| 1 | Part-A |
| 2 | 33/0.433 KV, 2.0 MVA Transformer: Non Comprehensive AMC Charges of 2.0 MVA rating Dry Type Transformer 33/0.433 KV Transformer with off load tap changer such as IR value test, Open circuit test, Magnetizing current, Magnetic Balancing Test, Checking of controlling D.C. component when it required. |
| 3 | Non Comprehensive AMC of 33 KV Breaker: 33 KV Vaccum Breaker of Servicing, de-carbonizing, lubricating and greasing the mechanism of 33 KV ABB make VCB including and set-right the wiring, Primary injection test on 33 KV Indoor type CT. IR value of various live parts with Contact Resistance, Timing of Tripping & Closing of Breaker. |
| 4 | Servicing, de-carbonizing, lubricating and greasing the mechanism of LT ACB make L&T including and set-right the wiring. The job also includes the measurement of IR value of various live parts.3200 Amp. - 08 Nos.2500 Amp. - 10 Nos.2000 Amp. - 02 Nos.1600 Amp. - 05 Nos.1250 Amp. - 02 Nos.1000 Amp. - 05 Nos.800 Amp. - 03 Nos. |
| 5 | Draw out the control wiring of Capacitor Panel such as programming of APFC relay, auto / manual mode, indication etc. |
| 6 | Draw out the control wiring of Main LT Panel such as programming of protection relay, auto / manual mode, indication, Amp meter etc. |
| 7 | Grand Total (NC-MC period 03 year) = 756000 x 3 year |
| 8 | Part-B |
| 9 | S/I/T/C of electrical material as per site requirement. |
| 10 | 33 KV PT for VCB resin cast, indoor, single phase, voltage transformer complete with built in HV fuse. Ratio 33000/110V. |
| 11 | 33 KV Epoxy Resin cast CT 200/100/5+5A, Class 0.5/ 5P10, Burden 15 VA. Make Savio Industries. |
| 12 | 33 KV Epoxy Resin cast CT 50/100/5+5A, Class 0.5/ 5P10, Burden 15 VA. Make Savio Industries. |
| 13 | Insulator 33 Kv oil Transformer |
| 14 | 33 KV Epoxy Resin cast Indoor Insulator |
| 15 | Power Bank 240 V/24 V for HT Panel |
| 16 | 33 Kv oil Transformer silica Gel |
| 17 | Transformer oil |
| 18 | Spound Core paint |
| 19 | Contractor 32 Amp (Make L&T) |
| 20 | Overload 7 to 11 Amp (Make L&T) |
| 21 | 33 KV Joint Kit 3x185 Sqmm (HT) |
| 22 | Capacitor 25 KV AR (L.T. Panel) (Make L&T) |
| 23 | Core Paint |
| 24 | Tulip Contact (33 Kv VD-4 Breaker ABB) |
| 25 | Closing Coil (33 Kv VD-4 Breaker ABB) |
| 26 | Closing Coil (L.T. Breaker) (Make Mitsubishi) |
| 27 | Motor 24V (L.T. Breaker) (Make Mitsubishi) |
| 28 | Triping Coil (33 Kv VD-4 Breaker ABB) |
| 29 | Master Trip Relay (H.T.) (Make ABB) |
| 30 | High-set IDMT relay with 3 O/C+E/F, ABB REJ601 24V-240V AC/DC 5A REJ601BE446NB1NH |
| 31 | Shunt trip coil 24 Volt DC (Make ABB) |
| 32 | Multi Function meter - EM 6400 |
| 33 | Volt Meter (Make - Schneider) |
| 34 | AMP Meter (Make - Schneider) |
| 35 | Master Trip Relay (H.T.) 24 Volt DC (Make - C&S) |
| 36 | Vaccum Bottel suitable for 33 KV indoor type panel VD4 (Make - ABB) |
| 37 | Pole for 33 KV indoor type panel ABB VD4 Make |
| 38 | Spout 33 KV VCB Make - ABB Indoor type panel for incomer (6 Nos.) |
| 39 | Spout 33 KV VCB Make - ABB Indoor type panel for outgoing (6 Nos.) |
| 40 | VCB Charging Motor (Make - ABB) |
| 41 | Indication Light |
| 42 | 110 Volt R, Y, B |
| 43 | 240 Volt R,G |
| 44 | Breaker Control Switch H.T. & L.T. (Make T&C) |
| 45 | Oil Filteration Charge |
| 46 | Labour Cess and GST will be paid extra as per govt. orders Please Enable Macros to View BoQ information |