| 1 | Renovation and Modernization of Vulnerable Distribution substations under PMKKKY Scheme 2026-27 (Turnkey Basis). |
| 2 | Supply, Installation, testing & Commissioning of 11 KV Gap-less Surge Arrestor 9 kV, 10 kA, LA with polymer housing, Stn. Type conforming to IEC-99-4 Capable of withstanding Maximum continuous operating voltages (M.C.O.V)1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 set2. 630 kVA Mirjanpora-ESD Nawakadal - 01 set3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 set4. 630 kVA Malbab Sahib-ESD Nawakadal - 01 set5. 400 kVA Sunar Kul- ESD Watalkadal - 01 set6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 set |
| 3 | Supply, Installation, testing & Commissioning of 11 KV Horn Gap Fuse Set 3 Phase 200A as per Relevant IS.1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 set2. 630 kVA Mirjanpora-ESD Nawakadal - 01 set3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 set4. 630 kVA Malbab Sahib-ESD Nawakadal - 01 set5. 400 kVA Sunar Kul- ESD Watalkadal - 01 set6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 set |
| 4 | 11 KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type (G.O. Set) conforming: IS-2544, IS: 5340 (Part-III) and SS: 9921 (Part-I -V)1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 set2. 630 kVA Mirjanpora-ESD Nawakadal - 01 set3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 set4. 630 kVA Malbab Sahib-ESD Nawakadal - 01 set5. 400 kVA Sunar Kul- ESD Watalkadal - 01 set6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 set |
| 5 | Supply, Installation, testing & Commissioning of G.I Pipe of 150 mm dia 3 mtr long for Pole Butts (6\\") (including digging of pits)1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 02 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 02 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 02 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 02 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 02 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 02 no. |
| 6 | Supply, Installation, testing & Commissioning of a. Transformer Pad/G.I Channel Bedding -(300 kg for 400 KVA & 450 kg for 630 kVA)b. GI Channel/Angle/Flat of sizes including clamps for L.A Set/G.O Set/Horn Gap -150 kg1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 450 kg2. 630 kVA Mirjanpora-ESD Nawakadal - 600 kg3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 600 kg4. 630 kVA Malbab Sahib-ESD Nawakadal - 600 kg5. 400 kVA Sunar Kul- ESD Watalkadal - 450 kg6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 600 kg |
| 7 | Supply, Installation, Testing and commissioning of S.T. poles 9.0 Meter long swayed Type conforming to ST 410 SP-33, IS: 2713 amended up-to date well finished and coated with black bituminous paint upto plant depth and Red-Oxide coated above ground level with earthing arrangement through bolt welded on pole of 14mm diameter, provided at height of 300mm above the planting depth which should be 1.5ms (SP 33). Top plate 3mm thick fully welded & bottom plate 35cm*35cm, 5mm thick fully welded.1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 02 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 02 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 02 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 02 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 02 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 02 no. |
| 8 | Supply, Laying, stringing, testing and commissioning of 630 mm² XLPE LT Cable Single Core, Un-Armoured, XLPE Insulated Stranded Conductor FRLS type1. 630 kVA Mirjanpora-ESD Nawakadal - 60 Mtr 2. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 60 Mtr 3. 630 kVA Malbab Sahib-ESD Nawakadal - 60 Mtr 4. 630 kVA SS at Gousia Colony -ESD Watalkadal - 60 Mtr |
| 9 | Supply, Laying, stringing, testing and commissioning of 300 mm² XLPE LT Cable Single Core, Un-Armoured, XLPE Insulated Stranded Conductor FRLS type1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 44 Mtr2. 400 kVA Sunar Kul- ESD Watalkadal - 44 Mtr |
| 10 | Supply, Laying, stringing, testing and commissioning of 11 KV Polymeric composite Disc Insulator 12 KV,min failing load 45kN, Lighting Impulse 75 KV Positive and 80 KV Negative, creepage distance 320 mm1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 03 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 03 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 03 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 03 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 03 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 03 no. |
| 11 | Supply, Laying, stringing, testing and commissioning of 11kV Polymeric composite Pin Insulator with pins 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 03 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 03 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 03 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 03 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 03 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 03 no. |
| 12 | Supply, Laying, stringing, testing and commissioning of LT Fuse Set (Customized) for Distribution Transformers as per KPDCL Drawing no. CE/P&P/DRG/2023/LTFS/0011. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 01 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 01 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 01 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 no. |
| 13 | Supply and Fixing of GI Barbed Wire for Anti Climbing1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 15 kg2. 630 kVA Mirjanpora-ESD Nawakadal - 15 kg3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 15 kg4. 630 kVA Malbab Sahib-ESD Nawakadal - 15 kg5. 400 kVA Sunar Kul- ESD Watalkadal - 15 kg6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 15 kg |
| 14 | Supply and fixing of Galvanized Nuts and Bolts1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 8 kg2. 630 kVA Mirjanpora-ESD Nawakadal - 8 kg3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 8 kg4. 630 kVA Malbab Sahib-ESD Nawakadal - 8 kg5. 400 kVA Sunar Kul- ESD Watalkadal - 8 kg6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 8 kg |
| 15 | Supply and Painting of poles with red Oxide with single coat and two coats of Aluminium Paint1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 02 job2. 630 kVA Mirjanpora-ESD Nawakadal - 02 job3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 02 job4. 630 kVA Malbab Sahib-ESD Nawakadal - 02 job5. 400 kVA Sunar Kul- ESD Watalkadal - 02 job6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 02 job |
| 16 | Providing and laying of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, baby insulators, refilled with earth enhancement materials and earth Chamber made of brick masonry with RCC slab cover.1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 03 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 03 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 03 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 03 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 03 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 03 no. |
| 17 | Providing and laying of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 04 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 04 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 04 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 04 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 04 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 04 no. |
| 18 | Providing and fixing of Danger Plates with Clamps1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 01 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 01 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 01 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 no. |
| 19 | Providing and fixing of PG Clamps/ Wedge connectors1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 06 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 06 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 06 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 06 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 06 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 06 no. |
| 20 | Dismantling & Re-erection of 630 kVA DT from old structure to New Structure including loading/unloading, carriage, installation, testing, & commissioning (integration with system).1. 630 kVA Mirjanpora-ESD Nawakadal - 01 job2. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 job 3. 630 kVA Malbab Sahib-ESD Nawakadal - 01 job 4. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 job |
| 21 | Dismantling & Re-erection of 400 kVA DT from old structure to New Structure including loading/unloading, carriage, installation, testing, & commissioning (integration with system).1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 job 2. 400 kVA Sunar Kul- ESD Watalkadal - 01 job |
| 22 | Dismantling of old Substation along with allied material and shifting of same to divisional stores. The job include Transportation, carriage, loading and unloading. However, the PCC Poles may be disposed off at appropriate site.1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 01 job2. 630 kVA Mirjanpora-ESD Nawakadal - 01 job3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 01 job4. 630 kVA Malbab Sahib-ESD Nawakadal - 01 job5. 400 kVA Sunar Kul- ESD Watalkadal - 01 job6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 01 job |
| 23 | Cement bottoming of poles (1:2:4 Mix as per REC Standards 0.48M3 per Pole) (2 no. for poles & 2 no. of GI Pole Butts)1. 400 kVA Sub-Station at Khaiwan ESD Nawakadal - 04 no. 2. 630 kVA Mirjanpora-ESD Nawakadal - 04 no. 3. 630 kVA Haftyarbal malik Sahib-ESD Nawakadal - 04 no. 4. 630 kVA Malbab Sahib-ESD Nawakadal - 04 no. 5. 400 kVA Sunar Kul- ESD Watalkadal - 04 no. 6. 630 kVA SS at Gousia Colony -ESD Watalkadal - 04 no. Please Enable Macros to View BoQ information |