| 1 | SITC 58.5 KVA / 46.6 KW 4 cylinders, inline, 4 stroke cycle, of CPCB IV+ Water cooled Turbocharged,. The engine shall be provided with electrical starting arrangement & shall give the electrical output of 58.5 KVA / 46.6 KW at 0.8 power factor, 415Volts at the alternator terminal including AMF panel including foundation cement concrete & Industrial cable 2.5 Sq. mm (6 core). |
| 2 | DIESEL ENGINE:-4 cylinder , 4 stroke cycle , rediated cooled, turbo charged Charged air cooled, . The engine shall be provided with electrical starting arrangement and shall give the electrical output of 58.5 KVA / 46.4 KW at 0.8 power factor, 415 volts at alternator terminals including AMF panel |
| 3 | Specifications:-4 cylinder , 4 stroke cycle , rediated cooled, turbo charged Charged. Rediator cooled , Engine mounted water pump, thermostats, coolamnt, self- contained piping. High pressure common rail fuels system, spin on type fuel filters , self- contained piping. Lub oil pump, spin on type lub oil filter , self contained piping. Dry type replacable paper element air filter, air intake manifold with necessary connections, turbo charger. Exhaust manifold , flexibkle piping, silencer, hospital grade. P1.1 conrteroler with PS0500 features, Starter 12 V, DC, battery charging alternator with inbuilt regulator, Flywheel, fly wheel housing |
| 4 | GENSET CONTROLLER:- The controler should be a microproceesor based generator set monitoring and control system. The control should provides a simple operator interface to the genrator set, manual and remote start/ stop control ,shutdown fault indication and an LCD hour counter. The integration of all function into a singkle control system provides enhenced reliability and performance compared to conventional generator set control systems. The control has been desined and tested to meet harsh envirment in which Gen. sets are typically applied. |
| 5 | ALTERNATOR:- Sigle bearing alternator suitable for continuos operation generating 58.5 KVA at 1500RPM, 415 Volts , 0.8 PF suitable for 50 Hz 3 Phase system. The alternator shall be in SP-DP enclosure, self excited , self regulated, foot mounted with ball and roller bearing on end shields The alternator shall be suitable automatic voltage regulator and shall conform to BS:2613 or BS:5000 and give rated output at NTP conditions. |
| 6 | CONTROL PANNEL FOR DG SET :-The generatoe control shall be indoor type , floor mouted , dust and vermin proof in sheet steel construction. The pannel shall have doors at front and back for proper maintenance. The pannel shall have steel channel fabricated kick-plate and bolted type cable glade plate fitted at the bottem . The opannel shall be construced from 2 mm thick steel sheet . All the joint shall have proper gasket. |
| 7 | Monitoring and control devices shall be housed on the front door. Generally the construction of the pannel will be such that various equipments for application will be housed in compartment. All incoming and outgoing power and control cables shall be from bottom. |
| 8 | The pannel will be equiped as follows:-Incomer- 1 No 3- pole, 100 Amps MCCB, Set of CTs for metering. Instrument :- 1-Voltmeter with selector switch , 1- ammeter with selector swich 1- frequency meter, 1- KWH meter, 1- KW meter. Indication lamps:- Genset running, Set on load, phase indication. SOUND ATTENUATED SYSTEM. Thickness of sheet-16-G |
| 9 | The sound attenuated DG set are designed and engineered by rthe CAD/CAM experts conforming to international standerds. The system is made of high class sheet metal fabicated pannels of 16 G thickness having modular construction with multi fold sheet channels and ISMC section for ease of assembly and dismentaling , high quality fire proof acoustic material i.e. rock wool (50-100 mm thick having 64-96 KG/ m3 density) |
| 10 | ACOUSTIC MATERIALS:- Acoustic enclosure is made of CRCA sheets in munsel green shade and a structural/ sheet metal base frame painted in black and fire retardent grade acoustic insulation material(P.U foam) to IS 8183 |
| 11 | VENTILATION:-Acoustic encloser is designed in such a way that they are no hot pockets around engine and is provided with suitable designed engine radiator which does not allow the temperature to rise more than 70 C above ambient temperatue. To achive optimal output and minimum sound lavel from the DG set , suitable openings are prvide for increasing the inflow of air required for combustion. |
| 12 | SILENCER:-Specially designed low noise silencer with rain cap suitably optimised to meet stingent noise emmission standerd laid down by MoEF/CPCB. |
| 13 | VIBRATION ISOLATION :-To avoid transfer of vibration from genset to enclosure and surrounding specially designed vibration islator are used . |
| 14 | Warranty:- Standard 2 years comprehensiv warranty on engine and alternator , from date of dispach or 5000hrs of operation from the dare of commissioning ,which ever is earlier against any manufacturing defect . 5 critical part of engine (cylinder head,cylinder block ,cranks saft,camsaft,connecting rod,) shall be Warranted for 5 years or 5000 hrs , of operation which ever is earlier from the date of dispatch against maniufacturing defect. |
| 15 | Complete rate of D.G. set including , price of DG se , price of AMF panel, installation charges cable connection each complete in all respect :- Makes :- Sudhir /Catepiller /volvo/Kirlosker Ashoka Leyland /TATA/ Mahindra /Eicher as apporved by Engineer charge . |
| 16 | Providing / filling Diesel in the existing diesel set of Gernator as required complete in all respect. |
| 17 | SUB HEAD II Excavation in foundation |
| 18 | Excavation in foundation, tranches etc. in earth work lift up to 1.50 metres stacking the excavated soil not more than 3 metres clear from the edge of excavation and then returning the stacked soil in 15 cm layers, when required in to plinths sides of foundation etc. consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth as directed with in a lead of 20 metres complete in pick and jumper work. |
| 19 | Providing and laying cement concrete 1:4:8 (1 Cement: 4 sand: 8 graded crushed stone aggregate 40 mm nominal size) and cutting complete excluding cost of form work in foundation and plinth. |
| 20 | Providing from work with steel plates 3.15mm (Three decimal one five milimeters) thick welded with angle iron in frame 30 x 30 x 5 mm so as to give a fair finish including centering, shuttering, structting and propping etc. with wodden battens and ballies, height of propping and centering below supporting floor to ceiling not exceeding 4 metres and removal of the same for institu- reinforced concrete and plain concrete work in foundation footings basis of columns etc. and mass concrete. |
| 21 | Providing and laying plain cement concrete 1:2:4 (1 Cement: 2 sand: 4 graded crushed stone aggregate 20 mm nominal size) mechanically mixed and vibrated and curing complete excluding cost of form work in foundation and plinth etc. as required complete in all respect. as per entire satisfcation of engineer in charge |
| 22 | Filling in plinth with sand under floors includingc watering ramming consolidating and dressing complete. as required complete in all respect. as per entire satisfcation of engineer in charge |
| 23 | SUB HEAD III EARTHING & LOOP EARTHING |
| 24 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required complete in all respect. as per entire satisfcation of engineer in charge |
| 25 | Providing and fixing following rating, four pole, 415 volts, On-Load change over switch unit, in sheet steel enclosure, with side handle operation, including drilling holes on the board, making connections, etc. as required complete in all respect. as per entire satisfcation of engineer in charge i) 100 amps. TPN, On Load Change over switch (SS Enclosure type) Make:-Havells,ABB,Legrand,L&T,schneider,C&S, SSK |
| 26 | S/E of MCCB 4 Pole 415 Volt. with Microprocesser Release for overload and short circuit protection breaking Capacity (Ics=100% Icu with positive isolation) with/ without Spreader/ Rotary Handle. as required complete in all respect. as per entire satisfcation of engineer in charge i) MCCB 40- 100 Amp. 36 ka 4 Pole Release with rotary handle Make:- Havells,ABB,Legrand,L&T,schneider,C&S, SSK |
| 27 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required complete in all respect. as per entire satisfcation of engineer in charge |
| 28 | SUB HEAD -IV :- WIRING & CABLE LAYING |
| 29 | Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size complete as required complete in all respect. as per entire satisfcation of engineer in charge . i) Armoured cable 70 sq. mm (3.5 core) Make :- Universal Cables,KEI,Havells,Grandley Please Enable Macros to View BoQ information |