| 1 | Disconnection of existing APFC panel of any capacity/rating, form all incoming and outgoing electrical connections, checking serviceability of each components viz. capacitors, contactors, relays, MCB's, MCCB's, indicator lights, display meters, PF controller, etc., replacement of burnt out internal wirings with with suitable size FRLSH PVC insulated multistranded copper conductor wires, replacement of defective lugs, thimbles etc., replacement of defective parts, through cleaning of panel both internally and externally, re-interconnection of parts including reconnection of all incoming and outgoing electrical connections after repairs, testing and commissioning complete all as specified and as directed. Notes: (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer-In-Charge. (ii) Spare parts for replacement will be measured and paid seperately. |
| 2 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 5 kVAr, 440 V, complete all as specified and as directed. Make: L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 3 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours, rating 7.5 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 4 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours, rating 10 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 5 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours, rating 12.5 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 6 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours, rating 15 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 7 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours, rating 20 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 8 | Supply only power factor correction capacitors,box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours, rating 25 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. |
| 9 | Supply only capacitor duty contactors, type MO C5, built in auxillary contacts 1NO, rating 5 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No.CS96127 or equivalent model of make as specified in Particular Specifications |
| 10 | Supply only capacitor duty contactors, type MO C8.5, built in auxillary contacts 1NO, rating 8.5 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No.CS96320 or equivalent model of make as specified in Particular Specifications |
| 11 | Supply only capacitor duty contactors, type MO C10, built in auxillary contacts 1NO, rating 10 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No.CS96156 or equivalent model of make as specified in Particular Specifications. |
| 12 | Supply only,capacitor duty contactors, type MO C12.5, built in auxillary contacts 1NO, rating 12.5 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No.CS96321 or equivalent model of make as specified in Particular Specifications. |
| 13 | Supply only capacitor duty contactors, type MO C15, built in auxillary contacts 1NO, rating 15 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No. CS90019 or equivalent model of make as specified in Particular Specifications. |
| 14 | Supply only capacitor duty contactors, type MO C20, built in auxillary contacts 1NO, rating 20 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No. CS90021 or equivalent model of make as specified in Particular Specifications. |
| 15 | Supply only capacitor duty contactors, type MO C25, built in auxillary contacts 1NO, rating 25 kVAr, 440 V, 3 phase, 50 Hz complete all as specified and as directed. Make : L&T, Cat Part No. CS96321 or equivalent model of make as specified in Particular Specifications |
| 16 | Supply only LED indicator 16mm with power consumption < 0.6W, LVGP & surge protection, 64/110 volts AC/DC / 240 volts AC, colour Red/Green/Yellow/Blue complete all as specified and as directed. Make : L&T, Cat Part No. SIL or equivalent model of make as specified in Particular Specifications. |
| 17 | Supply only APFC controller for contactor switching with 1 CT input 1/5 amp, 415 V, 8 steps (For Contactor Switching) complete all as specified and as directed. Make : L&T, Cat Part No. CS90902OOOO or equivalent model of make as specified in Particular Specifications. . |
| 18 | Supply only 3 Phase LED voltmeter, accuracy class 1.0, input voltage measurement range 50-550 VAC (P-P), Aux supply 80-300 VAC, CT secondary site selectable 1A / 5A, flush mounting 96x96mm, with inbuilt selector switch complete all as specified and as directed. Make : L&T, Cat Part No. WL132010OOOO or equivalent model of make as specified in Particular Specifications. |
| 19 | Supply only 3 phase LED ammeter, accuracy class 1.0, Aux supply 80-300 VAC, CT secondary site selectable 1A / 5A, flush mounting 96x96mm, with inbuilt selector switch complete all as specified and as directed. Make : L&T, Cat No. WL131010OOOO or equivalent model of make as specified in Particular Specifications. |
| 20 | Supply only miniature circuit breaker (MCBs) three pole and neutral, 240 volts, 10KA, 40 to 63 amps complete all as specified and as directed. Make : L&T, Cat Part No. BB40400C/BB40500C/BB40630C or equivalent model of make as specified in Particular Specifications. |
| 21 | Disconnection of existing Air Circuit Breakers (ACBs), 3 pole/4 pole, manually/electrically operated, fixed/draw-out type, AC 440 volts, breaking capacity 50-100 kA, rated current 800-2000 amps, form all incoming and outgoing electrical connections, checking serviceability of each components viz. ON/OFF button, CTs, tripping coil, shunt trip device, auxillary switches, locking arrangement, safety shutter, arc shield, etc., and replacement of defective lugs, thimbles, defective parts, through cleaning of ACB both internally and externally, reassembling of parts including reconnection of all incoming and outgoing electrical connections after repairs, testing and commissioning complete all as specified and as directed. Notes:- (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer-In-Charge. (ii) Spare Parts for replacement will be measured and paid seperately. |
| 22 | Supply only Locable Trip Push Button (LTPB) complete all as per OEM's specifications and as directed. |
| 23 | Supply only Locable Trip Push Button Kit (3IC & 2 BC), complete all as per OEM's specifications and as directed. |
| 24 | Supply only Locking of ACB in Isolated Position (LIP) type C, complete all as per OEM's specifications and as directed. |
| 25 | Supply only Locking of ACB in any Position (LAP) type C, complete all as per OEM's specifications and as directed. |
| 26 | Supply only Racking interlock type CC, complete all as per OEM's specifications and as directed. |
| 27 | Supply only Racking Padlock Assembly, complete all as per OEM's specifications and as directed. |
| 28 | Supply only Door Interlock, complete all as per OEM's specifications and as directed. |
| 29 | Supply only Mechanical operation counter, complete all as per OEM's specifications and as directed. |
| 30 | Supply only Mounting Kit for Front mounted counter in repair complete all as per OEM's specifications and as directed. |
| 31 | Supply only Shunt release, complete all as per OEM's specifications and as directed. |
| 32 | Supply only under voltage release, complete all as per OEM's specifications and as directed. |
| 33 | Supply only Earth fault Release, complete all as per OEM's specifications and as directed. |
| 34 | Supply only vertical terminal adaptors for draw out ACB, complete all as per OEM's specifications and as directed. |
| 35 | Supply only electronic timer adjustable type from 3 to 30 sec, Complete all as per OEM's specifications and as directed. Please Enable Macros to View BoQ information |
| 36 | Supply only electronic timer adjustable type from 3 to 30 sec, Complete all as per OEM's specifications and as directed. Please Enable Macros to View BoQ information |