| 1 | Taking down existing unserviceable point wiring of any type/ size of light/fan/socket/two way/bell etc on TW batten/conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc and removal of unserviceable material out of site area complete all as specified & directed. |
| 2 | Taking down existing unserviceable light fittings, security light fittings, bulk head fittings, fall ceiling light fittings etc. from any height of building complete all as specified & directed. |
| 3 | Taking down existing unserviceable Distribution boards of any capacity complete all as specified & directed. |
| 4 | Taking down existing unserviceable MCB's/MCCB's of any capacity complete all as specified & directed. |
| 5 | Taking down earthing material complete plate and pipe etc from 2.25 mtrs depth complete all as specified and directed. |
| 6 | Taking down existing unserviceable submain wiring complete all as specified and directed. |
| 7 | M&L for Point wiring one light/bell point controlled by one, one way switch complete with 1.5 sqmm single core PVC insulted FRLS cable 1100 volts grade multi stranded copper conductor drawn through in and including 20mm dia PVC rigid non-metallic conduit with all accessories such as internal bend, end caps etc complete concealed in walls and surface in ceiling/roof/etc including 1.5 Sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor cable as earth continuity conductor including fabricated branded modular metal flush box concealed in walls with suitable modular plate with cover with suitable screws for housing switches, socket outlets, fan regulators etc complete all as specified and directed. |
| 8 | All as per item No 7 herein before but one ceiling/exhaust fan point controlled by one, one-way switch complete all as specified and directed. |
| 9 | All as per item No 7 herein before but one 05 Amps socket outlet point on same board complete all as specified and directed. |
| 10 | All as per item No 7 herein before but one switch socket outlet points 5 Amps on independent board complete all as specified and directed. |
| 11 | All as per item No. 7 here-in-before but with copper conductor cable FRLS, 4.0 Sqmm for one 3 pin socket outlet, 15 Amps and including 4.0 Sqmm PVC insulated copper conductor cable as earth continuity conductor on independent board complete all as specified and directed. |
| 12 | Supply and fixing Switch Modular 6A single pole, one way, 1 module complete all as specified and directed. |
| 13 | Supply and fixing Switch Modular 16A single pole, one way, 1 module complete all as specified and directed. |
| 14 | Supply and fixing Socket, 6A - 2/3 pin combined 2 modules complete all as specified and directed. |
| 15 | Supply and fixing socket Modular 6/16A 2/3 pin combined 2 modules complete all as specified and as directed. |
| 16 | Supply and fixing Modular ceiling fan regulator stepped socket size, 2 modules suitable to work on 230 volts complete all as specified, complete all as specified and as directed |
| 17 | Supply and fixing ceiling rose three terminal surface Bakelite type AC 50 Hz 230 volts of size 65 x 50 mm complete all as specified and directed. |
| 18 | Supply and fixing 3 in 1 LED 4 ft batten 20 Watt (warm white, Neutral white, cool white), aluminium extrusion input voltage range 250 V, input frequency 50 Hz, efficacy not less than 120 Lumen/Watt, rated life 50000 Burning hours including 2 nos PVC Connector blocks electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. |
| 19 | Supply and fixing LED light fitting mirror type with high output diffuser 2 feet, 10-watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. |
| 20 | Supply and fixing flood light 150-Watt 230 V AC outdoor type with thermal management in multiple optics and equipment with IP66 protection including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 21 | M&L for repairing and servicing of flood light of up to 150-Watt 230 V AC outdoor type with thermal management in multiple optics and equipment with IP66 protection including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. |
| 22 | Supply and fixing MCB SP 6 to 32 Amps 240 volts C type with rupturing capacity 10 KA complete all as specified and directed. |
| 23 | S & F MCB SPN 40 to 63 Amps 240 volts C type with rupturing capacity 10 KA complete all as specified and directed. |
| 24 | Supply and fixing MCB TPN,100 Amps, rupturing capacity 10 KA 415 volts suitable for fixing in existing DB of any capacity complete all as specified and directed. |
| 25 | Supply and fixing MCCB 415V, 16KA, 100 amps 4 Pole thermal magnetic release fixed type, short circuit and over load protection suitable for DB including removing the existing unserviceable one complete all as specified and directed. |
| 26 | Supply and fixing sheet metal enclosure MCB DB SPN 4-way double door with 100 amps rated aluminium bus bar 240 volts double door with locking system complete all as specified and directed. |
| 27 | Supply and fixing sheet metal enclosure MCB DB SPN 8-way double door with 100 amps rated aluminium bus bar 240 volts double door with locking system complete all as specified and directed. |
| 28 | Supply and fixing MCB DB, TPN, 4 ways, double door, 415-volt, Isolated neutral bar with IP54 protection, door earthing arrangement with cement spill protector, mechanical impact strength IK09 complete all as specified and directed. |
| 29 | Supply and fixing TPN DB 4-way double door vertical load line with incoming as MCCB TP 415 volts AC 3 phase 50 Hz with fixed magnetic setting for current rating of 100 Amps 16 KA ,4P made out of CRCA sheet housing duly powder coated & confirming to IS specification with busbar rating not less than 160 A complete all as specified and directed. |
| 30 | Supply and fixing Triple pole and Neutral enclosure with a two pin and earth plug and socket complete with one triple pole MCB (AC Box) complete all as specified and directed. |
| 31 | Supply and fixing Single pole and Neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps (AC Box) all as specified and directed. Please Enable Macros to View BoQ information |
| 32 | Supply and fixing Single pole and Neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps (AC Box) all as specified and directed. Please Enable Macros to View BoQ information |