| 1 | Supply, laying, testing & commissioing of 25 Sqmm 4 core size XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 Part I marked, suitable for LT 1100 Volt system,laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe including jointing & testing all as specified and as directed. Make- Havells/Polycab/KEI/Finolex Note :- Excavation, earth work ,cable protection , sand fillings shall be measured and paid separately under respective items of schedule. |
| 2 | All as per Ser No 1 above but size 16 sqmm 4 core |
| 3 | All as per Ser No 1 above but size 10 sqmm 4 core |
| 4 | All as per Ser No 1 above but size 10 sqmm 2 core |
| 5 | All as per Ser No 1 above but size 6 sqmm 2 core |
| 6 | Taking out faulty underground LT 1100 volts grade heavy duty, armoured with steel strip of wire, with stranded aluminium conductor of sizes up to 25 Sqm 3.5/4 core by excavation and relaying same laocation or any other location rectification of fault and removing of surplus soil.Note: Excavation, stone for cable cover, tibba Sand and earth work will be measured and paid for seperately under respective items of schedule. |
| 7 | Excavation in trenches in soft/ loose soil n.exc 1.5mtr wide and not exc 1.5mtr in depth and getting out complete all as specified. |
| 8 | All as per item No 7 here in before but exc 1.5 mtr or part there of in depth beyond the first 1.5 mtr depth complete all as specified. |
| 9 | M&L for tibba sand locally available sand filling in trenches dry and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified. |
| 10 | M&L for laying jodhpur stone quarry stone slab cover 25 to 30cm in width, 60cm long and 40 to 50 mm thick laid in trenches and abutting each other with gap between adjacent slab not exceeding 10mm over sand covered under ground cables complete all as specified. |
| 11 | Returning, filling, in including spreading, leveling , watering and well ramming in layers n.exc 25 cm in soil complete all as specified. |
| 12 | Removing excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtrs above the starting point complete all as specified. |
| 13 | Material and labour plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in base of the pole as a foundation or in any situation complete all as specified. |
| 14 | Material and labour plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of the pole by demolition of existing /broken coping with taking out the LT cables and GI pipe Etc and refixing in new coping or in any situation complete all as specified. |
| 15 | M&L for Cutting the road / hard standings and excavating in trenches not exceding 0.40 mtr wide and not exc 0.80 mtr deep across the road for laying cable including making good the excavated portion by means of PCC 1:2:4, type B1 using 20mm graded stone aggregate complete and matching with the surroundings complete all as specified. |
| 16 | Supply and fixing in replacement GI Pipe light grade 50 mm dia with necessary accessories/ fittings bracing with pol/wall by FI clamps made with 32x6mm for cable protections/pole for crossing of culverts/nallah and all as specified and directed sizes:- |
| 17 | All as per ser item No 16 above but of size 40 mm dia |
| 18 | Supply, Installation Testing and Commissioning in replacement of IP 66 protected LED Street Light Luminaire 90 watt on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with an aesthetically smooth finish and durable construction including with heat dissipation fins on housing with UV stabilized PC Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each. Luminaire shall be designed at a system efficacy of atleast 135 lumen/watt (NB) and maximum system wattage of 90 W and input Voltage AC 120 to 270 V AC with High voltage Cut off @>=300 V AC and Auto resetting Safety, Power Factor >0.95 driver Efficiency > 90%, THD (I) <10%, driver current <750 mA. CRI>70 and CCT 5700K +355K. Surge protection shall bemin ≥ 4 KV internal and optional 10KV external bolted inside driver compartment.(LM79/ LM80) Certificate /report with liable warranty of product /accessories from OEM shall be submitted. Make Phillps Cat Part No BRP 275 or equivalent in Crompton/Havells/Wipro |
| 19 | All as per Ser No 18 above but 60 watt. Make Phillps Cat Part No BRP 274 or equivalent in Crompton/Havells/Wipro |
| 20 | Supply & Fixing in replacement of LED flood light fitting 200 watt elegently designed, pressure die cast aluminium housing in power coated finish IP-66, lumen efficancy >= 130 lm/watt and total lumens output must be = 26000 lumens or more, operating voltage range 120- 270, P.F > 0.95, CCT- 5700K, surge protector of 10 KV in/out side fitting, driver of fitting shall be potted type only for vibration proof performance with inbuilt surge protector, over voltage protection. both fixture and driver must have separate BIS marked registration with clearly mentioned on fixture & as well as on driver seperately.The manufacture of the LED fitting shall have in house NABL accrediated LAB & contractor shall furnish same along with LM-79, LM-80, test report etc including making connection with 3 core x 1.5 FRLSH wire, all as per directed by Engr in Charge. Make Crompton Cat Part No EFS-532-200-857-NL-HL2-NS-LM-NTG or equivalent in Phillps/Havells/Wipro |
| 21 | All as per Ser No 20 above but 150 watt. Make Crompton Cat Part No EFS-530-150-857-NL-HL2-NS-LM-NTG or equivalent in Phillps/Havells/Wipro |
| 22 | Taking down defective street light/ flood light/ of any size wattages from height of pole/walls/high mast of any location up to 12M height for repair work and fixing back after repair work including checking, inspecting, testing and commissioning complete all as directed by Engr-in-Charge. Note :- (a) LED Drivers shall be measured and paid as supply only separetely under relavant items of schedule'A' (b) Necessary tools like mobile ladder & other T&P required etc shall be arranged by the contractor without any extra cost.(c) The rate quoted deemed to be inclusive for minor repair parts like nuts, bolts, cirle clips , clamps etc required if any at site. |
| 23 | Supply only electronic driver for LED light fitting, LED out put power 50 watt, input voltage range : 160 - 260 volt AC , out put voltage DC as per make/ model range: 24 volt to 110 volt, make as per site requirement complete all as directed. |
| 24 | All as per item No 23 above capacity 60 watt |
| 25 | All as per item No 23 above capacity 75 watt |
| 26 | All as per item No 23 above capacity 100 watt |
| 27 | All as per item No 23 above capacity 120 watt |
| 28 | All as per item No 23 above capacity 150 watt |
| 29 | S & F in replacement of Street light nature switch (using infrared sensor technology) based automatic street light control panel. the panel should be suitable enough to take SIngle Phase load of 5 KW. Nature switch operation should be based on natural light Lux* level. required illuminance level for switching ON is ≤ 60 Lux and for switching off ≥ 10 Lux. The sensor should also have part night operation facility of min. 4 hrs to max 12 hrs. The sensor alongwith suitable one Nos power Contractors and one Nos incoming SPN of 40 Amp & 1 Nos outgoing SPN of 40 Amp & circuit wiring (Copper) of min 10 sqmm with lug should be enclosed in a pole/wall mountable rust proof, electric shock proff, termite proof and FR grade SMC elclosure confirming to IP 66. The circuit should also have provision for Manual operation (i.e. Sensor by Pass option). Make- Healer Enterprised Model No NAVDEEP-66-5KW1P or equivalent from the list of make given in pareticular specification. |
| 30 | Supply, Installation Testing and Commissioning in replacement of LED Highbay luminaire of 140 watt with a housing of High Pressure Die casted Aluminium and polycarbonate front cover. The luminaire should have a color consistency SDCM < 5, CRI > 70 and CCT of 5700K. The luminaire shall be compliant with IP65 classification and impact protection of IK08 to ensure durablility. Luminaire shall be designed to emit 25000 nominal lumens at a system efficacy of atleast 180 lumen/watt(NB) and maximum system wattage of 140 W.The lumainaire shall have both Narrow beam(60°) and Extra Narrow beam (30°) options available to provide flexbility in applications. The luminaire shall be designed for operations under diverse environment from -10 deg C to 50 deg C.The electronic driver used shall have a power factor >0.95, efficiency 90% and THD <10% with a minimum inbuilt surge protection of 6kV, ripple<10% and suitable for an operationg voltage range of 120-270V AC. LM79 and LM80 reports must be submitted from a NABL accredited laboratory. Driver and luminaire shall be of same make. Product shall have 5 year warranty. Make Phillps Cat Part No BY712 LED 250S or equivalent in Crompton/Havells/Wipro |
| 31 | S&F in replacement of decorative post top lantern luminarie LED light of 30 W with IP 65 protection with die cast aluminium graphite grey powder coated finished body , polycarbonate opal diffuser, low power warm white (WW) LEDs with better heat dissipation, high efficient constant current electronic driver having operating voltage range from 140 to 280 Volt AC, provided with high voltage, open and short circuit protection, Voltage surge protection 10 KV etc complete suitable for 60 mm OD pipe entry complete all as specified.Note: The GI pipe if required will be measured and paid separately under relevant schedule 'A' items. |
| 32 | All as per item No 31 above capacity 30 watt |
| 33 | S&F in replacement of 32 mm dia GI pipe bracket (Light grade) bent to shape of length not less than 1.2 mtr including fixing on wall/pole using flat iron clamps of suitable size ,nuts,bolts,washers etc includig paint of two coats of alluminium paint over one coat of red oxide primer suitable for street light fittings all as specified and directed by Engr-in-charge. |
| 34 | Supply & fixing in replacement of PVC insulated, sheathed weather proof, copper conductor of size 1.5 sqmm, 3 core complete all as specified and directed. |
| 35 | M&L in replacement of PVC conduit 20 mm, heavy duty rigid non metallic including of all tee, bends, elbows etc complete all as specified and as directed. |
| 36 | Supply and Fixing in replacement of pole mounted junction box of inside dimension 240x130x110 made out of FRP body (hot mulded type) with IP-66 protection and locking with screws alongwith 5/6 Amp rating MCB SP-01 No, up to 100 Amp rated 3 pole connector suitable to insert the cable size up to 25 Sqmm-01 No,with neutral link and din rail suitable for mounting the MCB/Connector etc complete in side box and duly fixed on steel tubular pole/PCC/RCC pole including cable glands, aluminum lugs/thimbles for incoming and out going cales complete all as specified. |
| 37 | Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade 10- 25 Sqmm 4 core and including taking out cable from faulty portion in any situation/position complete all as specified. |
| 38 | M&L for painting black and white strips 05 Nos (each strips of 30 cm height) with synthetic enamel paint of black and white colour round the PCC/steel tubular pole alternatevely from the bottom of the pole and also including numbering of pole with black paint in Yellow background complete all as specified. |
| 39 | Restretching aluminium conductor or GI wire on existing over head lines without removing including unbinding from insulator and rebinding to insulator using aluminium binding wire, connections of incoming and outgoing cables, binding with spacers where required, complete all as specified Note :- (i) Length of span shall be 40 to 50 m.(ii) Due care shall be given while resagging of overhead conductor that there shall be no damage to pin/post/disc insulator and pole. In case, due to any negligence, damage is caused, it shall be made good by the contractor and nothing extra shall be admissible.(iii) Proper shut down will be taken from department and T&P will be provided by contractor |
| 40 | S&F PVC seperators/spacers clamp mounted on ACSR conductor suitable for 2/4 run |
| 41 | Trimming and cutting of tree branches coming across LT over head line, clearing alround 3m the LT line and disposal of branches/bushes to a distance upto 40/50m and cleaning the site complete all as directed.Note :- (i) Length of span shall be 40 to 45m.(ii) Due care shall be given while trimming/cutting the tree branches that there shall be no damage to over head line conductor/pole. In case, due to any negligence, damage is caused, it shall be made good by the contractor and nothing extra shall be admissible.(iii) Proper shut down will be taken from department and T&P will be provoded by conractor. |
| 42 | Supply and fix in replacement of pin type porcelain insulator, vitreous white brown or green including one galvanised mild steel spindle two GI washer and GI Nuts 100 mm height 65 mm dia for 1100 volts grade complete all as specified. |
| 43 | Supply and fix in replacement of shackle type porcelain vitreous white insulator 1100 volt grade 75 mm in height and 90 mm dia including galvanised mild steel strap of size 31mm x 3mm , 12 mm dia insulators bolts, washers and nuts complete all as specified. |
| 44 | S&F in replacement of down rod made of GI pipe 15 mm dia medium grade of 3 feet long including MS hanging hooks 2 Nos, nut bolt & washer, wall fastner 100 mmlong etc complete all as specified. |
| 45 | Supply and fixing in replacement of power contactor of 415 volts 50Hz, 40 Amp capacity with 230 volts operated coil on existing panel/Timer complete all as specified. |
| 46 | S&F in replacement of steel structure, as in cross arms, bracing supports ,clamps, back plates of any type, section incl. nuts, bolts, washers, welding ,bending cold or hot in any size and shape all as directed Including two coats of aluminium paints over & including M&L single coat of red oxide primer incl preparation of surface complete all as specified. |
| 47 | Supply and errecting of Prestressed concrete pole, 9.0 meter long, 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 including painting alternative black & white strips of 30 cm width upto 1.5 mtr above ground level and including dismantling and taking out the damaged/old PCC pole and setting aside within 50 mtr distance complete all as specified. Please Enable Macros to View BoQ information |