| 1 | Construction and commissioning of RCC flat slab Over Head Service Reservoir of following capacity and staging including all material and labour charges as per the Scope of work and Technical Specification, consisting of the following main activities: - |
| 2 | a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc.c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil. d) Providing and applying two coats of food grade epoxy paint on the inside surface roof slab, and 600 mm height of the vertical wall.e) Successfully hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the top surface of the roof slab.g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc.h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top Slab to bottom Slab inside container. i) Providing and fixing of MS section ladder from the last landing to balcony and MS ladder with safety cage from balcony to top slab. |
| 3 | j) Providing and fixing water level indicator (float type).k) Providing and fixing of hand railing all around the balcony, roof and staircase, consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle iron vertical post at a maximum spacing of 1500mm centres.l) All MS parts to be painted with two coats of the enamel paint over the primer coat of red oxide.m) Providing and fixing of 150mm wide PVC water bar for the construction joints in the container (vertical wall & cone wall).n) Providing one Aluminium portable ladder of appropriate length to access first landing (3.5 to 4.5m above GL) from ground.o) Lighting arrestor consisting of providing and fixing of 2 Nos. of chemical earthing and connecting it to the conical cover of SS ventilator with two separate GI strips of 50mmX3mmp) CI/DI puddle collar shall be fixed in the bottom/slab for connecting inlet, outlet, overflow and washout pipe of the reservoir.q) Painting the name of the scheme and other details on the reservoir, and any other work related to structure as per the directions of Engineer-in- Charge, Technical Specification and Scope of Work.r) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. |
| 4 | Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-II & STAGING 15 M |
| 5 | 50 KL capacity |
| 6 | Construction of RCC (Flat slab type) Clear Water Reservoir of following capacity as per the Scope of work and Technical specification, consisting of the following main activities: - |
| 7 | a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour and material charges including providing and fixing of accessories such as SS ladder, SS manhole frame and covers, water level indicator (float type), SS ventilator with SS screen, float valve, puddle collars, G.I. pipe railing around walk way, Top Dome/Slab, Staircase.c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall. e) Successful hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab.g) Providing and applying three coats of cement-based paint on the remaining external surface area of the structure. |
| 8 | Rates for RCC Partially Underground type clear water reservoir SBC 7 T/sqm, SEISMIC ZONE2,3 & 4 |
| 9 | 50 KL capacity |
| 10 | Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required such as duck foot bend, bend, tee etc. providing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. |
| 11 | 100 mm |
| 12 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - SS 304 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date), All exposed machined ferrous surfaces shall be painted with one coat of aluminium red oxide primer conforming to IS:5660 and two coats of black Japan paint conforming toType B of IS 341or paint conforming to IS9862 or IS2932( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538.Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel.Insersion rubber of black EPDM 6mm thick . Suitable support structure as per directions of EIC. Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 13 | Manually Operated CI Sluice valve of Class PN-1.0 |
| 14 | 100 mm HW |
| 15 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - SS 304 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date), All exposed machined ferrous surfaces shall be painted with one coat of aluminium red oxide primer conforming to IS:5660 and two coats of black Japan paint conforming toType B of IS 341or paint conforming to IS9862 or IS2932( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538.Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel.Insersion rubber of black EPDM 6mm thick . Suitable support structure as per directions of EIC. Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 16 | Manually Operated CI Sluice valve of Class PN-1.0 |
| 17 | 100 mm HW |
| 18 | Supply & Installation of 3 phase ISI marked submersible motor pump set of five star rating by BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, |
| 19 | Up to 5.5 KW (7.5 HP) & head up to 120 mtr. |
| 20 | Providing & Lowering in tubewell ISI marked GI Pipe “B\\" (medium) class as per IS:1239 part I 2004 or amended up to date, threaded and double flanged (welded) on both ends and two number 25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect.. 50 mm dia |
| 21 | Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. 3 core 4.0 Sq.mm |
| 22 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 23 | 16.0 Sq.mm, 4 core |
| 24 | Supplying and fixing of electric control feeder panel comprising of suitable rating MCCB, fully automatic star-delta starter,over load relay,ampere meter with CTs ,volt meter,phase preventor,suitable starting capacitors,phase indicators,lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter (supplied by DISCOM) All these equipments shall be housed by panel box made from 18 guage MS sheet with powder coating.Panel should be of minimum size 900x600x450 mm with stand(made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having four legs, each leg's length 18\\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete platform.The size of CC platform should be equal or bigger than the base size of panel having height of atleast 200 mm ground level.The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 volt AC supply. |
| 25 | Above 5 HP and up to 10 HP |
| 26 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended upto date), with internal cement mortar lining suitable for potable water with rubber ring (EPDM) joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges, including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work) Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. |
| 27 | 100 Dia DI K-7 Pipe line at various Village in |
| 28 | Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended upto date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) . Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply may be in coil or straight length in 6 M/12 M. |
| 29 | 63 mm dia |
| 30 | 75 mm dia |
| 31 | 90 mm dia HDPE pipe PE 80 PN 6 |
| 32 | 110 mm dia HDPE pipe PE 80 PN 6 |
| 33 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 34 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge. |
| 35 | MS pipe specials up to 600mm dia (with minimum 5mm thickness sheet) |
| 36 | Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes |
| 37 | 65 mm dia |
| 38 | 80 mm dia Please Enable Macros to View BoQ information |