| 1 | Supplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:\\"(A) Diesel Engine:(Detailed specification mentioned in SOQ of NIT(B) Engine mounted Instrument Panel fitted with and having digital dis Plate (Detailed specification mentioned in SOQ of NIT)(C) Alternator (Detailed specification mentioned in SOQ of NIT)(D) Base Frame & Foundation (Detailed specification mentioned in SOQ of NIT)(E) Fuel Tank (Detailed specification mentioned in SOQ of NIT)(F) Exhaust system (Detailed specification mentioned in SOQ of NIT)(G) Starting system (Detailed specification mentioned in SOQ of NIT)(I) AMF Panel (Detailed specification mentioned in SOQ of NIT) |
| 2 | 250 KVA |
| 3 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 4 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 5 | Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 6 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 7 | Supplying and installation following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 8 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 9 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 10 | 3½ X 240 sq. mm (62mm) |
| 11 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 12 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 13 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 14 | Providing of 3½ X 240 sq. mm one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 15 | Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in |
| 16 | Cement mortar 1:6 (1 cement : 6 Coarse sand) |
| 17 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete |
| 18 | Hot finished welded type tubes |
| 19 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. |
| 20 | Nominal concrete 1:3:6 or richer mix (including equivalent design mix) |
| 21 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge |
| 22 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05mm) with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /seIf tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 23 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade: |
| 24 | Two or more coats on new work |
| 25 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in- charge. |
| 26 | Made of G.I. wire of dia 4 mm |
| 27 | 12 mm cement plaster of mix : |
| 28 | 1:6 (1 cement: 6 coarse sand) |
| 29 | Annual Comprehensive maintenance of 250 KVA DG systemNote: Comprehensive maintenance during the warranty period of one (01) year shall be included in the contract cost and no separate payment shall be admissible. |
| 30 | CAMC cost for 1st year (after completion of warranty period of 01 year |
| 31 | CAMC cost for 2nd year |
| 32 | CAMC cost for 3rd year |
| 33 | CAMC cost for 4th year Please Enable Macros to View BoQ information |