| 1 | BOQ (Special repair replacement to street lights system and conversion of LT over head lines to under ground at Certain location and special repair to electrical wiring in certain buildings alongwith connected items at AF Station Suratgarh) |
| 2 | Supply and laying LT UG XLPE insulated 1100 volt grade heavy duty cable, multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel strip wire or tape and connecting up to the electrical system with suitable size of aluminium lugs cable of size 25 sq mm 4 core as per IS:7098 (Part-I). Complete all as speciifed and as directed. |
| 3 | Supply and laying LT UG XLPE insulated 1100 volt grade heavy duty cable, multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel strip wire or tape and connecting up to the electrical system with suitable size of aluminium lugs cable of size 35sq mm 3.5 core as per IS:7098 (Part-I). Complete all as speciifed and as directed. |
| 4 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth for laying of cables and getting out of complete all as specified and directed by Engineer-in-charge. |
| 5 | Returning, filling in, including spreading leveling, watering and well ramming in layer not exc 25 cm in soft/ loose soil, complete all as specified and directed. |
| 6 | Removing excavated material to a distance not exc 50m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified. |
| 7 | M&L Brick of common burnt clay, sub class 'B' old size laid flat and dry on cables as in cable protection in trenches over cables perpendicular to direction of cables abutting each other complete all as specified and directed. |
| 8 | M & L for river bed fine sand laid in trenches 15 cm below cable and 8 cm above the cable for cushioning/protection to cable including spreding, levelling and 18cm after hand punning complete all as specified and directed at site.Note : For payment purpose punned thickness will be considered. |
| 9 | S&F for Galvanised iron steel tubes, ISI marked light grade of size 50mm bore for cable protection on the wall under road under drains complete all as specified. |
| 10 | S&F for Galvanised iron steel tubes, ISI marked light grade of size 40mm bore for cable protection on the wall under road under drains complete all as specified. |
| 11 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. |
| 12 | Taking down unserviceable main switches, DBs, bus bars chambers any capacity including all fittings and fixtures such as MCBs, isolator, etc and removing from site complete all as specified and directed. |
| 13 | Dismantling and taking down fluorescent tube light single/double of any wattage or size fitting for repair or replacement of burnt/worn out complete all as specified and as directed. |
| 14 | M&L for point wiring concealed with single core PVC insulated unsheathed 1100 volts grade FRLS cable of copper conductor multi stranded of size 1.5 sqmm (Nominal size) drawn through and including non metallic rigid PVC conduit medium grade, ISI marked not less then 20 mm dia with all accessories like tee, straight joint, L bend etc concealed in wall , ceiling , floor etc, pressed MS Sunken boxes in wall of required size and colour for switches and sockets, 1.5 sqmm (Nominal size) PVC insulated (green insulation) copper conductor FRLS earth continuity cable drawn with wiring and connected to common earth dolly all as specified for one light point, ceiling fan/exhaust fan controlled by one SP switch including making good distrubed surface, complete all as specified and directed.Note :- Cost for MS Sunken Boxes, Hylum sheets are cutting, chieseling and cutting the wall/Ceiling for conduit fixing. The disturbed surfaces of wall for concealing the wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate for point wiring shall be deemed to include the cost of making good. |
| 15 | All as per Srl item No 13 here-in-before but for one bell point controlled by one bell push, complete all as specified and directed. |
| 16 | All as per Srl item No 13 here-in-before but for one 5 pin socket out let, 6 Amps on same board with the cable 1.5 Sqmm size, complete all as specified and directed. |
| 17 | All as per Srl item No 13 here-in-before but for one 5 pin socket out let, 6 Amps on Independent board with the cable 1.5 Sqmm size, complete all as specified and directed. |
| 18 | All as per Srl item No 13 here-in-before but for one power point 6 pin 15 Amps socket out let and Geyser Point for sheet metal enclosure with 2.5 Sq mm stranded copper conductor FRLS cable PVC insulated including earth wire 2.5 Sq mm copper conductor FRLS cable connected to earth dolly complete, all as specified and directed. |
| 19 | S & F modular bell push switch, 01 module 10 Amps, 240 volts all as specified and as directed. |
| 20 | S&F modular step type fan regulator 02 module 100W 230 volts, 50 HZ, complete all as specified and as directed . |
| 21 | S&F ceiling rose, surface type, 3 plate. Complete all as specified and as directed by Engr-in-Charge. |
| 22 | S&F of Buzzer, Ding Dong AC. 230 volts,single pole, complete, all as specified and as directed. |
| 23 | S&F lamp holder, with metal ring insulated body with back plate of batten fitting complete all as specified and as directed by Engr-in-Charge. |
| 24 | Supply and fixing LED lights fitting 1x 20 W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. |
| 25 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete |
| 26 | S & F in replacement of LED Bulb, 10 Watts Lumen ≥ 900, Luminous afficacy ≥ 100 Lum/Watt, CCT:WW/NW/CW, CRI > 80 Ra, IP 20 rated, overmoulded plastic housing, polycarbonate diffuser, 4KV surge Protection with over voltage protection withstand upto 440 V (for 10 Minute) with open and short circuit protections as per IS: 16102 with all accessories and connecting up with twin core twisted copper conductor cable of suitable size including lamp complete all as specified and directed. |
| 27 | S&F in replacement of LED bulkhead luminaire 10 watt, wall/surface mounted complete with LED lamp 10 watt, all accessories, pre-wired including providing flexible copper wire, twin core cable PVC insulated sheathed, complete all as specified and directed . |
| 28 | S&F of LED building security light 30 watt, 230V with lens and toughen glass top.The luminarie should have a color temperature of 6500K, IP 65 complete PF > 0.95 with all accessories and including connecting up to ceiling rose with 1.5 sqmm three core copper flexible conductor cable, One GI medium grade 25/40 mm dia bracket of total length 90 cm and fixed to wall with 2 Nos MS Clamp and fastener all as specified and directed. |
| 29 | Supply and fix exhaust fan, steel body AC single Phase. 230V copper winding of 300mm sweep 900 RPM 50 watt ISI marked with frame and louvers complete all as specified and as directed |
| 30 | M&L for cutting openning through brick wall 230mm thick built in cement mortor suitable for exhaust fan 250&300mm sweep including making good dismantled portion in cement mortar 1:3 or cement concrete 1:2:4 type B-1 as required, complete all specified and directed. Please Enable Macros to View BoQ information |
| 31 | M&L for cutting openning through brick wall 230mm thick built in cement mortor suitable for exhaust fan 250&300mm sweep including making good dismantled portion in cement mortar 1:3 or cement concrete 1:2:4 type B-1 as required, complete all specified and directed. Please Enable Macros to View BoQ information |