| 1 | Taking down carefully copper/ aluminium point wiring for light, fan, socket or power including removing materials to store for keeping in safe custody or for taking credit and making good disturbed surface of walls, floors etc. complete all as specified and directed by Engineer-in-Charge. |
| 2 | M&L for cutting chases, pinning in brick wall, making good to facings where required and pointing in cement mortar (1:3) to ends or edges of landings, steps, cills, sun shades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc. and making good, cutting exceeding 20cm girth complete all as speicified and as directed. |
| 3 | M&L for cutting chases, pinning in concreate/ stone wall, making good to facings where required and pointing in cement mortar (1:3) to ends or edges of landings, steps, cills, sun shades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc. and making good, cutting exceeding 20cm girth complete all as speicified and as directed. |
| 4 | M&L for point wiring for one flame proof light point/ flame proof fans/ flame proof exhaust fans point controlled by one flame proof rotary switch 6/10/16 Amp complete with 1.5 Sqmm PVC insulated but unsheathed multistranded copper conductor FRLS cable 1100 Volts grade IS-694 (Phase - Red/ Blue/ Yellow, Netural - Black and earth continuity conductor 1.50 Sqmm Green) drawn through stove enameled steel conduit of dia not less than 20x12mm ISI marked, ivory colour including accessories like bends, tees junction boxes, etc. fixed on wall or ceiling etc. including 1.5 Sqmm, single core, PVC insulated but unsheathed multi stranded copper conductor FRLS cable 1100 Volts grade as earth continuity wire including sunken type pressed steel terminal boxes of suitable size white sheet cover for mounting swiches, sockets, fan regulators etc. complete all as specified and directed.Note:- Necessary chases cuttings for concealed wiring and making a good of distrubed surfaces shall be measured and paid under relevant items. |
| 5 | All as per item No. 04 above but with 2.5 Sqmm cable for independent one 6 pin 6/16/32 Amps socket outlet in and including 2.5 Sqmm PVC insulated copper conductor unsheathed 1100 V grade IS - 694 FRLS cable for continuous earth wire. |
| 6 | S&F in repair flame proof rotary switch current rating : 16 Amps, 230 Volts for industrial use, number pole: two switch positions 5 to 8, 2 to 4 with IP 66 suitable at gases/ fire hazardious areas complete all as specified and directed. |
| 7 | S&F in repair industrial type flame proof switch plug and socket 16 Amps, 3/5 pin, electrical rating 16 Amp, 3 pin/ 5 pin - (Phase 3 + Neutral 1 + Earth 1), weather proof alongwith IP 66 suitable at gases/ fire hazardious areas, gasket- 'O' ring endless neoprene, material - cast aluminium alloy LM-6 complete all as specified and directed. |
| 8 | S&F in repair industrial type flame proof switch plug and socket 32 Amps, 3/5 pin, electrical rating 32 Amp, 3 pin/ 5 pin - (Phase 3 + Neutral 1 + Earth 1), weather proof alongwith IP 66 suitable at gases/ fire hazardious areas, gasket- 'O' ring endless neoprene, material - cast aluminium alloy LM-6 complete all as speicified and as directed. |
| 9 | Supply and draw submain wiring with two single core 6 Sqmm FRLS PVC insulated copper cable 1100 Volts grade multistrand, unseathed conductor drawn into stove enamelled steel conduit and all necessary fittings including 6 Sqmm multi strand FRLS PVC insulated copper wire for earth continuty conductor connected to common earth dully complete including taking down old unserviceable submain wiring of any size and making good disturbed surface complete all as specified and directed. |
| 10 | All as per Item No. 09 above but two single core 4.0 Sqmm for phase and neutral and 01 single core 4 Sqmm for earth wire. |
| 11 | All as per Item No. 09 above but two single core 2.5 Sqmm for phase and neutral and 01 single core 2.5 Sqmm for earth wire. |
| 12 | All as per Item No. 09 above but two single core 1.5 Sqmm for phase and neutral and 01 single core 1.5 Sqmm for earth wire. Please Enable Macros to View BoQ information |
| 13 | All as per Item No. 09 above but two single core 1.5 Sqmm for phase and neutral and 01 single core 1.5 Sqmm for earth wire. Please Enable Macros to View BoQ information |