| 1 | Dismantling of existing 250 KVA E/A set with canopy from the existing foundation i/c disconnection of power cable, Control panel, Fuel tank, Earthing strip, exhaust pipe and fuel piping etc complete as reqd. |
| 2 | Transportation of existing 250 KVA E/A set with canopy complete with all accessories i.e power cable, Control panel, Fuel tank, exhaust pipe and fuel piping from T.Exch. Shahdara East, Gzb to T.Exch. Sector-19, Noida i/c loading the same in suitable vehicle with the help of specialize man power and crane at T.E Shahdara East and unloading the same at T.E Sector-19, Noida etc complete as reqd. (Approx. distance 15 Kmtrs) |
| 3 | Dismantling of existing 320 KVA E/A set with canopy from the existing foundation i/c disconnection of power cable with the help of specialized man power, placing the same at other specified location with the help of crane as per instruction of Engineer in charge i/c making cable connections, earth strip etc to make the DG set ready to use for feeding power supply during loading / unloading of other DG set. etc complete as reqd. (Sector-19, Noida) |
| 4 | Dismantling of existing 600 KVA E/A set with canopy i/c disconnection of power cable, Control panel, Fuel tank, Earthing strip, exhaust pipe and fuel piping etc complete as reqd. |
| 5 | Transportation charges of existing 600 KVA E/A set with canopy complete with all other accessories from T.Exch. Sector-19, Noida to T.E Bldg. Shastri Nagar, Meerut with the help of specialize man power and crane i/c loading /unloading in Shastri Nagar, Meerut etc. complete as reqd. (Approx. distance 74 Kmtrs) |
| 6 | ITC of 320 KVA E/A set with canopy with control panel etc on the existing foundation i/c connection of power cable, fuel piping, exhaust piping, control cable, testing at load etc complete as reqd. (Sector-19, Noida) |
| 7 | ITC of 250 KVA E/A set with canopy with control panel etc on the existing foundation i/c connection of power cable, fuel piping, exhaust piping, control cable, testing at load etc. complete as reqd. (Sector-19, Noida) |
| 8 | Cutting and dismantling of the existing M.S shed side pipe obstructing the removal of DG set re-fixing of the cut M.s pipe to restore the shed to its original condition i/c cutting, welding, painting etc. complete as required. |
| 9 | Dismantling of existing 725 KVA E/A set with canopy from the existing foundation i/c disconnection of power cable with the help of specialize man power and hydra crane i/c placing the same at other location in same premises. Etc. complete as reqd. (Shastri Nagar, Meerut) |
| 10 | ITC of 600 KVA E/A set with canopy with control panel etc. (Shifted from T.E sector-19, Noida) on the existing foundation i/c making connection of power cable, fuel piping, exhaust piping, control cable and loading unloading with specialize man power and hydra crane, testing at load etc. complete as reqd. |
| 11 | Supplying, Installation, Testing & commissioning of Maintenance Free chemical earth station as per latest RDSO specification consisting of: - a) Steel electrode, High Tensile, low carbon molecularly bonded with copper on outer surface as per UL requirement of 3 Mtrs long, 17 mm dia with copper bonded thickness of minimum 250 microns and a copper coated low carbon steel strip of 300mm x 25mm x 6mm with suitable hole shall be exothermically welded to main Earth electrode for taking the connection to main earth bus = 01 No. b) Earth Enhance material, Maintenance free, environmentally friendly, Mineral compounds, semi soluble, non-corrosive, conductivity improving material confirming to IS 62561 Part 7 of RDSO approved) = 30-35 Kgc) Poly plastic, Heavy duty, weather-proof, environmental free earth pit chamber with cover size about top dia 250mm bottom 330mm and height 260mm. Heavy duty of 7 TON load capacity, the base unit should have knockouts for interconnection of strips. Note:- a) Earth resistance at Main Earth bus bar should be up to 1.0 Ohm. b) Measurement of earth resistance will be done after 24 hour as per RDSO specification. c) Chemical Earthing work should be strictly carried out as per RDSO Specification attached. d) The above work is all inclusive i/c transportation, T&P and testing at site complete as required. |
| 12 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 13 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. Please Enable Macros to View BoQ information |