| 1 | Sub Head I CDMO Shahdara |
| 2 | Providing services of the qualified and experienced staff for attending day to day Electrical complaints i/c maintenance of electrical installation such as ceiling fan, exhaust fan, tube light fitting, lamp holder, electrical main board i/c repairing and cleaning of all the electrical fans tube light fitting, main boards, sub-distribution board, earthing compound light etc. in all working days excluding Sunday and Holiday in General shift in 9:00 AM to 5:00 PM at office of the Chief District Medical officer Shahdara, Directorate of Health services GNCT of Delhi, Working Women Hostel Jhilmil, Delhi – 110095. Wireman – 1 No. Khallasi – 1 No. |
| 3 | Sub Head II JJB, Vishwas Nagar |
| 4 | Maintenance of Electrical Installations & Fans i/c EDB's main boards, rising mains, exit sign boards, security lights and compound lights and Operation of 125 KVA capacity DG set with AMF panel from 9 AM to 5 PM on all days excluding Sunday & Gazetted holidays i/c cleaning & routine testing of equipment’s etc. complete as required. Wireman cum Operator: - 1 No. Khallasi :- 1 No. |
| 5 | Round the clock operation and maintenance of wet-riser/sprinkler, firefighting system, AFA/PAS installed at various places/floors along with panel, water supply pump sets drainage pumps etc. i/c cleaning of panels on all days excluding Sundays & Gazetted holidays complete as required. Operator: - 3 Nos. |
| 6 | Operation of 1 No. 4 passengers’ capacity, Judges lift and 1 No. 8 Passenger capacity, common lift (both lifts Johnson Make) from 9 AM to 5 PM on all days excluding Sunday & Gazetted holidays i/c cleaning of lift cars etc. complete as required. Lift Operator: - 2 Nos. |
| 7 | Providing services of the qualified and experienced staff for operation of CCTV surveillance system installed at Juvenile Justice Board and witness room, Vishwas Nagar, Delhi in all working days from 8:00 AM to 8:00 PM excluding Sundays and Holidays etc. i/c cleaning of all CCTV equipments etc. complete as required and as per terms & conditions. — One Job |
| 8 | SH:- III (Material) |
| 9 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and<135 lm/Watt).Supplying, of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66, IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) |
| 10 | 200 Watt |
| 11 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc.as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 12 | 150 Watt |
| 13 | 200 Watt |
| 14 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall splittype Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R- 407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).Inverter Type - Cooling only |
| 15 | 1.5 TR with 5 Star BEE Rating |
| 16 | 2.0 TR with 5 Star BEE Rating |
| 17 | Supplying & laying of 1/2\\" & 1/4\\" copper pipe and 4 core copper cable insulation & drain pipe i/c brazing, testing, commissioning etc. as required and buy back of dismantled material as required. |
| 18 | Providing & fixing of PVC flexible pipe tread type of 25 mm dia for AC sweating water drain complete as reqd. |
| 19 | SITC of 185 liter capacity single door refrigerator with smart inverter compressor and BEE 5 star rating suitable for operation on 230 Volt ± 10% 50 Hz, single phase AC supply with all accessories complete etc. as reqd. |
| 20 | Supplying, Installation, Testing & Commissioning of 43 inches (108 cm) (4K) UHD LED Display TV having display resolution of 3840 X 2160 , having 2 nos of USB Ports, 4 nos of HDMI Ports, Wi-Fi & Bluetooth supported with 20 watt , smart TV, Speakers, suitable for operation on 230 Volts 50 Hz AC supply complete with all connection complete etc as reqd. (Sony Bravia 2M2 or equivalent in LG) Please Enable Macros to View BoQ information |