| 1 | Lumpsum price worked out by the tenderer for BUILDING / STURCTURES as listed in Schedule 'A' Part-I |
| 2 | Lumpsum price worked out by the tenderer for SITE CLEARANCE, AREA DEVELOPMENT AND EXCAVATION AND EARTH WORK as listed in Schedule 'A' Part-II |
| 3 | Lumpsum price worked out by the tenderer for INTERNAL WATER SUPPLY as listed in Schedule 'A' Part-III |
| 4 | Lumpsum price worked out by the tenderer for INTERNAL ELECTRIC SUPPLY as listed in Schedule 'A' Part-IV |
| 5 | Lumpsum price worked out by the tenderer for PROTECTIVE WORK as listed in Schedule 'A' Part-V |
| 6 | Lumpsum price worked out by the tenderer for ROAD/ CULVERT as listed in Schedule 'A' Part-VI |
| 7 | Lumpsum price worked out by the tenderer for SEWAGE DISPOSAL as listed in Schedule 'A' Part-VII |
| 8 | Lumpsum price worked out by the tenderer for AREA DRAINAGE as listed in Schedule 'A' Part-VIII |
| 9 | Lumpsum price worked out by the tenderer for FENCING & GATE as listed in Schedule 'A' Part-IX |
| 10 | Lumpsum price worked out by the tenderer for EXTERNAL WATER SUPPLY as listed in Schedule 'A' Part-X |
| 11 | Lumpsum price worked out by the tenderer for EXTERNAL ELECTRIC SUPPLY AND STANDBY POWER SUPPLY as listed in Schedule 'A' Part-XI |
| 12 | NOTE: 1. Schedule ‘A’ Part - I here-in-before is not prepriced by MES and left blank under Col. 5 signifies this fact only. Bidder shall insert their rates in Green colour filled under Col-6.2. Schedule ‘A’ Part - II to XI here-in-before are prepriced by MES under Ser No. 2.00 to 11.00 Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.3. Schedule ‘A’ Part - XII (STP & MISCELLANEOUS ITEMS) here-in-after is not prepriced by MES and prepriced by MES and rate left blank under Col.5 signifies this fact only. Bidder shall insert their rates in Green colour filled under Col-6. |
| 13 | SCHEDULE ‘A’ PART - XII (STP & MISCELLANEOUS ITEMS) |
| 14 | SEWAGE TREATMENT PLANT (STP) AT AVA HILLDesigning (hydraulically, structurally & aesthetically), providing, constructing, hydraulic testing, commissioning and giving satisfactory trials of STP of capacity 75 cum/day (KLD) with SCADA Compliant MCC Panel with OCEMS (suiting to the climatic conditions of the site) consisting of RCC Collection Sump, Inlet Chamber, Fine bar Screen chamber (manual) with steel screen, Oil & Grease Remover, Grit separator, Equalization Tank (2 Tanks of 50% Capacity each), Air Grid for Equalization Tanks, Feed Pumps (2 Nos), Moving Bed Bio Reactor (s) with plastic media (of appropriate density, size and quantity to keep very high MLSS > 15,000 mg/lit), Air Blowers for MBBR, Tube Settler assembly, Sludge Drying Bed of appropriate size, Chlorine Dozing System, Chlorine contact tank, Treated Water Collection Sump, Foundation for all E/M equipments, Associated piping work with required valves, gates, drains, pathways, Electrical control Panel with interconnecting cable, spare parts for 2 years of operation, etc. complete as turnkey job with all involved civil, electrical, digital and mechanical works as per detailed specifications for civil, electrical and mechanical components with all duties and taxes complete. (Also refer important Notes below). For tertiary treatment it also includes Filter Feed Tank, Filter Feed Pumps, Dual Media Filter, Activated Carbon Filter, Treated water Tank. Treated water can be used for irrigation, horticulture, fire fighting and MT wash at Ava Hill complete all as directed. |
| 15 | (Note: (i) The capacity and dimensions of the Raw Sewage Collection Sump and Treated Water Collection Sump shall be finalized based on the detailed hydraulic design of the 75 KLD Sewage Treatment Plant, considering peak flow, detention time, pump operating cycles and operational requirements. (ii) The non-clog vertical sewage pumps installed in the RCC Collection Sump for transfering sewage to the Inlet Chamber shall be measured and paid seperately under the respective pumping equipment item in BOQ.(iii) All the connected pumps of STP package type should have 1W + 1S Model.) |
| 16 | SEWAGE TREATMENT PLANT (STP) AT MANDIR VIEWDesigning (hydraulically, structurally & aesthetically), providing, constructing, hydraulic testing, commissioning and giving satisfactory trials of STP of capacity 65 cum/day (KLD) with SCADA Compliant MCC Panel with OCEMS (suiting to the climatic conditions of the site) consisting of RCC Collection Sump, Inlet Chamber, Fine bar Screen chamber (manual) with steel screen, Oil & Grease Remover, Grit separator, Equalization Tank (2 Tanks of 50% Capacity each), Air Grid for Equalization Tanks, Feed Pumps (2 Nos), Moving Bed Bio Reactor (s) with plastic media (of appropriate density, size and quantity to keep very high MLSS > 15,000 mg/lit), Air Blowers for MBBR, Tube Settler assembly, Sludge Drying Bed of appropriate size, Chlorine Dozing System, Chlorine contact tank, Treated Water Collection Sump, Foundation for all E/M equipments, Associated piping work with required valves, gates, drains, pathways, Electrical control Panel with interconnecting cable, spare parts for 2 years of operation, etc. complete as turnkey job with all involved civil, electrical, digital and mechanical works as per detailed specifications for civil, electrical and mechanical components with all duties and taxes complete. (Also refer important Notes below). For tertiary treatment it also includes Filter Feed Tank, Filter Feed Pumps, Dual Media Filter, Activated Carbon Filter, Treated water Tank. Treated water can be used for irrigation, horticulture, fire fighting and MT wash at Mandir View complete all as directed. |
| 17 | (Note: (i) The capacity and dimensions of the Raw Sewage Collection Sump and Treated Water Collection Sump shall be finalized based on the detailed hydraulic design of the 65 KLD Sewage Treatment Plant, considering peak flow, detention time, pump operating cycles and operational requirements. (ii) The non-clog vertical sewage pumps installed in the RCC Collection Sump for transfering sewage to the Inlet Chamber shall be measured and paid seperately under the respective pumping equipment item in BOQ.(iii) All the connected pumps of STP package type should have 1W + 1S Model.) |
| 18 | Supply and installation of Non clog vertical submersible pumps of capacity 25 m head and 125 LPM, 3HP with chrome steel impeller and cutter, non-clog to pass 40 mm size particles including guide rail and lifting chain, cables, earthing, testing complete with 2 years maintenance etc complete all as specified and as directed. (Note: These pumps shall be used to transfer the sewage from RCC collection sump to inlet chamber STP with 1W + 1S model) |
| 19 | Supply and installation of Non clog vertical submersible pumps of capacity 25 m head and 75 LPM, 1.5 HP with chrome steel impeller and cutter, non-clog to pass 40 mm size particles including guide rail and lifting chain, cables, Earthing, testing complete with 2 years maintenance etc complete all as specified and as directed. (Note: These pumps shall be used to lift the sewage from all collection sumps, total 06 sumps for both location of STP with 1W + 1S model) |
| 20 | Supply and fix High density polyethylene pipes (HDPE) of 80 mm diameter, pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc complete all as specified and as directed |
| 21 | INTERNAL WATER SUPPLYSupply and fix 15mm two way, single handle, bib cock with flange Bib taps, fancy type, chromium plate cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and as directed |
| 22 | Supply and fix 15 mm bore angle cocks, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed but fancy type chromium plated all as specified and directed. complete all as specified and as directed. |
| 23 | SEWAGE DISPOSALMaterial and labour for Double Wall Corrugated Polyethylene Pipes (DWCPE) (SN8) 180mm outer dia & 163mm inner dia, laid in trench & in manhole etc complete all as specified and directed. |
| 24 | Material and labour for Double Wall Corrugated Polyethylene Pipes (DWCPE) (SN8) 200mm outer dia & 175mm inner dia, laid in trench & in manhole etc complete all as specified and directed. |
| 25 | EXTERNAL ELECTRIC SUPPLYSupply & Spreading clean dry riddled sand in trenches for cushioning for under ground cables protections (below, above and around the cable laid in trenches) complete all as specified and directed.(Note: Thickness after punning down shall be measured for payment) |
| 26 | Supply and fix terminal box made of thermoplastic type out door type of size 260 x 210 x 116 mm for fixing on pole with and including of mild steel clamps with bolt and nuts, provn for cable entry for incoming and outgoing from bottom including MCB SP 6 Amps 10 kA -1 Nos and 8 way connector with internal copper wiring connection duly fixed with and including cable glants threaded typemade of polymide with lock nut complete all as specified and as directed. |
| 27 | DG SETSupply, Install, test and commissioning, factory assembled silent Diesel Engine driven generator set as per CPCB IV+/ latest CPCB norms, fully wired alternator to give an out put of 20 kVA continuously raing at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz + 1% supply,directly coupled with diesel engine, liquid cooled of of suitable BHP de-rated for Wellington, Nilgiris at high altitude of approximate 2000 Mtr mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line and accessories, PCC foundation work as per manufacture's instructions, vibration damper pads, AMF control panel, Battery & other accessories etc and comprising of following :- |
| 28 | (a) Diesel Engine liquid cooled, turbocharged with after cooler to deliver required BHP a under NTP condition of BS 5514 standard de-rated for Wellington, Nilgiris at high altitude of approximate 2000 Mtr and conforming to IS 10001/10002 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories. (i) Dry type air cleaner(ii) Exhaust Silence suitable for canopy(iii) Expansion bellow(iv) Lube oil Cooler(v) Fuel Filters(vi) Radiator with pusher type fan and mounting(vii) In-line mono block fuel injection pump(viii) Mechanical governor and fuel feed pump(ix) Fly wheel with starter ring and bell bousing suitable for close coupling(x) 12 Volt electric starter motor(xi) Battery charging alternator(xii) Microprocessor based KG934(L1) Controller mounted are fixed in power panel(xiii) Protection system for Low lube oil pressure and High water temperature(xiv) Battery:- Suitable Maintenance free battery with leads & terminals as per OEM recommendation (Make- Exide/Amron) .(xv) Fuel tank: 08 hrs. full load diesel storage capacity fuel tank with mounting brackets factory made of 5mm thick HR/MS sheet with level indicator, fuel inlet, fuel outlet, air vent, drain plug, in let arrangement for diesel filling from exterior canopy (without opening its panel) etc complete all as specified and directed. |
| 29 | (b) Alternator suitable rated at 20 kVA at 0.8 power factor , 415 volts, 3 phase, 4 wire, 50 Hz at self excited and self regulated with AVR brushless excitation, screen protected, drip proof , insulation class H, self ventilated, floormounted with ball or bearing on end shields and conforming to IS: 4722 suitable for engine as mentioned here-in before. (c) Accoustic Enclosure:- Acoustic enclosure with outer body made of 3mm thick CRCA sheet , epoxy coated and sound insulation to reduce noise level to 75 dBA measured at 1.0 meter average distance for audible frequenciesas per guide of Central Pollution Control Board or latest CPCB norms and of suitable size and OEM specification and inside illumination with 1 No. 1 x 18 watt LED fitting(d) Standard Gen set Controller with Control Panel - Gen Set controller unit totally enclosed, steel construction control panel suitable for indoor floor/ wall mounting installation with control fuse base with necessary link, power terminals and control terminal start and stop relay having following safeties and display parameters :-(i) Engine display Parameter for :- (aa) Oil Pressure (ab) Engine Collant Temperature (ac) Fuel Status (ad) Engine Speed (ae) Battery Voltage (af) Engine Hours Please Enable Macros to View BoQ information |
| 30 | (b) Alternator suitable rated at 20 kVA at 0.8 power factor , 415 volts, 3 phase, 4 wire, 50 Hz at self excited and self regulated with AVR brushless excitation, screen protected, drip proof , insulation class H, self ventilated, floormounted with ball or bearing on end shields and conforming to IS: 4722 suitable for engine as mentioned here-in before. (c) Accoustic Enclosure:- Acoustic enclosure with outer body made of 3mm thick CRCA sheet , epoxy coated and sound insulation to reduce noise level to 75 dBA measured at 1.0 meter average distance for audible frequenciesas per guide of Central Pollution Control Board or latest CPCB norms and of suitable size and OEM specification and inside illumination with 1 No. 1 x 18 watt LED fitting(d) Standard Gen set Controller with Control Panel - Gen Set controller unit totally enclosed, steel construction control panel suitable for indoor floor/ wall mounting installation with control fuse base with necessary link, power terminals and control terminal start and stop relay having following safeties and display parameters :-(i) Engine display Parameter for :- (aa) Oil Pressure (ab) Engine Collant Temperature (ac) Fuel Status (ad) Engine Speed (ae) Battery Voltage (af) Engine Hours Please Enable Macros to View BoQ information |