Tender For Providing Of Klp (Ph-I Of Two Phase) Of Mi At Hisar Mil Stn
Tender Overview
Project Description
Tender For Providing Of Klp (Ph-I Of Two Phase) Of Mi At Hisar Mil Stn-- 1 Lump Sum Price Worked Out By The Contractor For \Building Works\ As Listed In Schedule ‘A’ Part-I Representing Percentage ( + Or - Denomination) Derived Under Last Column Of This Schedule Above/Below The Lump Sum Price Prepriced By The Mes 2 Lump Sum Price Worked Out By The Contractor For \Internal Water Supply \ As Listed In Schedule ‘A’ Part-Ii Representing Percentage ( + Or - Denomination) Derived Under Last Column Of This Schedule Above/Below The Lump Sum Price Prepriced By The Mes 3 Lump Sum Price Worked Out By The Contractor For \Internal Electrification\ As Listed In Schedule ‘A’ Part-Iii Representing Percentage ( + Or - Denomination) Derived Under Last Column Of This Schedule Above/Below The Lump Sum Price Prepriced By The Mes 4 Lump Sum Price Worked Out By The Contractor For \Road, Path, Culvert And Hard Standing\ As Listed In Schedule ‘A’ Part-Iv Representing Percentage ( + Or - Denomination) Derived Under Last Column Of This Schedule Above/Below The Lump Sum Price Prepriced By The Mes 5 Lump Sum Price Worked Out By The Contractor For \Sewage Disposal\ As Listed In Schedule ‘A’ Part-V Representing Percentage ( + Or - Denomination) Derived Under Last Column Of This Schedule Above/Below The Lump Sum Price Prepriced By The Mes
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-Jul-2026 | Corrigendum No. 01 | Date | 25-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Lump sum price worked out by the contractor for \\"BUILDING WORKS\\" as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 2 | Lump sum price worked out by the contractor for \\"INTERNAL WATER SUPPLY \\" as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 3 | Lump sum price worked out by the contractor for \\"INTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 4 | Lump sum price worked out by the contractor for \\"ROAD, PATH, CULVERT AND HARD STANDING\\" as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 5 | Lump sum price worked out by the contractor for \\"SEWAGE DISPOSAL\\" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 6 | Lump sum price worked out by the contractor for \\"AREA DRAINAGE \\" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 7 | Lump sum price worked out by the contractor for \\"FENCING AND GATE \\" as listed in Schedule ‘A’ Part-VII\\" representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 8 | Lump sum price worked out by the contractor for \\"EXTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 9 | Lump sum price worked out by the contractor for \\"EXTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 10 | Lump sum price worked out by the contractor for \\" LIGHTING PROTECTION \\" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 11 | Lump sum price worked out by the contractor for \\"SUMMER APPLIANCES\\" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 12 | Lump sum price worked out by the contractor for \\"CONDUIT\\" as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 13 | Lump sum price worked out by the contractor for \\"HOT WATER SUPPLY\\" as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 14 | Lump sum price worked out by the contractor for \\"DG SETS SUPPLY\\" as listed in Schedule ‘A’ Part-XIV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 15 | Lump sum price worked out by the contractor for \\"SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK\\" as listed in Schedule ‘A’ Part-XV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 16 | Sch 'A' Part-XVI MISC ITEMS (TO BE QUOTED BY CONTRACTOR) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-XV SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK schedule). |
| 17 | INTERNAL WATER SUPPLYS&F health faucet 15mm bore with 1.0 m tube & hook (Braded tube) etc complete all as specified and directed by Engineer-in-Charge |
| 18 | S&F for15 mm CP 2-in-1 long body bib tap fancy type for fixing of health faucet or jet spray for the WC etc complete all as specified & as direcetd. |
| 19 | S & F for CP Central Hole Basin Mixer with ‘U’ shape Round Casted Spout with 02 Nos 450 mm Long Braided Hoses etc complete all as specified and directed. |
| 20 | INTERNAL ELECTRIFICATIONS& F modular type 3 pin 20 A socket with SP MCB, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge |
| 21 | S&F for modular type 1 module RJ-11 telephone socket with shutter etc complete all as specified and directed |
| 22 | S&F for modular type 1 module co-axial type TV socket etc complete all as specified and directed |
| 23 | S&F for load line distribution board TPN vertical, 8 way double door type, fixed on wall semi flush with incoming MCCB 4 poles and, busbars , neutral link, blanking plates complete with all accessories etc complete all as specified and directed. |
| 24 | S&F for load line distribution board TPN vertical, 6 way double door type, fixed on wall semi flush with incoming MCCB 4 poles and, busbars , neutral link, blanking plates complete with all accessories etc complete all as specified and directed. |
| 25 | S&F for 100A, 4 pole moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% = Icu = 16 kA as per IEC 60947-2 and suitable for 3-Phase, 415 V, 50 Hz electric supply complete all as specified and directed by engineer-in-charge. |
| 26 | S&F for S & F 40 W surface / wall mounted LED batten capable of delivering minimum 2000 lumen, having PC diffuser, luminous efficacy of > 90 lumen/W, CRI > 80, PF > 0.9, CCT 6500K, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. |
| 27 | S&F for 12W LED Downlight having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed by the engineer-in-charge. |
| 28 | S&F for 3W/6W LED Study light having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed by the engineer-in-charge. |
| 29 | S&F for 9W LED bulk head light having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed by the engineer-in-charge. |
| 30 | S&F for surface mound Flame proof LED Batten, 20W, CRI > 70, suitable for Hazardous area group IIA and IIB and zone 1 & 2, IP 65 Protection with 100 lumens/watt with Die Cast Aluminium Housing, THD < 15% complete all as specified and directed by the engineer-in-charge. |
| 31 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. The Panel shall comprise of the following: |
| 32 | (A) BUSBAR CHAMBER(i) 01 Set (3L + N) of copper busbar of rated capacity 320 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection.(B) INCOMING:-(i)250A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 No(ii) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 No(iii)LED phase indicators (Red, Yellow, Blue)- 01 Set(C) OUTGOING:-(i)40A, 415 V, Ics = 100% Icu = 10 kA, 50 Hz 3P MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 08 Nos. (ii)63A, 415 V, Ics = 100% Icu = 10 kA, 50 Hz 3P MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 04 Nos. |
| 33 | (iii)63A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 1P MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 No(iv)40A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 1P MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 No(v)10A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 1P MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos. (vi)Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 17 Nos.(vii)LED phase indicators (Red, Yellow, Blue)- 17 Sets |
| 34 | Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. The Panel shall comprise of the following:(A) BUSBAR CHAMBER(i) 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection |
| 35 | (B) INCOMING:-(i)160A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 No(ii) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 No(iii)LED phase indicators (Red, Yellow, Blue)- 01 Set(C) OUTGOING:-(i)100A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 No(ii)63A, 415 V, Ics = 100% Icu = 10 kA, 50 Hz 4P MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 04 Nos. (iii)Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 06 Nos.(iv)LED phase indicators (Red, Yellow, Blue)- 06 Sets |
| 36 | M & L for concealed flame proof point wiring ( using red , black and green colour wires as colour coding for single phase circuit) for one light point complete with 1.50 Sqmm (nominal cross sectional area) FRLSH PVC insulated unsheathed and multistranded copper conductor cable 1100 V (ISI Marked) for main point and for continues as earth wire connected to earth dolly etc (Phase, neutral and earth wire) drawn through and including ERW steel rigid heavy duty stove enamelled conduit with all frame proof fittings and all accessories e.g pipe, bend, union socket,elbow,connector,reducer,pipe hook,steel ceilling rose/sheet etc for light/fan points including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc by using CM(1:3) complete all as specified and as directed by Engr-In-Charge. Note (i) Two nos of light point circuits shall be controlled by one rotary switch/MCB fixed in existing DB. (ii) Rotary Switches, junctin box, MCB shall be measured and paid separately under appropriate item of this Sch and complete all as specified and as directed by Engr-In-Charge. |
| 37 | S&F for (Concealed in wall) factory made Flame proof DB Duly painted, 4 way dust and vermin proof including operation Knob, cable glands, earth bar, bus bar with all accessories and comprising of all as specified and directed by the engineer-in-charge. Incoming:-(i) MCB, B Curve, SPN 32 Amps, 10 KA-01 NoOutgoing:-(ii) MCB, B Curve, SP 6 Amps, 10 KA-02 Nos |
| 38 | ROAD, PATH, CULVERT AND HARD STANDINGS&F ABS Speed Breaker/Rumbler of height 50mm and width 380mm in two colour of length 500mm each fixed alternately with reflectors on either side complete fixed with epoxy and bolts by drilling 6mmx75mm dia fastener as per manufacture instruction etc complete all as specified and directed . |
| 39 | S&F convex mirror having 130 degree of viewing angle made of one piece polycarbonate lens size of 0.80 mtr dia protect with any type of light ray, not prodice toxic fumes if brunt etc complete all as specified and directed . |
| 40 | M&L for Cement concrete (1:3:6) type C-2, concrete bed to drain pipes 450mm dia including packing under, and haunching against the sides of pipes after they are laid and tested in etc complete all as specified and directed . |
| 41 | Hard Standing for Guard House and Ancillaries etc complete all as shown on drawings (Drawing No. TD/2004/63 Sheet No. 1/1 as specified and as directed. |
| 42 | SEWAGE DISPOSALS&F factory made (SFRC) precasted reinforced cement concrete manhole cover as required thickness not less than 60mm of size 1420mm x 710mm, edge of manhole cover to be locked with 1mm thick MS sheet etc complete all as specified and directed. |
| 43 | S&F factory made (SFRC) precasted reinforced cement concrete manhole cover as required thickness not less than 60mm of size 1200mm x 600mm, edge of manhole cover to be locked with 1mm thick MS sheet .etc complete all as specified and directed. |
| 44 | EXTERNAL WATER SUPPLY 'Supply, lay, commissioning, jointing and testing of centrifugally cast (spun) ductile iron pipes of 100mm bore class K-9 with spigot and socket ends conforming to IS 8329/2000, IS: 12288 : 1987 code of practice for laying in trenches complete all as specified and directed.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 45 | Supply, lay, commissioning, jointing and testing of centrifugally cast (spun) ductile iron pipes of 150mm bore class K-9 with spigot and socket ends conforming to IS 8329/2000, IS: 12288 : 1987 code of practice for laying in trenches complete all as specified and directed.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 46 | Supply, lay, commissioning, jointing and testing of centrifugally cast (spun) ductile iron pipes of 200mm bore class K-9 with spigot and socket ends conforming to IS 8329/2000, IS: 12288 : 1987 code of practice for laying in trenches complete all as specified and directed.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 47 | Supplying, installing, testing and commissioning of centrifugal pumpset 7.5 HP with bronze impellor, electrical driven having discharge capacity 20 LPS of upto 16 metres head, with AC slow speed induction motor of suitable capacity to operate on AC, 3 phase, 415 volts, 50 Hz, with common base plate for electric motor and pump including provision of necessary star delta starter, cable connection from starter to motor with copper conductors complete, each pump set provided with independent suction arrangement consisting of suitable size and length of GI pipes and suitable size of sluice valves with flanged ends, long body, class PN-1 at suction and delivery sides and gun metal stop cock controlled pressure gauge on the delivery side with provision of over load protection no volt release, single phase preventor and armoured PVC cable of suitable size from panel to electric motor etc complete all as specified and directed. |
| 48 | Supply, fixing, jointing & testing cast Iron Sluice Valve of 250mm bore , ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body, Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete all as specified and as directed at site of following sizes. Note:- Flanged joints complete with jointing material shall deemed to be included in the unit rate of this item. |
| 49 | Supply and Fix ductile iron air valve with two air relese outlets, conforming to IS 14845 of size 200 mm dia bore and fixing up in DI/CI water supply mains complete all as specified and directed |
| 50 | Supply and fix CI foot valve with leather washer, of size 100 mm , lift and swing, single door, IS 4038 marked one with each pump suction line complete all as specified and directed. |
| 51 | Supply and Fixing DI/CI special fittings of any size,type,radius angle,tapers increasing decreasing sockets,tees,tail piece and collars etc complete upto 200 mm to 300mm dia etc complete all as specified and directed. |
| 52 | M&L for construction of valve chamber of PCC 1:3:6 masonry built in CM (1:4) with MS covers 3 mm thick and 50 x 50 x 6 mm locking arrangement including excavation and earth works PCC (1:4:8) type D2 for foundation PCC bed/coping in cement concrete (1:2:4) type B1 plastering 15mm thick with CM 1:4 painting with one coat of bituminous black paint over a coat of red oxide primer on all steel surface, for the size of chamber 1200 mm x 1200 mm x 1200 mm complete all as specified and directed by Engr-In-Charge (as per TD drg No. TD/2004/26 Sh No 1/ to 3/3) |
| 53 | M&L for construction of valve chamber of PCC 1:3:6 masonry built in CM (1:4) with MS covers 3 mm thick and 50 x 50 x 6 mm locking arrangement including excavation and earth works PCC (1:4:8) type D2 for foundation PCC bed/coping in cement concrete (1:2:4) type B1 plastering 15mm thick with CM 1:4 painting with one coat of bituminous black paint over a coat of red oxide primer on all steel surface, for the size of chamber 900 mm x 900 mm x 900 mm complete all as specified and directed by Engr-In-Charge (as per TD drg No. TD/2004/26 Sh No 1/ to 3/3) Please Enable Macros to View BoQ information |
| 54 | M&L for construction of valve chamber of PCC 1:3:6 masonry built in CM (1:4) with MS covers 3 mm thick and 50 x 50 x 6 mm locking arrangement including excavation and earth works PCC (1:4:8) type D2 for foundation PCC bed/coping in cement concrete (1:2:4) type B1 plastering 15mm thick with CM 1:4 painting with one coat of bituminous black paint over a coat of red oxide primer on all steel surface, for the size of chamber 900 mm x 900 mm x 900 mm complete all as specified and directed by Engr-In-Charge (as per TD drg No. TD/2004/26 Sh No 1/ to 3/3) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 14 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender