| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | a) Group A |
| 3 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required. |
| 4 | a) Group A |
| 5 | b) Group B |
| 6 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | 20 mm |
| 8 | 25 mm |
| 9 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 10 | 3 x 1.5 sq. mm |
| 11 | 6 x 1.5 sq. mm |
| 12 | 3 x 4 sq. mm |
| 13 | 6 x 4 sq mm |
| 14 | 3 x 6 sq. mm |
| 15 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in existing surface/ recessed medium class PVC/MS conduit as required |
| 16 | a) 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 17 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. |
| 18 | 1 or 2 module (75mm x 75mm) |
| 19 | 3 Module (100 mmX75 mm) |
| 20 | 6 module (200mm x 75mm) |
| 21 | 8 Module (125 mmX125 mm) |
| 22 | 12 Module (200m x 150mm) |
| 23 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 24 | 5/6 amps switch |
| 25 | 3 pin 5/6 A socket outlet |
| 26 | 15/16 amp switch |
| 27 | 6 pin 15/16 amp socket outlet |
| 28 | Bell Push |
| 29 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 30 | a) 1 or 2 Module |
| 31 | b) 3 Module |
| 32 | c) 6 Module |
| 33 | d) 8 Module |
| 34 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 35 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 36 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 37 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 38 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 39 | 16 way, Double door |
| 40 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 41 | Single Pole |
| 42 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 43 | a) 63 amp |
| 44 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual currentcircuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 45 | a) 63 A |
| 46 | Supplying and fixing DP sheet steel enclosure on surface/ recess complete with etc. as required. |
| 47 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) |
| 48 | a) 18- 22 watt |
| 49 | Supplying, installation, Testing & Commissioning of LEDRecessed / surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim |
| 50 | a) 18 watt |
| 51 | Supplying. Installation, testing and commissioning of 300 mm sweep metallic heavy duty 900 rpm exhaust fan suitable for operation on 230V, 50 Hz single phase AC supply complete with louvers / shutters in the existing opening including making the hole to suit the size of the above fan making good the damage and connections etc. as reqd. |
| 52 | Supplying & Intallation of fresh air fan 200 mm sweep with shutter and louver in the existing opeining , including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required. |
| 53 | Supplying & Intallation of fresh air fan 250 mm sweep with shutter and louver in the existing opeining , including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required. |
| 54 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 55 | Supplying, installation & testing & commissioning of 10W Edge Lite Linear LED Mirror Light (6000K) luminarie having i integrated LED Driver with high transitivity opal diffuser for direct lighting i/c wiring and making connections with 1.5sq.mm. PVC insulated FRLS, copper conductor, single core cable complete etc. as required, suitable for conduit/surface/suspended mounting etc. complete with all accessories/attachments etc as reqd. |
| 56 | SITC of 10watt integrated LED bulk head IP 65 protectin luminiare comprises of pressure die cast housing acrylic disffuser and frame directly on wall i/c connection etc as reqd. |
| 57 | Supplying, installation & testing & commissioning of decorative wall mounting Light with opal glass diffuser suitable for upto 10 W LED filament candle lamp B-22 base direct on wall including connection with 1.5sqmm FRLS copper conductor cable etc. as required. |
| 58 | Supply, installation, testing and commissioning of panel board of size 1450 mm x 900 mm x 300 mm with dust & vermin proof IP-42 protection compartmentalized indoor type cubical panel board made out of not less than 1.6 mm thick CRCA sheet, the sheet steel member shall be stiffened by angle iron framed. The depth of cubical panel shall not be less than 300 mm and suitable sizes earth strip shall be provided around the cubical panel. The cubical panel shall be of suitable size to incorporate following switchgear i/c connections, powder coating of approved colour and shades complete etc. as reqd. Panel should be fixed on CC foundation/ angle iron frame work.200A, 25KA, 4P incomer MCCB-1 No.63A DP 300mA RCCB with mounting plate-09 Nos.32/40A DP 10KA MCB- 3 NosCT's 200/5A class-1.0 10VA-03 NosDigital MFM -1 NoR,Y,B Phase Indicating Lamp-03Nos300A TPN, 415 volt Aluminium Bus BarExtended Rotating Handle -01 NoSingle phase energy meter housing of space provision of 300x300mm size =9Nos. |
| 59 | Supply, installation, testing and commissioning of panel board of size 1900 mm x 1200 mm x 400 mm with dust & vermin proof IP-55 protection compartmentalized outdoor type cubical panel board made out of not less than 1.6 mm thick CRCA sheet, the sheet steel member shall be stiffened by angle iron framed. The depth of cubical panel shall not be less than 300 mm and suitable sizes earth strip shall be provided around the cubical panel. The cubical panel shall be of suitable size to incorporate following switchgear i/c connections, powder coating of approved colour and shades complete etc. as reqd. Panel should be fixed on CC foundation/ angle iron frame work.250A, 25KA, 4P incomer MCCB-1 No.200A, 25KA, 4P MCCB-1 No.125A, 25KA, 4P outgoing MCCB-02 Nos.63A DP 10KA MCB-2 Nos.32/40A DP 10KA MCB- 3 NosCT's 250/5A class-1.0 15VA-03 NosDigital MFM -1 NoR,Y,B Phase Indicating Lamp-03Nos300A TPN, 415 volt Aluminium Bus BarExtended Rotating Handle -04 NosThree phase energy meter housing of approved size =01 No.63A FP 30mA RCCB with mounting plate-01No. |
| 60 | Disamntling of existing panel with suitable mechanical means at site and repair the same and store the electrical panel as per instruction of site engineer complete etc as reqd. |
| 61 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. a) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 62 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 63 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 64 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 65 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 66 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 67 | Credit for dismantle materials |
| 68 | Assorted : Ceiling Fan |
| 69 | Assorted : Exhaust Fans |
| 70 | Assorted : Switch/socket/regulator/ (Piano/Modular) |
| 71 | Assorted : SP /DP MCB upto 63 A |
| 72 | Assorted : SP MCB DB |
| 73 | Assorted : Al. Wire with insulation |
| 74 | Assorted : copper Wire with insulation |
| 75 | Assorted : GI Box with modular plate/phenolic sheet |
| 76 | Assorted : LED batten/Downlighter/fl. Fitting |
| 77 | Assorted : Fresh Air Fan |
| 78 | Assorted : Panel |
| 79 | Assorted : cable Please Enable Macros to View BoQ information |