| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GARRISON ENGINEER (AF) BANGALORE NAME OF WORK :REPAIR/MAINT OF WATER SUPPLY DISTRIBUTION AT POCKET II, REPAIR/MAINT OF RO PLANTS , CLEANING OF OHT, SEMI UG SUMPS, RCC/PVC TANKS AND CONNECTED WORKS AT CHAF CA NO: GE(AF)/B/ OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | COMMON ITEMS APPLICABLE FOR 'JOB A' & 'JOB B' & JOB'C' |
| 3 | S&F GI tubing medium grade laid in trenches in any length with screwed and socket joints together with all galvanised steel fitting such as sockets, bends, elbows, tees, reducers, union etc, including jointing and testing complete all as specified and directed for following sizes:- |
| 4 | 15 mm bore |
| 5 | 20 mm bore |
| 6 | 25 mm bore |
| 7 | 40 mm bore |
| 8 | 50 mm bore Sl no 6.05 of JOB A+ Sl no 20 of JOB B |
| 9 | S&F in replacement CPVC pipes of 50mm dia,having thermal stability for hot & cold water supply,including all CPVC plain and brass threaded fittings including jointing of pipes & fittings with CPVC solvent cement and testing of joints complete all as specified and directed. |
| 10 | S&F in replacement CPVC pipes of 40mm dia,having thermal stability for hot & cold water supply,including all CPVC plain and brass threaded fittings including jointing of pipes & fittings with CPVC solvent cement and testing of joints complete all as specified and directed. |
| 11 | S&F in replacement of MCCB 160 Amps MCCB ,3 pole, 36 KA rupturing capacity in the existing panel with necessary modification if reqd all as specified and directed |
| 12 | All as per item No- 5.00 here-in-before but 125 Amps MCCB ,3 pole, 16 KA rupturing capacity |
| 13 | All as per item No- 5.00 here-in-before but 25 to 100 Amps MCCB ,3 pole, 16 KA rupturing capacity |
| 14 | ITEMS APPLICABLE FOR 'JOB A' |
| 15 | Excavation of trenches in any type of soil not exc 1.5 m wide and not exc 1.5 min depth for taking out / laying of pipe lines and getting out forming bottom surfaces to required gradients Soft/loose soil complete all as specified and as directed . |
| 16 | Returning, filling in and including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed. |
| 17 | Removing excavated surplus materials to a distance not exceeding 50 Mtrs and deposited where directed at a level not exceeding 1.5 m above starting point complete all as specified and directed. |
| 18 | Taking up or down G.I. tubing and connection and stacking neatly for reuse and removing the balance material from site complete all as specified and directed for the following sizes :- |
| 19 | 15 mm bore |
| 20 | 20 mm bore |
| 21 | 25 mm bore |
| 22 | 40 mm bore |
| 23 | 50 mm bore |
| 24 | Refixing only of old GI tubing obtained from Item No 17.00 here-in-before and connections in new or old position (walls, trenches, ceiling and floors etc.) for the following sizes complete all as specified and directed |
| 25 | 15 mm bore |
| 26 | 20 mm bore |
| 27 | 25 mm bore |
| 28 | 40 mm bore |
| 29 | 50 mm bore |
| 30 | S&F GI tubing medium grade 80 mm bore laid in trenches in any length with screwed and socket joints together with all galvanised steel fitting such as sockets, bends, elbows, tees, reducers, union etc, including jointing and testing complete all as specified and directed. |
| 31 | S&F in replacement of CI Non Return Valve of size 50 mm bore flanged type and including jointing materials, rubber gasket suitable size nuts bolts and washers etc including taking down of old unsv complete all as specified and directed. |
| 32 | S&F in replacement of CI Non Return Valve of size 80 mm bore flanged type and including jointing materials, rubber gasket, suitable size of nuts bolts and washers etc including taking down of old unsv complete all as specified and directed |
| 33 | S&F in replacement of CI Non Return Valve of size 100 mm bore flanged type and including jointing materials, rubber gasket, suitable of size nuts bolts and washers etc including taking down of old unsv complete all as specified and directed |
| 34 | S&F in replacement of CI Non Return Valve of size 150 mm bore flanged type and including jointing materials, rubber gasket, suitable size of nuts bolts and washers etc including taking down of old unsv complete all as specified and directed |
| 35 | S&Fin replacement of gun metal valve of size 15 mm bore with iron wheel head screwed both ends suitable for GI tubing including taking down of old unsv one complete all as specified and as directed. |
| 36 | S&F in replacement of gun metal valve of size 20 mm bore with iron wheel head screwed both ends suitable for GI tubing including taking down of old unsv one complete all as specified and as directed. |
| 37 | S&F in replacement of gun metal valve of size 25 mm bore with iron wheel head screwed both ends suitable for GI tubing including taking down of old unsv one complete all as specified and as directed. |
| 38 | S&F in replacement of gun metal valve of size 40 mm bore with iron wheel head screwed both ends suitable for GI tubing including taking down of old unsv one complete all as specified and as directed. |
| 39 | S&F in replacement of gun metal valve of size 50 mm bore with iron wheel head screwed both ends suitable for GI tubing including taking down of old unsv one complete all as specified and as directed. |
| 40 | M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate in floorings for repairs of the plinth protection,foot paths closing pipe holes in walls or any other location of the tanks after dressing/cleaning the disturbed/damaged surface and freshing top surface fair and even complete all as specified and as directed. |
| 41 | S&F in replacement HDPE pipes of 50 mm dia,having pressure rating of pipe 6 kgf/cm2 lowering into the borewell including all T&P and vehicle with all necessary fittings required and taking down of old unsv pipe complete all as specified and directed. |
| 42 | S&F in replacement of MCCB 250 Amps, 3 pole, 36 KA rupturing capacity in the existing panel with necessary modification if reqd complete all as specified and directed. |
| 43 | All as per item No 41.00 here-in-before but of capacity of 250 Amps MCCB , 4pole, 36 KA rupturing capacity |
| 44 | All as per item No 41.00 here-in-before but of capacity of 200 Amps MCCB , 4pole, 36 KA rupturing capacity |
| 45 | All as per item No 41.00 here-in-before but of capacity of 200 Amps MCCB ,3 pole, 36 KA rupturing capacity |
| 46 | S&F CI fittings for spigot and socket ends for pressure pipe for water mains such as bends, tapers, tee pieces single branch, cross collar, caps and plugs suitable for upto 150 mm bore, all specifications as per IS-1538 (Pt-1 to 23)-1976 and all as specified and directed. |
| 47 | Supply fabrication and fixing MS joints like Flanged, bends, Tee, Tapers, collars, elbow, tail piece (any type) caps, plugs for 80 mm to 300 mm bore pipe complete all as specified and directed. |
| 48 | S&F in replacement DI pipes,of size 150 mm bore ,class K-7, with spigot and socketed ends centrifugally cast (spun) with factory applied cement mortar lining inside the pipes and outside with zinc coating with suitable push on joint (Rubber gasket D joint) confirming to IS 8329/2000 and connected items complete all as specified and directed. |
| 49 | Construction of valve chamber in repairs of size 60x60x60cm of brick masonry valve pit of internal size 60x60x60cm with 230mm thick brick wall built in cement mortar 1:6, plain cement concrete foundation 1:4:8 type D2, plastering on brick surfaces 15mm thick in cement mortar 1:4 covered with MS plain sheet 3 mm thick duly fixed to MS frame size 40x40x6mm and duly embedded in plain cement concrete coping 5 cm thick plain cement concrete 1:2:4 type B1 with opening and locking arrangements including painting with two coats of synthetic enamel paint over one coat of primer including demolition of old damaged valve chamber complete all as specified and directed. |
| 50 | Construction of valve chamber in repairs of size 90x90x90cm of brick masonry valve pit of internal size 90x90x90cm with 230mm thick brick wall built in cement mortar 1:6, plain cement concrete foundation 1:4:8 type D2, plastering on brick surfaces 15mm thick in cement mortar 1:4 covered with MS plain sheet 3 mm thick duly fixed to MS frame size 40x40x6mm and duly embedded in plain cement concrete coping 5 cm thick plain cement concrete 1:2:4 type B1with opening and locking arrangements including painting with two coat of synthetic enamel paint over one coat of primer including demolition of old damaged valve chamber complete all as specified and directed. |
| 51 | S&F Sluice valve of size 80 mm class PN-I.6 (ISI) marked with flanged and iron wheel head, SS spindle, shut and open directed cast on it and including jointing materials, rubber gasket suitable size nut bolts and washer etc complete all as specified and directed. |
| 52 | S&F Sluice valve of size 100 mm class PN-I.6 (ISI) marked with flanged and iron wheel head, SS spindle, shut and open directed cast on it and including jointing materials, rubber gasket suitable size nut bolts and washer etc complete all as specified and directed |
| 53 | S&F Sluice valve of size 150 mm class PN-I.6 (ISI) marked with flanged and iron wheel head, SS spindle, shut and open directed cast on it and including jointing materials, rubber gasket suitable size nut bolts and washer etc complete all as specified and directed |
| 54 | S&F Sluice valve of size 200 mm class PN-I.6 (ISI) marked with flanged and iron wheel head, SS spindle, shut and open directed cast on it and including jointing materials, rubber gasket suitable size nut bolts and washer etc complete all as specified and directed |
| 55 | Supply only traditional calcium hypochlorite based Granular disinfectant for water treatment packed in 45 kg plastic Drum complete all as specified and directed. |
| 56 | S&F in replacement CI body ISI marked foot valves of size 40 to 50mm one end flanged and other end CI Jallies with neoprene ball duly tested and confirming to IS including taking out existing unsv foot valve complete all as specified and directed. |
| 57 | S&F in replacement CI body ISI marked foot valves of size 65 to 80mm one end flanged and other end CI Jallies with neoprene ball duly tested and confirming to IS including taking out existing unsv foot valve complete all as specified and directed. |
| 58 | S&F in replacement CI body ISI marked foot valves of size 100 mm one end flanged and other end CI Jallies with neoprene ball duly tested and confirming to IS including taking out existing unsv foot valve all as specified and directed. |
| 59 | Dismantling the unserviceable gaskets and S&F new gaskets for replacing of Sluice valve / Pump set of any Size or capacity complete all as specified and as directed. |
| 60 | Supply and connecting PVC insulated sheathed cable with multi stranded submersible copper conductor of size 3 core 6 sqmm for pump set including removing the old unservsible cable complete all as specified and directed. |
| 61 | M&L for Leakage detection in the GI water mains not exc 80mm dia and necessary repairs including cutting threading for addition/alteration for insertion if required any of fittings complete all as specified and directed. Note : The rate quoted by the contractor shall be deemed to be inclusive of earth work/excavation and returning filling. |
| 62 | M&L for total painting of inlet water supply pipe line any size any length and delivery pipe line including motor pump/ foundation at fire fighting pump /water supply pump house as per approved colour complete all as specified and directed. |
| 63 | M&L for complete scrapping of old rusted paint and painting with super enamelled paint of MS pipe for fire fighting system/sprinklers system complete with all arrangement of T&P required for the same as per approved colour complete all as specified and directed for following dia of pipes :- |
| 64 | 80 mm bore |
| 65 | 100 mm bore |
| 66 | 150 mm bore |
| 67 | ITEMS APPLICABLE FOR 'JOB B' |
| 68 | M&L for servicing of semi automatic RO plant 500 Ltr per hr installed at OT including mono block pump sets of 0.5 H.P capacity - 02 Nos complete for trouble free operation by checking of all parts, cleaning and backwashing of filter media of all units/ membranes, arresting of leakages and checking quality of water and keeping the plant in serviceable condition to provide the acceptable quality standard parameters as required all as specified by manufacturers complete all as specified and directed.Note: (i) Servicing shall be carried out through authorised service dealer of M/s ION EXCHANGE INDIA LTD or from any other authorised service dealer as approved by GE. (ii) Spares required to be chnaged and chemicals required to be used in servicing shall be measured and paid seperately |
| 69 | S&F in replacement of 2x5 micron cartridge filter for RO plant as required for servicing under Sl Item No 49.00 above including taking out existing unserviceable filter complete all as specified and directed. |
| 70 | Supply & fill antiscalent chemical for RO plant as required for servicing under Sl Item No 49.00 above complete all as specified and directed. |
| 71 | Supply & fill membrane cleaning chemical (6Kg/3month) for RO plant as required for servicing under Sl Item No 49.00 above complete all as specified and directed. |
| 72 | S&F in replacement filtering sand fine for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 73 | S&F in replacement Activated carbon filter for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 74 | S&F in replacement RO Membrane for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 75 | S&F in replacement sand media for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 76 | S&F in replacement activated carbon for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 77 | S&F in replacement dosing pump for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 78 | S&F in replacement 4040 membrane for RO plant as required for servicing under Sl Item No 49.00 complete all as specified and directed. |
| 79 | Dismantling electric driven induction motor of capacity 1 HP 230 volt, single phase 50 HZ of RO plant shifting to local work shop taking out the burnt windings, cleaning of slots and rewinding the same with copper winding wire of existing gauge and quantity heating applying shellac varnish to the windings, replacing insulating materials as required baking up and assembling back including replacing the bearings bushes using hydraulic pressure complete all as specified and directed. |
| 80 | Dismantling electric driven induction motor of capacity 2 HP 230 volt, single phase 50 HZ of RO plant shifting to local work shop taking out the burnt windings, cleaning of slots and rewinding the same with copper winding wire of existing gauge and quantity heating applying shellac varnish to the windings, replacing insulating materials as required baking up and assembling back including replacing the bearings bushes using hydraulic pressure complete all as specified and directed. |
| 81 | Collection of raw/treated water samples and carryout following tests from approved laboratory and submitting the test report result including necessary transportation complete all as specified and directed :-(a) Micro biological test (Total coliforms, Thermotolerant coliforms of E. coli)(b) Chemical quality test (Aluminium, Cadmium,, Chloride, Copper, Total Iron, Lead, Nickel, Nitrate, Nitrite, Sodium, Sulphate, Zinc,, Alkalinity, Calcium, conductivity, Colour, hardness, Magnesium, pH, Potassium, Total disolved solids, Total suspended solids, Turbidity, Ammonia, Antimony, Arsenic, Barium, Boron, Chromium, Total cynide, Fluoride, Hydrogen sulfide, Maganese, Molybdenum, Selenium, silver, Tin, Uranium) |
| 82 | S&F in replacement Direct-on-line (DOL) starter in sheet steel enclosure for single phase 1 to 2 HP complete all as specified and directed.(Make : Lauritz Knudsen (Formerly L&T) type MF-1 single phase or Techno-commercially equivalent in Crompton Greaves/Siemens /GE) |
| 83 | S&F in replacement CPVC pipes of 20mm dia,having thermal stability for hot & cold water supply,including all CPVC plain and brass threaded fittings including jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete all as specified and directed. |
| 84 | S&F in replacement CPVC pipes of 25 mm dia,having thermal stability for hot & cold water supply,including all CPVC plain and brass threaded fittings including jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete all as specified and directed. |
| 85 | S&F in replacement ball valve size 50 mm dia for CPVC pipes of 50 mm dia complete all as specified and directed. |
| 86 | S&F in replacement ball valve size 40 mm dia for CPVC pipes of 40 mm dia complete all as specified and directed. |
| 87 | S&F in replacement ball valve size 25 mm dia for CPVC pipes of 25 mm dia complete all as specified and directed. |
| 88 | S&F in replacement ball valve size 20 mm dia for CPVC pipes of 20 mm dia complete all as specified and directed. |
| 89 | S&F in replacement Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position Of capacity 1000 ltrs all as specified in SSR Part I complete all as specified and directed. |
| 90 | S&F in replacement Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position Of capacity 2000 ltrs all as specified in SSR Part I complete all as specified and directed. |
| 91 | S&F of ball valves high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for iron pipe an of 20 mm dia fixed for the following sizes including taking out existing unserviceable complete all as specified and directed.(Minimum weight 15 mm -142 gms/20 mm - 20 gms/25 mm - 455 gms/40 mm - 690 gms) |
| 92 | S&F of ball valves high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for iron pipe an of 25 mm dia fixed for the following sizes including taking out existing unserviceable complete all as specified and directed.(Minimum weight 15 mm -142 gms/20 mm - 20 gms/25 mm - 455 gms/40 mm - 690 gms) |
| 93 | S&Fof ball valves high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for iron pipe an of 40 mm dia fixed for the following sizes including taking out existing unserviceable complete all as specified and directed.(Minimum weight 15 mm -142 gms/20 mm - 20 gms/25 mm - 455 gms/40 mm - 690 gms) |
| 94 | Disconnecting existing water tanks capacity 1000 ltrs setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and re-fixing in position and cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc complete all as specified and directed. |
| 95 | Disconnecting existing water tanks capacity 2000 ltrs setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and re-fixing in position and cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc complete all as specified and directed. |
| 96 | ITEMS APPLICABLE FOR 'JOB C' |
| 97 | Dewatering, removing all mosses, algae and dirt from internal walls, floors & mouths of pipes of RCC overhead reservoir/ under ground sump by using steel wire brush and cleaning with high pressure industrial vacuum cleaner including removing of dirty water completely using sludge pump set and disposing off the same to a safe distance and applying of anti bacterial sterilization spray to internal surfaces using Zero bacterial compound (Sodium hypochlorte) or equivalent approved chemical complete and writing the date of cleaning on outside of tank/ sump using synthetic enamel paint of white colour over black background with letters of size 100mm height x 100mm breadth complete all as specified and directed for the OH Reservoir of 75000 Gallons capacity with 24 metre staging, complete all as specified and directed. |
| 98 | All as per Sl item No 78.00 here-in-before but for Overhead reservoir 50,000 Gallons capacity with staging exceeding 15 metres and not exceeding 24 metres complete all as specified and directed. |
| 99 | All as per Sl item No 78.00 here-in-before but for Overhead reservoir 15,000 Gallons capacity with 6 metres staging complete all as specified and directed. |
| 100 | All as per Sl item No 78.00 here-in-before but for Overhead reservoir 5000 Gallons capacity with staging of 6 metres complete all as specified and directed. |
| 101 | All as per Sl item No 78.00 here-in-before but for UG sump 2,00,000 Gallons capacity complete all as specified and directed. |
| 102 | All as per Sl item No 78.00 here-in-before but for UG sump 1,50,000 Gallons capacity complete all as specified and directed. |
| 103 | All as per Sl item No 78.00 here-in-before but for UG sump 1,25,000 Gallons capacity complete all as specified and directed. |
| 104 | All as per Sl item No 78.00 here-in-before but for UG sump 20,000 Gallons capacity complete all as specified and directed. |
| 105 | All as per Sl item No 78.00 here-in-before but for UG sump 25,000 Gallons capacity complete all as specified and directed. |
| 106 | All as per Sl item No 78.00 here-in-before but for UG sump 10,000 Gallons capacity complete all as specified and directed. |
| 107 | M&L for Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6.00mm thick burried directly in ground (earth pit not less than 2.25 meter deep below normal ground level with top edge of earth plate not less than 1.5 m below the normal ground level) connected to galvanised iron strip 25 x 4mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in elelctrical plalte No 3 including charcoal dust, commen salt, 20mm bore GI medium grade watering pipe, 40mm dia GI light grade protection pipe with funel and wire mesh, PCC Pit in 1:2:4 type B 1 using 20mm graded stone aggregate with angle iron 40x40x5mm frame, RCC pit cover of suitable size complete all as specified and directed by engineer encharge and testing for required value complete all as specified and directed.Note :- (i) Item rate shall include the cost of earth lead and GI protection pipe upto 7.5 mtr length. (ii) On completion of Earthing Contractor should check Earthing Results and submit the Test Report to Engr-in-charge. If desired results are not obtained then Earthing shall be redone by the contractor at his own cost. |
| 108 | M&L for angle iron/MS plate including nuts,bolts,washers, welding,drilling holes for bolts in any shape or size as indicated or directed of making staging of the tank and painting with one coat of red oxide zinc chrome primer, over one finishing coat of aluminium paint complete all as specified and directed. |
| 109 | M&L Plain cement concrete 1:2:4 type B1 using 20 mm graded stone aggregate as in coping including use and waste of form work complete all as specified and directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |