returning, filling in, excavated soil in trenches, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed. |
| 24 | Removing of excavated surplus soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 25 | Disconnecting and taking down old existing steel tubing and connections of any description/ grade and in any position in trenches/under floors / on walls etc including all fittings/accessories and fixtures such as bends, union, elbow socket etc, all as directed and specified for the following sizes :- |
| 26 | 80 mm bore |
| 27 | 50 mm bore |
| 28 | 40 mm bore |
| 29 | 25 mm bore |
| 30 | 20 mm boreNote applicable for item no 25:- Excavation & earth work shall be measured and paid separately under respective item of Sch 'A'. |
| 31 | Supply, laying, jointing and testing galvanized iron water tubing, medium grade, including all necessary GI fittings /accessories laid in trenches complete all as specified and directed for the following sizes |
| 32 | 80mm bore |
| 33 | 50 mm bore |
| 34 | 40 mm bore |
| 35 | 25 mm bore |
| 36 | 20 mm bore |
| 37 | Disconnecting and taking down old existing cast iron/DI pipe line/ water main and connections of any description/ grade including lead if any and in any position in trenches/under floors / etc including all fittings/accessories and fixtures such as bends, union,elbow socket etc, all as directed and specified for the following sizes :- |
| 38 | (a) 150 mm bore |
| 39 | (b) 100 mm bore |
| 40 | Supplying ,laying, jointing & testing in trenches ductile iron pipes with spigot and socketed ends centrifugally cast (spun cast) class K-9 suitable for Titen joints complete all as specified and directed for the following size:- |
| 41 | (a) 150 mm bore |
| 42 | (b) 100 mm bore NOTE :- Earth work, and CI specials/ fittings of the pipes shall be measured and paid for separately under respective item of Schedule `A'. |
| 43 | S&F in repair for ISI Marked, gun metal globe/gate valve with iron wheel head, both ends screwed for iron pipe complete all as specified and directed for following bore of pipes:-- |
| 44 | 50 mm bore |
| 45 | 40 mm bore |
| 46 | 25 mm bore |
| 47 | 20 mm bore |
| 48 | 15 mm bore |
| 49 | M & L for Bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and directed for the sizes :-15mm dia bore |
| 50 | Supply, installation, fixing, jointing and testing, ISI Marked, cast iron sluice valve of class PN-1.6 conforming to IS-14846 of 2000 both ends flanged with iron wheel head and stainless steel spindle, jointed with and including jointing material such as rubber or fibre gasket, nuts, bolts washers etc and tested including taking down old sluice valve complete all as specified and directed for following bores :- |
| 51 | 150 mm bore |
| 52 | 100 mm bore |
| 53 | 80 mm bore |
| 54 | S&F in repair 100mm bore, ISI Marked, cast iron non return valve, both ends flanged jointed and tested complete all as specified and directed |
| 55 | S&F in repair 80 mm bore, ISI Marked, cast iron non return valve, both ends flanged jointed and tested complete all as specified and directed |
| 56 | Supplying, fixing, jointing and testing cast iron/ductile iron specials/fittings such as bend, tee, socket, color, Reducer, Tail Pieces etc. suitable for spigot and socketed/ flanged end pipes upto 150 mm bore complete all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |