| 1 | Excavation in trenches in hard/dense soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc and getting out complete all as specified and directed. |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 3 | Removing excavated soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 4 | M&L for Sand cushioning using Ganga River sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and directed.Note : Punned thickness shall be considered for payment. |
| 5 | M&L Burnt Bricks, Sub Class 'B' of designation 75, standard size laid in trenches as in protection of UG cables complete all as specified and directed. |
| 6 | Taking up or down unserviceable steel tubing and connections of sizes 50 mm / 80 mm or above |
| 7 | M&L in replacement of GI tubing light grade 50 mm bore as in cable protection fixed to poles/walls or laid intrenches/under road crossing etc complete all as specified and directed. |
| 8 | Description same all as per item No 7 here-in-before but for 80 mm bore |
| 9 | M&L for boring of holes under road pavement hard standing by manual boring including making good the disturbed surfaces complete all as specified and directed. |
| 10 | Taking down old unserviceable UG cable of any size. |
| 11 | M&L of laid in trench/ducts/through pipes/in floors/under roads/under hard standing/along poles and testing cross linked polytehylene (XLPE) LT cable XLPE insulated, PVC inner sheathed, bedded, galvanised steel strip or wire armoured heavy duty 1100 Volts grade with stranded aluminium conductor having cross sectional area 300 Sqmm, 3.5 core and conforming to IS-7098 (Part-I-1988 & as per latest amendments) complete all as specified and directed. |
| 12 | Description same all as per item No 11 here-in-before but for 3.5 core, 240 Sqmm |
| 13 | Description same all as per item No 11 here-in-before but for 3.5 core, 185 Sqmm |
| 14 | Description same all as per item No 11 here-in-before but for 3.5 core, 150 Sqmm |
| 15 | Description same all as per item No 11 here-in-before but for 3.5 core, 120 Sqmm |
| 16 | Description same all as per item No 11 here-in-before but for 3.5 core, 95 Sqmm |
| 17 | Description same all as per item No 11 here-in-before but for 3.5 core, 70 Sqmm |
| 18 | Description same all as per item No 11 here-in-before but for 3.5 core, 50 Sqmm |
| 19 | Description same all as per item No 11 here-in-before but for 4 core, 25 Sqmm |
| 20 | Description same all as per item No 11 here-in-before but for 2 core, 10 Sqmm |
| 21 | M&L for cleaning, dusting and servicing LT panel Indoor/Out door, MCCB/ACB Panel , Bus bars tightening cable connections, providing lugs, cable glands and replacing of worn out parts such as busbar spout, spacers, hinges, locks and connected items/Mechanical parts etc for its smooth functioning including Internal spray Paiting of the panel, insulation of busbar, replacement of control wiring, cleaning the disturbed area beneath the LT panel and removing vegitation, derbis and replacement following items in the existing out door/indoor LT panels including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using locking arrangement & gasketed made of CRCA sheet 2 mm thick including hing & welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. Note : 1. New Items/switch gear etc required to be considered separately and paid in respected items. 2. All fabrication cleaning, painting etc shall be included in unit rate. |
| 22 | M&L in replacment of MCCB, 4 pole, 415 Volts, 63 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 23 | M&L in replacment of MCCB, 4 Pole, 415 Volts, 100 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs incl disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 24 | M&L in replacment of MCCB, 4 pole, 415 Volts, 125 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 25 | M&L in replacment of MCCB, 4 pole, 415 Volts, 160 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 26 | M&L in replacment of MCCB, 4 pole, 415 Volts, 200 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 27 | M&L in replacment of MCCB, 4 pole, 415 Volts, 250 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs incl disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 28 | M&L in replacment of MCCB, 4 pole, 415 Volts, 315/320 Amps, 36 KA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using welding wk and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 29 | M&L in replacment of MCCB, 4 pole, 415 Volts, 400 Amps, 36 KA, 50 Hz, AC, adjustable type, in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs including disconnection & connection of cable and making necessary alteration in panel/door using welding work and cutting as required for proper fixing & connection and testing complete all as specified and directed. |
| 30 | Supply and fixing of MCB TPN 63 Amps, 'C' Curve, 10 KA rupturing capacity complete all as specified and directed. |
| 31 | M&L for servicing of ACBs 800/1000 Amps rating by disconnect and taking out the breaker after taking power shut down of the respective panel and overhauling/servicing the ACB by opening all parts and cleaning of electrical contacts with CTC/rust remover, lubricating electrical moving parts with petrolium jelly and mechanical moving parts with grease & applying Becktrol red solution to the surface of the bus bars and spouts, applying Monoplast compound at the bus bar joints after tightening of joints and replacing defective spare parts like springs/bolts/nuts/washers etc, including testing, calibrating, refixing the circuit breaker and make fuctional complete all as specified and directed. |
| 32 | Disconnecting Electrically items and cleanig of LT Panel for Internal/External Spray Painting complete of any capacity after preparation of surface and applying two coats of synthetic enamel (smoke grey) paint and old steel surafce, replace the Danger notice plate, Insulation of busbar etc complete all as specified and directed. |
| 33 | S&F in replacement of Analog voltmeters 0-500 Volts, with all connected accessories including connecting up and testing complete all as specified and directed, Make : RISHABH/ MECO/HAGGAR |
| 34 | S&F in replacement of Analog Ammeter 0-600 Amps (minimum) with CT's, all connected accessories including connecting up and testing complete all as specified and directed, Make : RISHABH/MECO/HAGGAR |
| 35 | S&F in replacement of LED indicator lamp 240 Volts, with suitable colour Red/Blue/Yellow/ Amber/Green and connected acccessories complete all as specified and directed, Make : L&T/Siemens/Mnilec/Aes |
| 36 | S&F in replacement of push button switch with NO/NC contacts 415 Volts, 6 Amps, with add on Aux Contacts and connected acccessories complete all as specified and directed, Make : L&T/Siemens |
| 37 | S&F in replacement of Rotatory selector switch 3/4 way 10 Amps for Panel meter including connection complete all as specified and directed, Make : L&T/Simens/Minilec |
| 38 | S&F of Copper Cable single core 2.5 Sqmm for panel control wiring |
| 39 | S&F of Bus bar, Bus bar spout, Glands, Nut, Bolts etc for panel |
| 40 | S&F of Aluminium Lugs dove tail type set of three for panel |
| 41 | Cutting/pruning of tree branches along/around over head LT line at places within a radius of 2 mtr from fasted conductor and removing from site complete all as specified and directed. |
| 42 | Trimming/cutting of tree/removal of bushes/removal of vegetation growth/cutting trunk portion protruding over ground, digging out roots arround 2 mtr radius of LT panel and removal from site complete all as specified and directed.Note : This job may be repeated after three month at the same location. |
| 43 | M&L in replacment of ON LOAD change over switch with sheet metal enclosure 415 Volts, 4 pole of capacity 250 Amps including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and directed, Make : Havells Cat Part No IHCNFO0250. or equivalent makes as approved by GE |
| 44 | M&L in replacment of ON LOAD change over switch with sheet metal enclosure, 415 Volts , 4 pole of capacity 315/320 Amps including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and directed, Make : Havells Cat Part No IHCNFO0320 or equivalent makes as approved |
| 45 | S&F in replacement of sheet metal enclosure made out of 2mm thick CRCA sheet duly power coated suitable for fixing/mounting MCCB of 160 Amps 4 pole duly fixed on wall with all fixing arangements complete all as specified and directed. |
| 46 | S&F in replacement of sheet metal enclosure made out of 2mm thick CRCA sheet duly power coated suitable for fixing/mounting MCCB of 250A Amps 4 pole duly fixed on wall with all fixing arangements complete all as specified and directed. |
| 47 | Dismantling & taking out defective LT PVC/XLPE cable from trenches with cutting and removing defective parts and supply & making cable joint using straight through joint cold shrink type and making connection of LT cables, meggering & re-storation of electric supply complete including jointing material for size of 25 Sqmm 3.5 core to 70 Sqmm, 3.5 core of cable joint complete all as specified and directed. |
| 48 | Description same all as per item No 47 here-in-before but of 95 Sqmm, 3.5 core to 240 Sqmm, 3.5 core |
| 49 | Disconnecting of OH line of ACSR conductor/GI earthing wire, opening of binding wires, jumper connections any size and restringing, tightening of conductor with suitable line vice, replacing all worn out jumper connection with suitable conductor, re-tightening and straightening all cross arms, insulators, clamps etc including replacement of all wornout nut bolts and washers complete all as specified and directed. |
| 50 | Dismantling & taking out old steel tubular pole 9/11 mtr long carefully from foundation for re-use, shifting and re-fixing/re-erecting at other location within New Cantt area including following complete all as specified and directed :-(a) Excavation in post hole not exceeding 1.5 mtr wide & 2 mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers not exc 25 cm thick and disposal of surplus soil to a distance not exc 50 mtr.(b) M&L for Providing PCC 1:4:8, type D2 ( using 40mm graded stone aggregate) in foundation 600 x 600 x 1500mm (planting depth) for concrete encasing the pole upto GL all as specified and directed. (c) M&L for Providing PCC 1:3:6, type C2 (using 20mm graded stone aggregate) for plinth block /Collar above GL, 300mm high and 450 x 450mm size. (d) M&L for Painting of pole externally with one coats of black bituminous paint (upto planting depth) and above plinth block/concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 mtr above plinth block. |
| 51 | M&L for applying two coats of aluminium paint over a coat of red oxide on Steel tubular pole of following length including cross arms and clamps except embedded portion of pole in ground including copping after removing old painted surfaces by scraping of poles complete and making colour brand with synthetic enamel paint of approved colour up to 1.2 mtr from coping level including numbering of poles in red colour paint and paintng of coping complete all as specified and directed. |
| 52 | S&F in replacement steel tubular electric pole, swaged type, welded (9 mtr long) single swan neck type complete with CI base plate, bolts, nuts & screws all as specified including the following, complete all as specified and directed :- (a) Excavation in post hole not exceeding 1.5 mtr wide & 2 mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers not exc 25 cm thick and disposal of surplus soil to a distance not exc 50 mtr. (b) M&L for Providing PCC 1:4:8, type D2 (using 40mm graded stone aggregate) in foundation 600 x 600 x 1500mm (planting depth) for concrete encasing the pole upto GL. (c) M&L for Providing PCC 1:3:6, type C2 (using 20mm graded stone aggregate) for plinth block /Collar above GL, 300mm high and 450mm dia. (d) M&L for painting of pole externally with one coats of black bituminous paint (upto planting depth) and above plinth block/concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 mtr above plinth block. |
| 53 | Description same all as per item No 52 here-in-before but double swan necked type pole complete all as specified and directed |
| 54 | M&L for dismanteling of of old damaged/cracked PCC coping and prepare the new coping for steel/PCC pole using PCC 1:3:6 type D-2 with 20mm graded stone aggregate making collar above ground level on existing foundation of pole size 450 x 450 x 300mm high and plastering with 1:4 cement sand mixter for smooth look including curing to achieve the strength and breaking/removing existing old damaged coping complete all as specified and directed. |
| 55 | Repair of earth pit including required excavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8mm bars at 150mm centre to centre both ways incl supply & fixing of wire mess and funnel including re-connection of earth wire/strip with panel/transformer using GI nut, bolts washer complete all as specified and directed. |
| 56 | S&F in replacement of Danger notice plates, made out of 1.6mm thick MS sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for LT 20 x 15 cm size, fixed as in repairs, complete all as specified and directed. |
| 57 | Supply in replacement of installing, testing and commisioning of CPRI approved LT cubical panel board 440 Volts, 50 Hz, 3 phase, 4 wire, out door type > IP 65, weather, vermin, dust proof, front operated with adequate air ventilation at sides and back fabricated out of 3.00 mm thick CRCA sheet with double door shutter and locking arrangements, cables trays, cable lugs, cable gland etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables, danger board etc, floor mounted with PCC 1:2:4, type B1 platform of 50 cm height suitable nut bolts, washer etc for grouting, and painting with power coated epoxy finish of approved colour over a coat of red oxide primer suitable to accomodate and including the following mentioned fittings comprising the following complete all as specified and directed :-(i) Bus bar chamber consisting of four Nos Copper bus bars duly sleeved of capacity of 600 Amps for phases and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment.(ii) Digital Voltmater and Ammeter three line display ( L1 L2 L3 ) with suitable CT's.(iii) LED type indicating lamps (RYB) with holders controlled by fuses and swicthes .(iv) Panel board internal wiring with suitable rated PVC insulated copper conductors.(v) MCCB 3 Phase 415V, 400 Amps 4 pole 36 kA (Ics=100 % of Icu) , Adjustable magnetic and fixed thermal - 1 No (I/C)(vi) MCCB 3 Phase 415V, 160 Amps 4 pole 36 kA (Ics=100 % of Icu) , Fixed magnetic and Fixed thermal - 5 No (O/G) (01 Spare). |
| 58 | Supply, installing, testing and commisioning of CPRI approved LT cubical panel board 440 Volts, 50 Hz, 3 phase, 4 wire, indoor type >IP 65, weather, vermin, dust proof, front operated with adequate air ventilation at sides and back fabricated out of 3.00 mm thick CRCA sheet with double door shutter and locking arrangements, cables trays, cable lugs, cable gland etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables, danger board etc, floor mounted with PCC 1:2:4, type B1 platform of suitable height suitable nut bolts, washer etc for grouting, and painting with power coated epoxy finish of approved colour over a coat of red oxide primer suitable to accomodate and including the following mentioned fittings comprising the following complete all as specified and directed :-(i) Bus bar chamber consisting of four Nos Aluminium bus bars duly sleeved of capacity of 400 Amps for phases and 200 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment.(ii) Digital Voltmater and Ammeter three line display ( L1 L2 L3 ) with suitable CT's.(iii) LED type indicating lamps (RYB) with holders controlled by fuses and swicthes.(iv) Panel board internal wiring with suitable rated PVC insulated copper conductors.(v) MCCB 3ø phase 415V, 250 Amps 4 pole 35 kA (Ics=100 % of Icu) , Adjustable magnetic and fixed thermal - 1 No (I/C)(vi) MCCB 3ø phase 415V, 160 Amps 4 pole 25 kA (Ics=100 % of Icu) , Adjustable magnetic and Fixed thermal - 4 No (O/G)(viii) MCCB 3ø phase 415V, 100 Amps 4 pole 25 kA (Ics=100 % of Icu) , Adjustable magnetic and Fixed thermal - 1No (O/G) |
| 59 | M&L for earthing complete with Galvanized Steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including GI wire of 4mm dia connected by means of GI bolts, nuts, and washers, protected by 15mm bore GI light grade ISI marked pipe upto and including test points. Earthing plate shall be surrounded by alternate layers 15 cm thick of charcoal or coke and common salt all around bottom and top, 20mm dia GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C2 (using 20mm graded crushed store aggrgate) including necessary form work, excavation and earth work in any type of soil, returning filling in and disposal of surplus soil to a distance not exceed ing 50 mtr, pit cover 40 mm thick made with RCC (1:2:4) type B-1 (using 20mm graded crushed store aggrgate) including TMT reinforcement 80mm dia @ 75 mm C/C both way, MS handle of 12 mm dia, cover rest on MS angle iron frame 40 x 40 x 6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, as shown in electrical plate No-3 of SSR Part-I complete all as specified and directed. |
| 60 | M&L for earthing complete with Galvanized Steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including GI iron strip of size 32 x 6mm flat by means of GI bolts, nuts, and washers, protected by 40mm bore GI light grade ISI marked pipe upto and including test points earthing plate shall be surrounded by alternate layers 15cm thick of charcoal or coke and common salt all around bottom and top, 20mm dia GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C2 (using 20mm graded crushed store aggrgate) including necessary form work, excavation and earth work in any type of soil, returning filling in and disposal of surplus soil to a distance not exceed ing 50 mtr, pit cover 40mm thick made with RCC (1:2:4) type B-1 (using 20mm graded crushed store aggrgate) including TMT reinforcement 80mm dia @ 75mm C/C both way, MS handle of 12mm dia, cover rest on MS angle iron frame 40 x 40 x 6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and as shown in electrical plate No-3 of SSR Part-I and all as directed. |
| 61 | M&L for laying earth continuity conductor GI Strip 32 x 6mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc complete all as specified and directed. |
| 62 | M&L for laying earth continuity conductor GI wire 4 mm dia fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc complete all as specified and directed. |
| 63 | Schedule of Credit (MINUS) Rs. 60,204.00 B/F from Serial Page No. ____ [Note : Details of items for schedule of credit is given on Srl Page No. ___] This amount shall be automatically deducted to arrive at tendered sum Please Enable Macros to View BoQ information |